– 20  –
CS-MC90KA
MAC9902014C3
Operation Details
1) Cooling Mode Operation
Cooling in operation according to Remote Control setting.
• When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3
minutes when the Power Switch, Remote Control is turned ON or the power supply is resumed.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3
minutes.
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is below the
compressor ON temperature.
• If the compressor is operating continually for 5 minutes or longer and the temperature difference between intake air
and indoor heat exchanger is 2.5
°
C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid).
∆ 
T = Intake air temperature – Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
Time Delay Safety Control (3 minutes)
7 minutes Time Saved Control
Anti-Freezing Control
• If the temperature of the indoor heat exchanger
falls continously below 2
°
C for 4 minutes, the
compressor turns off to protect the indoor heat
exchanger from freezing. The fan speed setting
remains the same.
• Compressor recommences when the indoor heat
exchanger temperature rises to 10
°
C (Recovery).
*
3 minutes waiting of Time Delay Safety
Control is valid for Cooling Operation.
Compressor Reverse Rotation
Protection Control
• Compressor starts for 
>
 5 minutes
• 
∆ 
<
 2.5
°
C for 2 minutes
Compressor
restarts
(3 minutes waiting)
Compressor
OFF
Recovery
4 min
Compressor OFF
Indoor Heat 
Exchanger
Temperature
(°C)
2
10
Untitled-23
6/19/00, 10:14 AM
20
– 21 –
CS-MC90KA
MAC9902014C3
Automatic Fan Speed Mode
When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.
Operation Details
Cooling Operation Time Diagram
*
 1 Fan Speed is Hi until the compressor stops (when the room temperature reaches
    setting temperature).
*
 2 Fan Speed is Me after the compressor restarts.
Operation
Stop
<Description of operation>
d – g
:
Time Delay Safety Control (waiting for 3 minutes)
g – h
:
60 sec. Forced Operation
h – 0
:
7 min. Time Saved Control
q – t
:
Anti Freezing Control
<Condition>
a – h
:
When outdoor temperature is high
h – p
:
When outdoor temperature is moderate
p – w
:
When outdoor temperature is low
Indoor
Fan
Comp.
SLo
Lo
Lo
Lo
ON
ON
OFF
stop
stop
stop
30"
stop
30"
160"
   1
40"
40"
20"
...
.
   2
...
.
a b c d e f g h i j k l m n o p q r s t u v w x y z
Basic Time
Compressor
Indoor Fan
Outdoor Fan
Operation LED
1’
3’
1’
7’
1’
3’
4’
1.5
°
C
ON
OFF
Comp.
Intake Air
Temperature
Comp.
Set Temp.
Indoor 
Heat
Exchanger
Temp.
10
°
C
2
°
C
Untitled-23
6/19/00, 10:14 AM
21
– 22  –
CS-MC90KA
MAC9902014C3
Operation Details
2) Soft Dry Mode Operation
• The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote
Control, and then Soft Dry operation will start.
• During Soft Dry operation, the Indoor Fan will operate and stop at 4-second intervals at low speed.
• The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry opera-
tion is turned off, it stops for 6 minutes.
• Once the compressor stops, it will not start for 3 minutes during Cooling operation.
• Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during
compressor stops.)
• Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (Refer page 20)
When Automatic Fan Speed is selected at Remote Control during Soft Dry Operation.
• Fan speed rotates at SLo and Lo speed.
• Deodorizing Control.
*
 SLo: Indoor Fan rotates at 4-second intervals at low speed.
Time Delay Safety Control
Anti-Freezing Control
Compressor Reverse Rotation
Protection
Automatic Fan Speed Mode
Indoor
Fan
COMP
stop
stop
stop
SLo
Lo
SLo
ON
ON
OFF
40"
40"
6'
Untitled-23
6/19/00, 10:14 AM
22
– 23 –
CS-MC90KA
MAC9902014C3
Operation Details
Soft Dry Operation Time Diagram
<Description of operation>
a – c, p~r :
Cooling Operation
c – p
:
Soft Dry Operation
e – f
:
Soft Dry OFF
j – l
:
60 sec. Forced Operation
q – t
:
Anti Freezing Control
<Condition>
a – h :
When outdoor temperature is high
h – p :
When outdoor temperature is moderate
p – u :
When outdoor temperature is low
Soft Dry operation
Operation
Stop
- - - - -
a b c d e f g h i j k l m n o p q r s t u v
Basic Time
Compressor
Indoor Fan
Outdoor Fan
Operation LED
10’
1’
1’
1’
6’
6’
6’
6’
4’
1’
Cooling ON
Cooling OFF
Soft Dry ON
Soft Dry OFF
1.5°C
1.0°C
SLo
SLo
SLo
 Lo
SLo
SLo
SLo SLo
SLo
SLo
SLo
SLo
Indoor
Heat Exchanger
Temp.
10°C
2°C
6’
Intake Air
Temperature
Set Temp.
Untitled-23
6/19/00, 10:14 AM
23