16.4.26. F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61
° C) is detected by the outdoor pipe
temperature sensor.
Malfunction Caused
• Outdoor pipe temperature rise due to short circuit of hot discharge air flow.
• Outdoor pipe temperature rise due to defective of outdoor fan motor.
• Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor.
• Outdoor pipe temperature rise due to defective outdoor unit PCB.
Troubleshooting
94
16.4.27. F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling and heating, when IPM temperature data (100
° C) is detected by the IPM temperature sensor.
Multi Models Only
• Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated.
• Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90
° C) is detected by the
heat sink temperature sensor.
Malfunction Caused
• IPM overheats due to short circuit of hot discharge air flow.
• IPM overheats due to defective of outdoor fan motor.
• IPM overheats due to defective of internal circuitry of IPM.
• IPM overheats due to defective IPM temperature sensor.
Multi Models Only
- Compressor OL connector poor contact.
- Compressor OL faulty.
Troubleshooting
95
16.4.28. F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling and heating, when compressor tank temperature data (112
° C) is detected by the compressor tank
temperature sensor.
Malfunction Caused
• Refrigerant shortage (refrigerant leakage).
• 2/3 way valve closed.
• Detection error due to faulty compressor tank temperature sensor.
Troubleshooting
96
16.4.29. F98 (Input Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an input over-current (16.8A) is detected by checking the input current value
being detected by current transformer (CT) with the compressor running.
Malfunction Caused
• Over-current due to compressor failure.
• Over-current due to defective outdoor unit PCB.
• Over-current due to defective inverter main circuit electrolytic capacitor.
• Over-current due to excessive refrigerant.
Troubleshooting