16.1.1  Relationship Between the Condition of the Air Conditioner and Pressure and 
Electric Current 
 
Condition of the  
air conditioner 
Cooling Mode 
Heating Mode 
Low Pressure 
High Pressure 
Electric current 
during operation
Low Pressure 
High Pressure 
Electric current 
during operation
Insufficient refrigerant 
(gas leakage) 
 
 
 
 
 
 
Clogged capillary tube or 
Strainer 
 
 
 
 
 
 
Short circuit in the indoor unit 
 
 
 
 
 
 
Heat radiation deficiency 
of the outdoor unit 
 
 
 
 
 
 
Inefficient compression 
 
 
 
 
 
 
•  Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
66 
16.2  Breakdown Self Diagnosis Function 
16.2.1  Self Diagnosis Function (Three Digits Alphanumeric Code) 
  Once abnormality has occurred during operation, the unit will stop its operation, and OFF/ON operation LED OFF. 
  OFF indicator does not shown on remote control display. 
  In operation after breakdown repair, the last error code abnormality will be stored in EEPROM. 
  To make a diagnosis 
1.  OFF/ON operation LED OFF and the unit automatically stops the operation, but the OFF indicator does not 
shown. 
2.  Press CHECK button continuously for 5 seconds. 
3.  “- -” will be displayed on the remote controller display. 
4. Press 
timer 
▲ or ▼ button on the remote control. The error code “H00” (no abnormality) will be displayed. 
5.  Every press of the button (▲ or ▼) will increase the error code number. 
6.  When the displayed error code matches the unit's error code, OFF/ON operation LED will be ON 
continuously. 
7.  The breakdown diagnosis mode will be cancelled by pressing CHECK button continuously for 5 seconds or 
wait for 30 seconds 
 
  AC Reset button 
When AC Reset button is pressed, the error code 
will be reset so that the unit will be able to operate 
and recheck if any error occurred. 
 
 
 
  To display memorized error status: 
1  Turn ON the power supply. 
2  Press CHECK button continuously for 5 seconds. 
3  “- -” will be displayed on the remote controller display. 
4 Press 
timer 
▲ or ▼ button on the remote control. The error code "H00" (no abnormality) will be displayed. 
5  Every press of the button (▲ or ▼) will increase the error code number. 
6  When the displayed error code matches the unit's error code, OFF/ON operation LED will be ON 
continuously. 
7  The breakdown diagnosis mode will be cancelled by pressing CHECK button continuously for 5 seconds or 
wait for 30 seconds. 
 
 
 
 
 
 
 
 
 
67 
16.3  Error Codes Table 
 
Diagnosis 
display 
Abnormality / 
Protection control 
Abnormality 
Judgment 
Protection 
Operation 
Problem Check 
location 
H00 
No memory of failure 
— 
Normal operation
— 
— 
H11 
Indoor/outdoor 
abnormal 
communication 
After operation for 
1 minute 
Indoor fan only 
operation can 
start by entering 
into force cooling
operation 
Indoor/outdoor 
communication not 
establish 
 Indoor/outdoor wire terminal 
 Indoor/outdoor PCB 
 Indoor/outdoor connection wire 
H12 
Indoor unit capacity 
unmatched 
90s after power 
supply 
— 
Total indoor capability 
more than maximum limit 
or less than minimum limit, 
or number of indoor unit 
less than two 
 Indoor/outdoor connection wire 
 Indoor/outdoor PCB 
  Specification and combination 
table in catalogue 
H14 
Indoor intake air 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Indoor intake air 
temperature sensor open 
or short circuit 
  Indoor intake air temperature 
sensor lead wire and connector 
H15 
Compressor 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Compressor temperature 
sensor open or short circuit 
 Compressor temperature 
sensor lead wire and connector 
H16 
Outdoor current 
transformer (CT) 
abnormality 
— — 
Current transformer faulty 
or compressor faulty 
  Outdoor PCB faulty or 
compressor faulty 
H19 
Indoor fan motor 
mechanism lock 
Continuous 
happen for 7 times 
— 
Indoor fan motor lock or 
feedback abnormal 
  Fan motor lead wire and 
connector 
  Fan motor lock or block 
H21 
Indoor float switch 
operation abnormal 
— — 
— 
— 
H23 
Indoor heat 
exchanger 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Indoor heat exchanger 
temperature sensor open 
or short circuit 
  Indoor heat exchanger 
temperature sensor lead wire 
and connector 
H24 
Indoor heat 
exchanger 
temperature sensor 
2 abnormality 
Continuous for 5s 
— 
Indoor heat exchanger 
temperature sensor 2 open 
or short circuit 
  Indoor heat exchanger 
temperature sensor 2 lead wire 
and connector 
H27 
Outdoor air 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Outdoor air temperature 
sensor open or short circuit 
  Outdoor air temperature sensor 
lead wire and connector 
H28 
Outdoor heat 
exchanger 
temperature sensor 
1 abnormality 
Continuous for 5s 
— 
Outdoor heat exchanger 
temperature sensor 1 open 
or short circuit 
  Outdoor heat exchanger 
temperature sensor 1 lead wire 
and connector 
H30 
Outdoor discharge 
pipe temperature 
sensor abnormality 
Continuous for 5s 
— 
Outdoor discharge pipe 
temperature sensor open 
or short circuit 
  Outdoor discharge pipe 
temperature sensor lead wire 
and connector 
H32 
Outdoor heat 
exchanger 
temperature sensor 
2 abnormality 
Continuous for 5s 
— 
Outdoor heat exchanger 
temperature sensor 2 open 
or short circuit 
  Outdoor heat exchanger 
temperature sensor 2 lead wire 
and connector 
H33 
Indoor / outdoor 
misconnection 
abnormality 
— — 
Indoor and outdoor rated 
voltage different 
  Indoor and outdoor units check 
H35 
Indoor drain water 
adverse current 
abnormal 
— — 
— 
— 
H36 
Outdoor gas pipe 
temperature sensor 
abnormality 
Continuous for 5s 
Heating 
protection 
operation only 
Outdoor gas pipe 
temperature sensor open 
or short circuit 
  Outdoor gas pipe temperature 
sensor lead wire and connector 
H37 
Outdoor liquid pipe 
temperature sensor 
abnormality 
Continuous for 5s 
Cooling 
protection 
operation only 
Outdoor liquid pipe 
temperature sensor open 
or short circuit 
  Outdoor liquid pipe temperature 
sensor lead wire and connector 
H38 
Indoor/Outdoor 
mismatch (brand 
code) 
— 
— 
Brand code not match 
  Check indoor unit and outdoor 
unit 
H39 
Abnormal indoor 
operating unit or 
standby units 
3 times happen 
within 40 minutes 
— 
Wrong wiring and 
connecting pipe, expansion 
valve abnormality, indoor 
heat exchanger sensor 
open circuit 
 Check indoor/outdoor 
connection wire and connection 
pipe 
  Indoor heat exchanger sensor 
lead wire and connector 
  Expansion valve and lead wire 
and connector 
 
