Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ▷ View online
Mini VRF SYSTEM
Self-Diagnostics Function Table
5
Contents
5-1
5. Self-Diagnostics Function Table
1. Self-Diagnostics Function Table ........................................................................................ 5-2
SM830196-03_Mini_VRF SYS.indb 1
SM830196-03_Mini_VRF SYS.indb 1
2014/09/04 15:34:10
2014/09/04 15:34:10
Mini VRF SYSTEM
Self-Diagnostics Function Table
5
1. Self-Diagnostics Function Table
5-2
Self-Diagnostics Function Table
• Causes and corrections in instances when automatic address setting cannot be started.
Trouble
Cause and correction
The power LED on the outdoor unit control PCB does
not turn ON.
not turn ON.
Check for any errors in the power wiring to the outdoor
unit, and check for a missing phase.
unit, and check for a missing phase.
LED 1 and 2 on the outdoor unit control PCB do not
turn OFF when the outdoor unit power is turned ON,
and automatic address setting cannot be started.
turn OFF when the outdoor unit power is turned ON,
and automatic address setting cannot be started.
Check the “Alarm Displays” table and correct the
problem.
problem.
An alarm appears immediately when automatic
address setting is started from the remote controller.
address setting is started from the remote controller.
Nothing happens when the operator attempts to start
automatic address setting from the remote controller.
automatic address setting from the remote controller.
Check that the remote controller wiring and the inter-
unit control wiring are connected correctly.
Check that the indoor unit power is ON.
unit control wiring are connected correctly.
Check that the indoor unit power is ON.
• Causes and corrections in instances when automatic address setting starts, but cannot be completed successfully.
Trouble
Cause and correction
An alarm appears on the remote controller sometime
from several seconds to several minutes after
automatic address setting is started.
from several seconds to several minutes after
automatic address setting is started.
Check the “Alarm Displays” table and correct the
problem.
problem.
LED 1 and 2 on the outdoor unit control PCB indicate
that automatic address setting is in progress (the LEDs
blink alternately) for several minutes after automatic
address setting is started (the compressors may also
start and stop several times), however LED 1 and
2 never indicate that automatic address setting is
completed (turn OFF).
that automatic address setting is in progress (the LEDs
blink alternately) for several minutes after automatic
address setting is started (the compressors may also
start and stop several times), however LED 1 and
2 never indicate that automatic address setting is
completed (turn OFF).
Check the alarm details on the “Outdoor Unit Control
PCB LED 1 and 2 Alarms” table, then check the “Alarm
Displays” table and correct the problem.
PCB LED 1 and 2 Alarms” table, then check the “Alarm
Displays” table and correct the problem.
• If alarm E15, E16, or E20 appears after automatic address setting is started, check the following items.
Alarm display
Alarm description
E15
The number of indoor units detected during automatic address setting was smaller than the
number of indoor units which was set with switch S004 on the outdoor unit PCB.
number of indoor units which was set with switch S004 on the outdoor unit PCB.
E16
The number of indoor units detected during automatic address setting was larger than the
number of indoor units which was set with switch S004 on the outdoor unit PCB.
number of indoor units which was set with switch S004 on the outdoor unit PCB.
E20
The outdoor unit received no serial signals from indoor units within 90 seconds after
automatic address setting was started.
automatic address setting was started.
SM830196-03_Mini_VRF SYS.indb 2
SM830196-03_Mini_VRF SYS.indb 2
2014/09/04 15:34:17
2014/09/04 15:34:17
Mini VRF SYSTEM
Self-Diagnostics Function Table
5
1. Self-Diagnostics Function Table
5-3
Check items
E15 E16 E20
Check that the indoor unit power is turned ON.
Check that the inter-unit control wiring is connected correctly. (Check that there are no open
circuits, short circuits, terminal plugs, incorrect wiring to the remote controller terminals, or
similar problems.)
circuits, short circuits, terminal plugs, incorrect wiring to the remote controller terminals, or
similar problems.)
Check that the remote controller wiring is connected correctly. (Check that there are no open
circuits, short circuits, incorrect wiring to the inter-unit control wiring terminals, group control
communication wiring, or similar problems.)
circuits, short circuits, incorrect wiring to the inter-unit control wiring terminals, group control
communication wiring, or similar problems.)
Check that the number of indoor units has been set correctly using switch S004 on the
outdoor unit control PCB.
outdoor unit control PCB.
Check that the amount of additional refrigerant charge is correct (if automatic address setting
is performed with the compressors ON).
is performed with the compressors ON).
Check that the refrigerant tubing connections are correct (if automatic address setting is
performed with the compressors ON).
performed with the compressors ON).
