61 
14.7.1  Drain Pump Control 
  This unit has built-in with drain pump. 
 
Control content 
  During COOL/DRY mode. 
o  During COOL/DRY mode, drain pump starts 10 seconds after indoor fan motor starts. 
o  The drain pump turns ON and turns OFF periodically. (ON or OFF duration depends on room temperature). 
 
  After COOL/DRY mode, when unit turns OFF (power standby) or changes to HEAT mode. 
o  The drain pump turns ON for 60 seconds immediately. 
 
 Error 
judgment 
o  When float switch detects ON signal continuously for 2 minutes 30 seconds, error code H21 are shown. 
o  When float switch ON has operated 2 times within 20 minutes, error code H35 are shown. 
14.7.2  Pump down Operation by CN-S 
  A convenience method to activate pump down operation. 
 
  Control start condition: 
o  During power standby condition, short CN-S continuously between 1 second and 10 seconds. 
 
  Control stop condition:  
o  480 seconds after pump down operation starts. 
o  CN-S is shorted again during pump down operation. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
62 
15.  Operation Control (For Multi Split Connection) 
During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in 
this chapter. 
15.1 Cooling 
operation 
15.1.1 Thermostat 
control 
  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting 
temperature < -2.0°C. 
  Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting 
temperature > Capability supply OFF point. 
15.2  Soft Dry Operation 
15.2.1 Thermostat 
control 
  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting 
temperature < -3.0°C. 
  Capability resume to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting 
temperature > Capability supply OFF point. 
15.3 Heating 
Operation 
15.3.1 Thermostat 
control 
  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting 
temperature > +1.0°C. 
  During this condition, the indoor fan is stopped if compressor is ON. 
  Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air Temperature — Internal 
setting temperature < Capability supply OFF point. 
15.3.2  Temperature Sampling Control 
  Temperature sampling is controlled by outdoor unit where room temperature for all power supply ON indoor unit 
could be obtained. 
  When capability supply to the indoor unit is OFF and the compressor is ON, the indoor fan motor is stopped. 
During this condition, 15 seconds after sampling signal from outdoor unit is received, the indoor fan start 
operation at low fan speed. 
  However, within first 4 minutes of capability stopped supply to the indoor unit, even sampling signal is received, 
the sampling control is cancelled. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
63 
15.4 Automatic 
Operation 
  This mode can be set using remote control and the operation is decided by remote control setting temperature, 
remote control operation mode, indoor intake and outdoor air temperature. 
  During operation mode judgment, indoor fan motor (with speed of -Lo) and outdoor fan motor are running for 
30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on 
below chart. 
 
 
  Every 180 minutes, the indoor and outdoor temperature is judge. Based on remote control setting temperature, 
the value of T1 will increase up to 10°C, T2 will decrease by 3°C and T3 will decrease up to 8°C. 
15.5  Indoor Fan Motor Operation 
15.5.1  Residual Heat Removal Control 
  To prevent high pressure at indoor unit, when heating mode thermostat-off condition or power supply OFF, 
indoor fan continue to operate at controlled fan speed for maximum 30 seconds then stop. 
15.6 Powerful 
Mode 
Operation 
  When the powerful mode is selected, the internal setting temperature will shift lower up to 4.0°C for Cooling/Soft 
Dry or higher up to 6.0°C for heating than remote control setting temperature. This operation stops automatically 
after 20 minutes. 
15.7 Auto 
Restart 
Control 
  When the power supply is cut off during the operation of air conditioner, the compressor will re-operate between 
three to four minutes (10 patterns to be selected randomly) after power resume. 
  During multi split connection, Indoor unit will resume previous mode, include unit standby mode. 
15.8 Indication 
Panel 
 
LED OFF/ON 
Operation 
Color Green 
Light ON 
Operation ON 
Light OFF 
Operation OFF 
 
Note: 
  If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation 
mode judgment, or ON timer sampling. 
  If Timer LED is blinking, there is an abnormality operation occurs. 
 
 
 
 
 
 
64 
16. Troubleshooting 
Guide 
16.1  Refrigeration Cycle System 
In order to diagnose malfunctions, make sure that there are no 
electrical problems before inspecting the refrigeration cycle. 
Such problems include insufficient insulation, problem with the 
power source, malfunction of a compressor and a fan. 
The normal outlet air temperature and pressure of the refrigeration 
cycle depends on various conditions, the standard values for them 
are shown in the table on the right. 
 
 
 
 
 
 
 
 
Difference in the intake
and outlet
air temperatures 
More than 8°C
(15 minutes after an
operation is started.)
at cooling mode.
Above 14°C
(15 minutes after an
operation is started.)
at heating mode. 
Value of electric
current during operation
Normal
Inefficient compressor
Insufficient refrigerant
Excessive amount
of refrigerant
Dusty condenser
preventing heat radiation
Measuring the air temperature
difference
Measuring electric current
during operation
Less than 8°C at the cooling mode
Less than 14°C at the heating mode.
Higher than specified
Gas side
pressure
Clogged strainer or
capillary tube
Measuring gas side pressure
Cooling Mode
High
Lower than specified
Low
Low
Inefficient compressor
Insufficient refrigerant
Clogged strainer, capillary
tube or expansion valve
Heating Mode
Low
Low
High
Normal Pressure and Outlet Air Temperature (Standard)
 
Gas Pressure 
MPa 
(kg/cm
2
G) 
Outlet air 
Temperature 
(°C) 
Cooling Mode
0.9 ~ 1.2 (9 ~ 12) 
13 ~ 17 
Heating Mode 2.0 ~ 2.7 (20 ~ 27) 
32 ~ 42 
*Condition:  • Indoor fan speed = High 
• Outdoor temperature 35°C at the cooling 
                      mode and 7°C at the heating mode 
                    • Compressor operates at rated frequency       
Page of 103