33 
12.  Operation and Control 
12.1 Basic Function 
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time 
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating 
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and 
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by 
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air 
temperature. 
12.1.1  Internal Setting Temperature 
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting 
processes. These shifting processes are depending on the air conditioner settings and the operation environment. 
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the 
electrical power is supplied to the unit. 
 
 
12.1.2 Cooling 
Operation 
12.1.2.1 Thermostat 
control 
š  Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C continue for 3 minutes. 
š  Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > 
Compressor OFF point. 
 
12.1.3  Soft Dry Operation 
12.1.3.1 Thermostat 
control 
š  Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C continue for 3 minutes. 
š  Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > 
Compressor OFF point. 
 
12.1.4 Heating 
Operation 
12.1.4.1 Thermostat 
control 
š  Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C continue for 3 minutes. 
š  Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < 
Compressor OFF point. 
 
 
 
 
 
 
34 
12.1.5 Automatic 
Operation 
š  This mode can be set using remote control and the operation is decided by remote control setting temperature, 
remote control operation mode, indoor intake air temperature and outdoor air temperature. 
š  During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 
30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on 
below chart. 
 
 
 
Every 30 minutes, the indoor and outdoor temperature is judged. Based on remote control setting temperature, the 
value of T1 will increase up to 10°C, T2 will decrease by 3°C and T3 will decrease up to 8°C. 
The Auto Operation Mode shifting will take place whenever operation mode changed from Cooling/Soft Dry to 
Heating or vice versa. 
 
12.2  Indoor Fan Motor Operation 
A. Basic Rotation Speed (rpm) 
i. Manual Fan Speed 
[Cooling, Dry] 
š  Fan motor’s number of rotation is determined according to remote control setting. 
 
Remote control 
○ 
○ 
○ 
○ 
○ 
Tab Hi 
Me+ 
Me 
Me- 
Lo 
 
[Heating] 
š  Fan motor’s number of rotation is determined according to remote control setting. 
 
Remote control 
○ 
○ 
○ 
○ 
○ 
Tab SHi 
Me+ 
Me 
Me- 
Lo 
 
ii. Auto Fan Speed 
[Cooling, Dry] 
š  According to room temperature and setting temperature, indoor fan speed is determined automatically. 
š  The indoor fan will operate according to pattern below. 
 
 
 
 
 
 
 
 
 
 
35 
[Heating] 
o
  According to indoor pipe temperature, automatic heating fan speed is determined as follows. 
 
 
 
B. Feedback control 
š  Immediately after the fan motor started, feedback control is performed once every second. 
š  During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error 
counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan 
motor error is detected. Operation stops and cannot on back. 
 
12.3  Outdoor Fan Motor Operation 
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 
30 seconds after compressor stops operation. 
 
 
 
12.4 Airflow Direction 
š  There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by 
vertical vanes). 
š  Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat 
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using 
remote control). 
12.4.1 Vertical 
Flow 
Vane Angle (°) 
Operation Mode 
Airflow Direction 
1 2 3 4 5 
A 10 
B 43.8 
Auto Heat Exchanger 
Temperature 
C 21.2 
Heating 
Manual 10 
21.2 
32.5 
43.8 
55 
Auto 
10 ~ 40 
Cooling 
Manual 
10 17.5 25 32.5 40 
Auto 
10 ~ 40 
Soft Dry 
Manual 
10 17.5 25 32.5 40 
 
1  Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the 
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat 
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner 
is stopped using remote control, the vane will shift to close position. 
36 
2  Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above 
and the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, 
the vane will shift to close position. 
 
 
12.4.2 Horizontal 
Airflow 
1  Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within 
the angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat 
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. 
 
 
Operation Mode 
Vane Angle (°) 
65 ~ 115 
Heating, with heat exchanger temperature 
B 90 
Cooling and Soft Dry 
 
65 ~ 115 
 
 
 
2  Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated 
below and the positions of the vane are as Figure 2 above. 
 
Pattern 
1 2 3 4 5 
Airflow Direction 
Patterns at Remote 
Control 
 
 
 
 
 
Vane Angle (°) 
90 
65 
77.5 
102.5 
115 
 
12.5  Quiet operation (Cooling Mode/Cooling area of Dry Mode) 
A. Purpose 
To provide quiet cooling operation compare to normal operation. 
 
B. Control condition 
a.  Quiet operation start condition 
o
 
When “POWERFUL/QUIET” button at remote control is pressed twice. 
POWERFUL/QUIET LED illuminates (low intensity). 
 
b.  Quiet operation stop condition 
1  When one of the following conditions is satisfied, quiet operation stops: 
a.  POWERFUL/QUIET button is pressed again. 
b.  Stop by OFF/ON switch. 
c.  Timer “off” activates. 
Page of 107