9.6.
Connecting piping and the cable to outdoor unit
9.6.1. Connecting the piping to outdoor unit
1. Align the center of the piping and sufficiently tighten the flare nut with fingers.
2. Finally tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow of the wrench.
Caution
When connecting the piping, always use a torque wrench.
Other tools may cause damage to the flare nut because
of improper force.
Piping side
Torque
Liquid side 1/ 4"
Gas side 3/8”
18N.m
42N.m
3. Ensure not to let the piping exposed to air.
9.6.2. Connecting the cable to the outdoor unit
1. Remove the control board cover of the outdoor unit from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (PC7DKD,
PC9DKD) or 5 (PA7DKD, PA9DKD)x 1.5 mm flexible cord, type designation 245 IEC 57 or heavier cord.
For PA7DKD, PA9DKD the attached wire 6 with two connectors should be applied.
2
45
3. Secure the cable onto the control board with the holder ( clamper ).
4. Attach the control board cover to the original position with the screws.
Indoor Connecting Terminal
Outdoor Connecting Terminal
Colours of wires
1(L) 2(N)
1(L) 2(N)
CS/CU-PC7DKD,CS/CU-PC9DKD
1(L) 2(N)
3
4
1(L) 2(N)
3
4
Indoor Connecting Terminal
Outdoor Connecting Terminal
Colours of wires
Connector
CS/CU-PA7DKD,CS/CU-PA9DKD
CS-PA7DKD / CU-PA7DKD / CS-PC7DKD / CU-PC7DKD
46
9.7. Checking the drainage and connecting the cable to indoor unit
9.7.1. Checking the drainage
1. Remove the front grille from the cabinet
When removing the front grille for maintenance purposes
etc, carry out by the following procedures.
a. Set the vertical airflow direction louver to the
horizontal position.
b. Remove the two caps on the front grille as shown in the
illustration at right, and then remove the two mounting
screws.
c. Pull the lower section of the front grille toward you to
remove the front grille.
Air filter
Horizontal airflow
direction louver
Cap
Front Grille
Pull the lower section
of the front grille
toward you to remove
the front grille.
Manually adjust the
horizontal airflow
direction louver to
horizontal position
Traystyrofoam
When reinstalling the front grille, first set the vertical airflow
direction louver to the horizontal position, and then carry out
by steps” c” and “b” in that order. At this time check to sure
that the fixing tabs on the top inside edge of the front grille
are securely inserted into the respective slots.
2. Checking the drainage
• Pour a glass of water into the drain train traystyroform.
• Ensure water flow out from drain hose of indoor unit.
Fig.30
Fig.31
3. Drainage control for outdoor unit
(For heating pump models only)
If a drainage plug is applied,the outdoor unit
should at least be 3 centimeters high from the
floor.
If is better not to use the drainage plug if the
temperature is lower than 0
,since icing of the
condensed water may block the water flow.
Drain plug
CS-PA7DKD / CU-PA7DKD / CS-PC7DKD / CU-PC7DKD
9.7.2. Connect the cable to the indoor
unit
47
CS-PC7DKD
CS-PC9DKD
1(L)
2(N)
3
4
CS-PA7DKD
CS-PA9DKD
Plug
The inside and outside connecting cable can be
connected without removing the front grille.
Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3
(PC7DKD,PC9DKD, ) or 5(PA7DKD,PA9DKD)x1.5mm
flexible cord, type designation 245 IEC 57 or heavier
cord. For PA7DKD,PA9DKD, the attached wire 6 with
two connectors should be applied.
2
1.
2.
• Ensure the colour of wires of outdoor unit and the terminal
number are the same as the indoor ’s respectively.
• Secure the cable onto the board with the holder (clamper).
• Both the unit and the power supply socket should be
properly grounded.
Indoor Connecting Terminal
Outdoor Connecting Terminal
Colours of wires
1(L) 2(N)
1(L) 2(N)
CS/CU-PC7DKD,CS/CU-PC9DKD
1(L) 2(N)
3
4
1(L) 2(N)
3
4
Colours of wires
Connector
CS/CU-PA7DKD,CS/CU-PA9DKD
Indoor Connecting Terminal
Outdoor Connecting Terminal
Secure the cable onto the control board with the holder
(clamper).
HOW TO TAKE OUT THE FRONT GRILLE
Please follow the steps below to take out front grille
If necessary such as when servicing.
Set the vertical airflow direction louver to the
horizontal position.
Slide down the two caps on the front grille as shown
in the illustration below, and then remove the two
mounting screw.
Pull the lower section of the front grille towards you
to remove the front grille.
1.
2.
3.
Cap
Screw
Vertical airflow
deflection louver
(Move the vertical
vane to horizontal)
When reinstalling the front grille, first set the vertical
airflow direction louver to the horizontal position and
the carry out above steps 2-3 in the reverse order.
AUTO SWITCH OPERATION
The below operation will be performed by pressing
the “Auto” switch.
AUTO OPERATION MODE
The Auto operation will be activated immediately
once the Auto Switch is pressed.
TEST RUN OPERATION(FOR PUMP DOWN /
SERVICING PURPOSE)
The Test Run operation will be activated if the Auto
Switch is pressed continuously for more than 5 sec.
to below 10 sec.A “pep” sound will occur at the fifth
sec., in order to identify the starting of Test Run
operation.
REMOTE CONTROLLER RECEIVING SOUND
ON/OFF
The ON/OFF of Remote Controller receiving sound
can be changed over by pressing the “AUTO”
Switch continuously for 10 sec. and above. A “pep”,
“pep” sound will occur at the tenth sec., in order to
indicate the “ON/OFF” changed over of remote
control receiving sound.
1.
2.
3.
CS-PA7DKD / CU-PA7DKD / CS-PC7DKD / CU-PC7DKD
9.8.
Test Running
9.8.1. Connect the power supply
1. Connect the power supply cord to independent power
supply.
• Circuit breaker is necessary.
2. Prepare the remote control
• Insert two batteries
• Remove the cover from the back of the remote control.
Insert two batteries
• Be sure that the (+) and (-) directions are correct.
• Be sure that both batteries are new.
• Re-attach the cover.
• Slide the cover back into position.
3. Operate the unit at cooling mode operation for 15 minutes
or more.
OPEN
9.8.2. Evaluation of the performance
1. Operate the air conditioner for 15 minutes.
2. Measure the temperature of the intake and discharge air.
3. Ensure the difference of temperature between the intake
and discharge air is more than 8°C in cooling operation,
or more than 14°C in heating operation.
CAUTION
Connecting cable between the indoor and outdoor unit shall be
approved cable and the size of the conductor shall be 1.5mm2.
48
Intake
air
Thermometer
Discharge air
CS-PA7DKD / CU-PA7DKD / CS-PC7DKD / CU-PC7DKD
Page of 74
Display