Check that there are no problems with indoor unit sensors E1 and E3 (if automatic address
setting is performed with the compressors ON).
setting is performed with the compressors ON).
Check that there are no indoor units where the system address was already incorrectly set by
manual or automatic address setting.
manual or automatic address setting.
• When automatic address setting is started from the outdoor unit control PCB or from the remote controller,
(SETTING) appears on the remote controller at units where the inter-unit control wiring and remote
controller wiring are connected correctly. LED 1 and 2 on the outdoor unit control PCB blink alternately.
• In the case of indoor unit group control, if there is a mistake in the remote controller communication wiring,
addresses may not be set even if
(SETTING) appears.
• Even if alarm E15 or E16 appears, addresses are set at those indoor units which could be verifi ed. The set
addresses can be checked using the remote controller.
• If one of the below alarms appears when the remote controller is operated after automatic address setting was
completed (LED 1 and 2 on the outdoor unit control PCB are turned OFF), follow the instructions in the table
below and correct the problem location.
below and correct the problem location.
Remote
controller display
Cause
Nothing is
displayed.
The remote controller is not connected correctly (power trouble).
The indoor unit power was cut off after automatic address setting was completed.
The indoor unit power was cut off after automatic address setting was completed.
E01
The remote controller is not connected correctly (remote controller receiving trouble).
The remote controller of an indoor unit where the indoor unit address is not set is inadvertently
operated. (Communications with the outdoor unit are not possible.)
The remote controller of an indoor unit where the indoor unit address is not set is inadvertently
operated. (Communications with the outdoor unit are not possible.)
E02
The remote controller is not connected correctly (trouble with sending of the signal from the
remote controller to the indoor unit).
remote controller to the indoor unit).
E09
The indoor unit ceiling panel connector is not connected correctly.
SM830196-03_Mini_VRF SYS.indb 3
SM830196-03_Mini_VRF SYS.indb 3
2014/09/04 15:34:17
2014/09/04 15:34:17
Mini VRF SYSTEM
Self-Diagnostics Function Table
5
1. Self-Diagnostics Function Table
5-4
The outdoor unit maintenance remote controller can be used to check the alarm display.
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm
display. (Refer to “Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.”)
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm
display. (Refer to “Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.”)
•
Alarm
Code
Code
Alarm Meaning
E01
E02
E03
E04
E05
E06
Error in the Outdoor Unit Receiving Signal from the Indoor Unit
Error in Indoor Unit Transmitting Signal to the Outdoor Unit
Error in Indoor Unit Receiving Signal from the Outdoor unit
Error in Indoor Unit Receiving Signal from Remote Controller (central)
Remote Controller Transmission Error
Remote Controller Reception Error
E07
E08
E09
E12
E13
E15
Auto-Address Alarm (not enough units)
Error in Indoor Unit Transmitting Signal to Remote Controller
Start of Auto Address Setting Prohibited Due to Auto Address Setting Being in Progress
More Than One Remote Controller Set to Main Error
E16
E18
E20
E30
Outdoor Unit Serial Transmission Error
No Indoor Units Error
Faulty Communication in Group Control Wiring
Auto-Address Alarm (too many units)
F04
F07
Heat Exchanger Inlet Temperature Sensor (C1) Error
Compressor Discharge Temperature Sensor Error
F08
F12
F16
F31
Outdoor Unit Nonvolatile Memory (EEPROM) Error
High Pressure Sensor Error
Compressor Intake Temperature Sensor (TS) Error
Outdoor Air Temperature Sensor (TO) Error
H01
H02
H03
H31
HIC Error
Compressor CT Sensor (Current Sensor) Unplugged
L04
L10
Outdoor Unit Capacity Not Yet Setup Error
L18
4-way valve operation failure
Duplicated Setting of Outdoor System Address Error
PAM Error
Primary Current (Input) Detect of Overcurrent
Duplicate Indoor Unit Address Settings Error
Error in Outdoor Unit Transmitting Signal to the Indoor Unit
P03
P04
P05
P13
P14
P16
Overcurrent of Inverter Compressor
O
2
Sensor
Forgot-to-open Valve Alarm
Power Supply Error
Actuation of High Pressure Switch
Compressor Discharge Temperature Error
P22
P29
INV Compressor Start-up Failed (including lock) Due to INV Compressor Wiring Open Phase, Faulty DCCT, etc.
Outdoor Fan Motor Error
SM830196-03_Mini_VRF SYS.indb 4
SM830196-03_Mini_VRF SYS.indb 4
2014/09/04 15:34:17
2014/09/04 15:34:17
Click on the first or last page to see other U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 service manuals if exist.