6 Block Diagram
13
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
REMARKS
B
: BLUE
P
: PINK
BR
: BROWN
R
: RED
BL
: BLACK
W
: WHITE
G
: GREEN
Y
: YELLOW
GRY
: GRAY
Y/G
: YELLOW/GREEN
O
: ORANGE
Resistance of Indoor Fan Motor Windings
MODEL
CS-XC9CK
CS-XC12CK
CONNECTION
CWA921181
BLUE-YELLOW
390
Ω
YELLOW-RED
390
Ω
Note: Resistance at 20°C/25°C of ambient temperature.
Resistance of Outdoor Fan Motor Windings
MODEL
CU-XC9CK
CONNECTION
CWA951114
BLUE-YELLOW
259
Ω
YELLOW-RED
235
Ω
MODEL
CU-XC12CK
CONNECTION
CWA951116
BLUE-YELLOW
230
Ω
YELLOW-RED
255
Ω
Note: Resistance at 20°C of ambient temperature.
Resistance of Compressor Windings
MODEL
CU-XC9CK
CU-XC12CK
CONNECTION
2PS146D3AA04
2KS206D5AF04
C-R
3.941
Ω
2.234
Ω
C-S
3.499
Ω
2.630
Ω
Note: Resistance at 20°C/25°C of ambient temperature.
7 Wiring Diagram
14
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
8 Operation Details
8.1. Indoor Fan Speed Control
•
•
•
• Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
•
•
•
• Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote
control.
control.
15
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
•
•
•
• If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
•
•
•
• Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Cooling Operation.
Compressor Reverse Rotation Protection Control
8.2. Cooling Mode Operation
•
•
•
• When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
•
•
•
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
•
•
•
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
•
•
•
• When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
•
•
•
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
(Time Delay Safety Control is valid)
! T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
16