29 
10.5  Connect The Cable To The Outdoor Unit 
1.  Remove the particular plate from the unit by 
loosening two screws. 
2.  Cable connection to the power supply through 
isolating Devices (Disconnecting means). 
o
 
Connect approved type polychloroprene 
sheathed power supply cord 
CU-4E27***(3 x 2.5 mm²), CU-5E34*** 
(3 x 4.0 mm²) 245 IEC 57 type 
designation or heavier cord to the 
terminal board, and connect the others 
end of the cord to Isolating Devices 
(Disconnecting means). 
3.  Connection cable between indoor unit and 
outdoor unit shall be approved 
polychloroprene sheathed 4 x 1.5 mm
2
 flexible 
cord, type designation 245 IEC 57 or heavier 
cord. Allowable connection cable length of 
each indoor unit shall be 30 m or less. 
4.  Connect the power supply cord and 
connection cable between indoor unit and 
outdoor unit according to the diagram as 
shown. 
 
 
 
 
 
 
 
 
Remarks: 
It is the responsibility of the installer or user of the equipment to ensure, by consultation with the suitable 
distribution/supply network operator if necessary, that the equipment should be connected only to a supply with, 
š Short-circuit 
power 
Ssc 
– 1150kW 
š Service 
current 
capacity 
– 100A per phase 
The equipment complies with IEC/EN 61000-3-11 and IEC/EN 61000-3-12. Please liaise with supply authority to 
ensure that the above items at the interface point are sufficient for the installation of the equipment. 
 
 
 
 
30 
5.  For wire stripping and connection requirement, refer to the diagram below. 
6.  Secure the power supply cord and connecting cables onto the control board with the holder. 
7.  Attach the control board cover back to the original position with screw. 
 
 
 
10.6 Heat Insulation 
 
 
Use a material with good heat-resistant properties as the heat insulation for the 
pipes. Be sure to insulate both the gas-side and liquid-side pipes. If the pipes are 
not adequately insulated, condensation or water leakages may occur. 
 
Liquid-side pipes  Material shall 
withstand 
120°C or higher 
Gas-side pipes 
 
10.7  Disposal Of Outdoor Unit Drain Water 
š  If a drain elbow is used, the unit should be placed on a stand which is taller than 5 cm. 
š  If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it is recommended 
not to use a drain elbow, for the drain water freezes and the fan will not rotate. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
31 
11. Operation 
Control 
11.1 Cooling Operation 
11.1.1  Outdoor fan control 
š  When cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted 
according to figure below: 
 
 
 
11.1.2  Annual Cooling control 
š  This control is to enable cooling operation when outdoor ambient temperature is low. 
š  Control start conditions: 
o
  Cooling operation is activated with compressor ON. 
o
  Outdoor ambient temperature is less than 15°C. 
š Control 
contents: 
o
  When the above conditions are fulfilled, based on outdoor pipe temperature, the outdoor fan motor will 
operate according to figure below: 
 
 
 
š  To improve the judgment accuracy during annual cooling control, outdoor ambient temperature sampling for 
2 minutes will be activated every 35 minutes under designated fan speed. 
š Control 
stop 
conditions: 
o
  When either one of the start conditions are not complied. 
 
11.1.3 Cooling 
Powerful Operation 1 
š  During cooling operation, this control is to concentrate outdoor unit capability to the powerful operation enabled 
indoor unit by temporary stop the capability supply to low load demand indoor units. 
š  Operation start condition: 
o
  Powerful operation ON for targeted indoor unit 
š Operation 
content: 
o
  If other indoor units (where Powerful operation are OFF) achieve setting temperature continuously for 
1 minute after received powerful command from indoor unit, then capability supply to other indoor units are 
stopped for minimum 3 minutes. 
Capability supply stop period follows powerful operation period. 
š  Operation stops when comply either one of the following conditions: 
o
  When other indoor units (where Powerful operation are OFF) is demand for capacity. 
o
  When the powerful operation is OFF for all indoor units. 
o
  When Quiet operation received from 1 indoor unit. 
o
  When protection control starts. 
32 
11.2 Heating Operation 
11.2.1  Outdoor fan control 
š  When heating operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted 
according to figure below for Heating overload control: 
 
 
 
11.2.2  Heating Room Temp Sampling Control 
š  To improve the judgment accuracy, indoor room temperature sampling starts when any indoor unit has stopped 
capability supplied (heating thermo-off) during heating operation with compressor ON, outdoor unit will send 
signal to all thermo-off indoor units to ON fan motor and get room temperature sample. 
š  To prevent discharge temperature drop at indoor units which is ON when sampling the room temperature of 
heating thermo-off units, the compressor frequency is increased accordingly. 
š  However, if indoor room temperature is much higher compare to remote control setting temperature, before 
thermo-off, sampling of corresponding indoor unit will be cancelled. 
 
11.2.3  Powerful Operation 2 
š  During cooling / heating operation, this control is to provide fast cooling / heating operation compare to normal 
operation. 
š  Operation start if all condition below are complied: 
o
  Powerful operation ON for indoor unit. 
o
  Not under Annual Cooling control. 
š Operation 
content: 
o
  Outdoor fan speed will adjust automatically. 
o
 Compressor 
frequency 
will adjust automatically. 
š  Operation stop when comply either one of the follow conditions: 
o
  When the powerful operation is OFF for all indoor units. 
o
  When annual cooling control activated. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 60