11. Installation 
Instruction 
11.1  Select the Best Location 
11.1.1 Indoor 
Unit 
š  Do not install the unit in excessive oil fume area 
such as kitchen, workshop and etc. 
š  There should not be any heat source or steam 
near the unit. 
š  There should not be any obstacles blocking the air 
circulation. 
š  A place where air circulation in the room is good. 
š  A place where drainage can be easily done. 
š  A place where noise prevention is taken into 
consideration. 
š  Do not install the unit near the door way. 
š  Ensure the spaces indicated by arrows from the 
wall, ceiling, fence or other obstacles. 
š  Recommended installation height for indoor unit 
shall be at least 2.5 m. 
11.1.2 Outdoor 
Unit 
š  If an awning is built over the unit to prevent direct 
sunlight or rain, be careful that heat radiation from 
the condenser is not obstructed. 
š  There should not be any animal or plant which 
could be affected by hot air discharged. 
š  Keep the spaces indicated by arrows from wall, 
ceiling, fence or other obstacles. 
š  Do not place any obstacles which may cause a 
short circuit of the discharged air. 
š  If piping length is over the [piping length for 
additional gas], additional refrigerant should be 
added as shown in the table. 
 
Model 
Horse 
Power 
(HP) 
Piping size 
Std. 
Length 
(m) 
Max 
Eleva-
tion (m)
Min.    
Piping 
Length 
(m) 
Max.   
Piping 
Length 
(m) 
Addi-
tional 
Refri-
gerant 
(g/m)
Piping 
Length 
for add. 
gas (m)
Gas Liquid 
E7*** 3/4HP 
9.52 
mm 
(3/8”) 
6.35 
mm 
(1/4”) 
15 3 15 
20 
7.5 
E9*** 1.0HP 
15 
15  20  7.5 
E12*** 1.5HP 
15 
15 
20 
7.5 
E15*** 1.75HP 12.7 
mm 
(1/2”) 
15 3 15 
20 
7.5 
E18*** 2.0HP 
15 
20 
20 
7.5 
E24*** 2.5HP 15.88 
mm 
(5/8”) 
20 3 30 
30 
10 
E28*** 3.0HP 
20 
30 
30 
10 
Example: For E9*** 
If the unit is installed at 10 m distance, the quantity of 
additional refrigerant should be 50 g .... (10-7.5) m x  
20 g/m = 50 g. 
 
 
 
 
 
 
 
 
11.1.3  Indoor/Outdoor Unit Installation 
Diagram 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
51 
11.2 Indoor Unit 
11.2.1  How to Fix Installation Plate 
The mounting wall shall be strong and solid enough to prevent it from vibration. 
 
 
 
The center of installation plate should be at more than c at right and left of the wall. 
The distance from installation plate edge to ceiling should more than d. 
From installation plate center to unit’s left side is e. 
From installation plate center to unit’s right side is f. 
B  
: For left side piping, piping connection for liquid should be about g from this line. 
 
: For left side piping, piping connection for gas should be about h from this line. 
1  Mount the installation plate on the wall with 5 screws or more (at least 5 screws). 
(If mounting the unit on the concrete wall, consider using anchor bolts.) 
o
  Always mount the installation plate horizontally by aligning the marking-off line with the thread and using 
a level gauge. 
2  Drill the piping plate hole with ø70 mm hole-core drill. 
o
 
Line according to the left and right side of the installation plate. The meeting point of the extended line is 
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram 
above. The hole center is obtained by measuring the distance namely 128 mm for left and right hole 
respectively. 
o
 
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor 
side. 
 
11.2.2  To Drill a Hole in the Wall and 
Install a Sleeve of Piping 
1  Insert the piping sleeve to the hole. 
2  Fix the bushing to the sleeve. 
3  Cut the sleeve until it extrudes about 15 mm 
from the wall. 
 
  
CAUTION
 
   
           
   When the wall is hollow, please be sure to use 
the sleeve for tube assembly to prevent dangers 
caused by mice biting the connection cable. 
 
4  Finish by sealing the sleeve with putty or 
caulking compound at the final stage. 
 
 
52 
11.2.3  Indoor Unit Installation 
 
 
11.2.3.1  For the Right Rear Piping 
 
 
11.2.3.2  For the Right and Right Bottom 
Piping 
 
 
11.2.3.3   For the Embedded Piping 
 
 
 
 
 
(This can be used for left rear piping and bottom 
piping also.) 