14. Troubleshooting 
Guide 
14.1  Refrigeration cycle system 
In order to diagnose malfunctions, make sure that there are no 
electrical problems before inspecting the refrigeration cycle. Such 
problems include insufficient insulation, problem with the power 
source, malfunction of a compressor and a fan. The normal outlet air 
temperature and pressure of the refrigeration cycle depends on 
various conditions, the standard values for them are shown in the 
table on the right. 
 
14.1.1 
Normal Pressure and Outlet Air Temperature (Standard)
 
Gas Pressure 
Mpa 
(kg/cm
2
G) 
Outlet air 
Temperature 
(°C) 
Cooling Mode 0.9~1.2 ( 9~12) 
12~16 
Heating Mode 2.3 ~2.9 (23~29) 
36~45 
Condition:  Indoor fan speed = High 
Outdoor temperature = 35°C at cooling mode   and 7°C at 
heating mode. 
Compressor operates at rated frequency 
Different in the intake 
and outlet 
air temperatures 
Normal 
Value of electric current 
during operation 
Dusty condenser 
preventing heat radiation
Excessive amount 
of refrigerant 
•  Measuring the air 
temperature different 
•  Measuring electric 
current during operation
•  Measuring gas side 
pressure 
More than 8°C 
(15 minutes after an operation 
is started) at cooling mode. 
Above 14°C (15 minutes after 
an operation is started.) at 
heating mode 
Less than 8°C at the cooling mode 
Less than 14°C at the heating mode 
Higher than specified
Lower than 
specified 
Gas side 
pressure 
Inefficient compressor
Insufficient refrigerant
Clogged strainer or 
capillary cube 
Cooling 
Mode 
High 
Low 
Low 
Inefficient compressor
Insufficient refrigerant
Clogged strainer or 
capillary cube 
Heating 
Mode 
Low 
Low 
Low 
39 
 
14.1.2  Relationship between the condition of the air conditioner and pressure and electric 
current 
 
Cooling Mode 
Heating Mode 
Condition of the  
air conditioner 
Low Pressure 
High 
Pressure 
Electric current 
during 
operation 
Low Pressure 
High 
Pressure 
Electric current 
during operation
Insufficient 
refrigerant 
(gas leakage) 
Ô 
Ô 
Ô 
Ô 
Ô 
Ô 
Clogged capillary 
tube or 
strainer 
Ô 
Ô 
Ô 
Ò 
Ò 
Ò 
Short circuit in the 
indoor unit 
Ô 
Ô 
Ô 
Ò 
Ò 
Ò 
Heat radiation 
deficiency 
of the outdoor unit 
Ò 
Ò 
Ò 
Ô 
Ô 
Ô 
Inefficient 
compression 
Ò 
Ô 
Ô 
Ò 
Ô 
Ô 
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is 
started. 
 
14.2  Breakdown Self Diagnosis Function 
14.2.1  About Self Diagnosis 
When the air-conditioner is stopped due to malfunction detected by itself, the operation can be restarted using AUTO 
Switch on the indoor unit. In forced operation, the frequency for compressor and fan speed can not be changed and 
the signal receiving sound is different. 
Normal Operation ON: “pep” 
Forced Operation ON: “pep”, “pep”, “pep”, “pep” 
Stop: “pep” 
Note: Refer to the Diagnosis Code Table for the malfunction when forced operation is not available.
 
14.2.2  Display of Error Code 
1. Keeping the CHECK button on the remote controller depressed for 5 seconds, error code ranging fromH11 to H99 
can be displayed on the remote controller. 
2. The error code is changed and diagnosis signal is transmitted to the indoor unit by pressing the Temp Up button on 
the remote control. 
3. When the malfunction of the air-conditioner matches the error code on the remote control, four beeps can be heard 
from the indoor unit and the operation indicator will light up. 
4. Keep the CHECK button depressed continuously for 5 seconds to cancel the diagnosis function. 
 
 
 
40 
14.2.3  Error Codes Table 
 
 
Page of 47