DOWNLOAD Panasonic CS-XC9CKT / CU-XC9CKT / CS-XC12CKT / CU-XC12CKT Service Manual ↓ Size: 13.27 MB | Pages: 78 in PDF or view online for FREE

Model
CS-XC9CKT CU-XC9CKT CS-XC12CKT CU-XC12CKT
Pages
78
Size
13.27 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / ROOM AIR CONDITIONER
File
cs-xc9ckt-cu-xc9ckt-cs-xc12ckt-cu-xc12ckt.pdf
Date

Panasonic CS-XC9CKT / CU-XC9CKT / CS-XC12CKT / CU-XC12CKT Service Manual ▷ View online

6 Block Diagram
13
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
REMARKS
B
: BLUE
P
: PINK
BR
: BROWN
R
: RED
BL
: BLACK
W
: WHITE
G
: GREEN
Y
: YELLOW
GRY
: GRAY
Y/G
: YELLOW/GREEN
O
: ORANGE
Resistance of Indoor Fan Motor Windings
MODEL
CS-XC9CK
CS-XC12CK
CONNECTION
CWA921181
BLUE-YELLOW
390
YELLOW-RED
390
Note: Resistance at 20°C/25°C of ambient temperature.
Resistance of Outdoor Fan Motor Windings
MODEL
CU-XC9CK
CONNECTION
CWA951114
BLUE-YELLOW
259
YELLOW-RED
235
MODEL
CU-XC12CK
CONNECTION
CWA951116
BLUE-YELLOW
230
YELLOW-RED
255
Note: Resistance at 20°C of ambient temperature.
Resistance of Compressor Windings
MODEL
CU-XC9CK
CU-XC12CK
CONNECTION
2PS146D3AA04
2KS206D5AF04
C-R
3.941
2.234
C-S
3.499
2.630
Note: Resistance at 20°C/25°C of ambient temperature.
7 Wiring Diagram
14
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
8 Operation Details
8.1. Indoor Fan Speed Control
     • 
• 
• 
• Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
     • 
• 
• 
• Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote
control.
15
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
     • 
• 
• 
• If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
     • 
• 
• 
• Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
8.2. Cooling Mode Operation
     • 
• 
• 
• When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
     • 
• 
• 
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
     • 
• 
• 
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
     • 
• 
• 
• When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
     • 
• 
• 
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
! T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
16
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
Page of 78
Display

Click on the first or last page to see other CS-XC9CKT / CU-XC9CKT / CS-XC12CKT / CU-XC12CKT service manuals if exist.