 
 
68 
Diagnosis 
display 
Abnormality / 
Protection control 
Abnormality 
Judgment 
Protection 
Operation 
Problem Check 
location 
H41 
Abnormal wiring or 
piping connection 
— — 
Wrong wiring and 
connecting pipe, expansion 
valve abnormality 
 Check indoor/outdoor 
connection wire and connection 
pipe 
  Expansion valve and lead wire 
and connector 
H64 
Outdoor high 
pressure sensor 
abnormality 
Continuous for 1 
minutes 
— 
High pressure sensor open 
circuit during compressor 
stop 
  High pressure sensor 
  Lead wire and connector 
H97 
Outdoor fan motor 
mechanism lock 
2 times happen 
within 30 minutes 
— 
Outdoor fan motor lock or 
feedback abnormal 
  Outdoor fan motor lead wire 
and connector 
  Fan motor lock or block 
H98 
Indoor high pressure 
protection 
— — 
Indoor high pressure 
protection (Heating) 
  Check indoor heat exchanger 
  Air filter dirty 
  Air circulation short circuit 
H99 
Indoor operating unit 
freeze protection 
— — 
Indoor freeze protection 
(Cooling) 
  Check indoor heat exchanger 
  Air filter dirty 
  Air circulation short circuit 
F11 
4-way valve 
switching 
abnormality 
4 times happen 
within 30 minutes 
— 
4-way valve switching 
abnormal 
 4-way valve 
  Lead wire and connector 
F17 
Indoor standby units 
freezing abnormality 
3 times happen 
within 40 minutes 
— 
Wrong wiring and 
connecting pipe, expansion 
valve leakage, indoor heat 
exchanger sensor open 
circuit 
 Check indoor/outdoor 
connection wire and pipe 
  Indoor heat exchanger sensor 
lead wire and connector 
  Expansion valve lead wire and 
connector 
F90 
Power factor 
correction 
(PFC) circuit 
protection  
4 times happen 
within 10 minutes 
— 
Power factor correction 
circuit abnormal 
  Outdoor PCB faulty 
F91 
Refrigeration cycle 
abnormality 
2 times happen 
within 20 minutes 
— 
Refrigeration cycle 
abnormal 
  Insufficient refrigerant or valve 
close 
F93 
Compressor 
abnormal revolution 
4 times happen 
within 20 minutes 
— 
Compressor abnormal 
revolution 
  Power transistor module faulty 
or compressor lock 
F94 
Compressor 
discharge overshoot 
protection 
4 times happen 
within 30 minutes 
— 
Compressor discharge 
pressure overshoot 
  Check refrigeration system 
F95 
Outdoor cooling high 
pressure protection 
4 times happen 
within 20 minutes 
— 
Cooling high pressure 
protection 
  Check refrigeration system 
  Outdoor air circuit 
F96 
Power transistor 
module overheating 
protection 
4 times happen 
within 30 minutes 
— 
Power transistor module 
overheat 
 PCB faulty 
  Outdoor air circuit (fan motor) 
F97 
Compressor 
overheating 
protection 
3 times happen 
within 30 minutes 
— Compressor 
overheat 
 Insufficient refrigerant 
F98 
Total running current 
protection 
3 times happen 
within 20 minutes 
— Total 
current 
protection 
  Check refrigeration system 
  Power source or compressor 
lock 
F99 
Outdoor direct 
current (DC) peak 
detection 
Continuous 
happen for 7 times 
— 
Power transistor module 
current protection 
  Power transistor module faulty 
or compressor lock 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 