16.4.17  H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED 
flashing) 
Malfunction Decision Conditions 
  Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is 
operating in heating operation. 
  Phenomena: unit is stopping and re-starting very often in heating mode 
 
Malfunction Caused 
  Indoor heat exchanger thermistor 
  Clogged air filter or heat exchanger 
  Over-bent pipe (liquid side) 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
86 
16.4.18  H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) 
Error Code will not display (no Timer LED blinking) but store in EEPROM 
 
Malfunction Decision Conditions 
  Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) 
 
Malfunction Caused 
  Air short circuit at indoor unit 
  Clogged indoor unit air filter 
  Dust accumulation on the indoor unit heat exchanger 
  2/3 way valve closed 
  Faulty indoor unit fan motor 
 Refrigerant 
shortage 
(refrigerant leakage) 
  Clogged expansion valve or strainer 
  Faulty indoor pipe temperature sensor 
  Faulty indoor unit PCB 
 
Troubleshooting 
 
 
 
 
 
 
 
87 
16.4.19  F11 (4-way Valve Switching Failure) 
Malfunction Decision Conditions 
  When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during 
cooling and compressor operating, the 4-way valve is detected as malfunction. 
 
Malfunction Caused 
  Indoor heat exchanger (pipe) thermistor 
  4-way valve malfunction 
 
Troubleshooting 
 
 
 
* Check gas side pipe – for hot gas flow in cooling mode 
 
 
 
 
 
 
 
88 
16.4.20  F17 (Indoor Standby Units Freezing Abnormality) 
Malfunction Decision Conditions 
  When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor 
pipe temperature is below -1.0°C. 
 
Remark: 
When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor 
unit and H39 to other indoor unit(s). 
 
Malfunction Caused 
  Wrong wiring connection 
 Faulty 
sensor 
  Faulty expansion valve 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 