4  REMOTE CONTROL RECEIVING SOUND OFF/ON MODE 
The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed 
continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote 
Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset” button at remote 
control. 
 
Press “Auto OFF/ON button” to toggle remote control receiving sound. 
o
 
Short “beep”: Turn OFF remote control receiving sound. 
o
 
Long “beep”: Turn ON remote control receiving sound. 
 
After Auto OFF/ON Button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON 
Mode is restarted. 
 
15.2 Remote Control Button 
15.2.1 SET 
BUTTON 
š  To check remote control transmission code and store the transmission code to EEPROM 
o
  Press “SET” button continuously for 10 seconds by using pointer. 
o
  Press “TIMER SET” button until a “beep” sound is heard as confirmation of transmission code changed. 
 
15.2.2 RESET 
(RC) 
š  To clear and restore the remote control setting to factory default. 
o
  Press once to clear the memory 
 
15.2.3 RESET 
(AC) 
š  To restore the unit’s setting to factory default 
o
  Press once to restore the unit’s setting. 
15.2.4 TIMER 
▲ 
š  To change indoor unit indicator’s LED intensity 
o
  Press continuously for 5 seconds. 
 
15.2.5 TIMER 
▼ 
š  To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F) 
o
  Press continuously for 10 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
70 
16. Troubleshooting 
Guide 
16.1  Refrigeration Cycle System 
In order to diagnose malfunctions, make sure that there are no 
electrical problems before inspecting the refrigeration cycle. 
Such problems include insufficient insulation, problem with the 
power source, malfunction of a compressor and a fan. 
The normal outlet air temperature and pressure of the refrigeration 
cycle depends on various conditions, the standard values for them 
are shown in the table on the right. 
 
 
 
 
 
 
 
 
 
 
Normal Pressure and Outlet Air Temperature (Standard)
 
Gas pressure 
Mpa 
(kg/cm
2
G) 
Outlet air 
temperature 
(°C) 
Cooling Mode
0.9 ~ 1.2 (9 ~ 12) 
12 ~ 16 
Heating Mode 2.3 ~ 2.9 (23 ~ 29) 
36 ~ 45 
*Condition:  • Indoor fan speed = High 
• Outdoor temperature 35°C at the cooling 
                      mode and 7°C at the heating mode 
                    • Compressor operates at rated frequency       
71 
16.1.1  Relationship between the condition of the air conditioner and pressure and 
electric current 
 
Cooling Mode 
Heating Mode 
Condition of the  
air conditioner 
Low Pressure 
High Pressure 
Electric current 
during operation
Low Pressure 
High Pressure 
Electric current 
during operation
Insufficient refrigerant 
(gas leakage) 
Ô
 
Ô
 
Ô
 
Ô
 
Ô
 
Ô
 
Clogged capillary tube or 
Strainer 
Ô
 
Ô
 
Ô
 
Ò
 
Ò
 
Ò
 
Short circuit in the indoor unit 
Ô
 
Ô
 
Ô
 
Ò
 
Ò
 
Ò
 
Heat radiation deficiency 
of the outdoor unit 
Ò
 
Ò
 
Ò
 
Ô
 
Ô
 
Ô
 
Inefficient compression 
Ò
 
Ô
 
Ô
 
Ò
 
Ô
 
Ô
 
•  Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
72 
16.2  Breakdown Self Diagnosis Function 
16.2.1  Self Diagnosis Function (Three Digits Alphanumeric Code) 
š  Once abnormality has occurred during operation, 
the unit will stop its operation, and Timer LED 
blinks. 
š  Although Timer LED goes off when power supply 
is turned off, if the unit is operated under a 
breakdown condition, the LED will light up again. 
š  In operation after breakdown repair, the Timer 
LED will no more blink. The last error code 
(abnormality) will be stored in IC memory. 
16.2.2  To Make a Diagnosis 
1  Timer LED start to blink and the unit 
automatically stops the operation. 
2  Press the CHECK button on the remote 
controller continuously for 5 seconds. 
3  “- -” will be displayed on the remote controller 
display. 
Note: Display only for “- -”. (No transmitting 
signal, no receiving sound and no Power LED 
blinking.) 
4  Press the “TIMER” ▲ or ▼ button on the 
remote controller. The code “H00” (no 
abnormality) will be displayed and signal will 
be transmitted to the main unit. 
5  Every press of the button (up or down) will 
increase abnormality numbers and transmit 
abnormality code signal to the main unit. 
6  When the latest abnormality code on the main 
unit and code transmitted from the remote 
controller are matched, power LED will light 
up for 30 seconds and a beep sound 
(continuously for 4 seconds) will be heard. If 
no codes are matched, power LED will light up 
for 0.5 seconds and no sound will be heard. 
7  The breakdown diagnosis mode will be 
canceled unless pressing the CHECK button 
continuously for 5 seconds or operating the 
unit for 30 seconds. 
8  The LED will be off if the unit is turned off or 
the RESET button on the main unit is pressed. 
16.2.3  To Display Memorized Error 
(Protective Operation) status 
1  Turn power on. 
2  Press the CHECK button on the remote 
controller continuously for 5 seconds. 
3  “- -” will be displayed on the remote controller 
display. 
Note: Display only for “- -”. (No transmitting 
signal, no receiving sound and no Power LED 
blinking.) 
4  Press the “TIMER” ▲ or ▼ button on the 
remote controller. The code “H00” (no 
abnormality) will be displayed and signal will 
be transmitted to the main unit. The power 
LED lights up. If no abnormality is stored in 
the memory, three beeps sound will be heard. 
5  Every press of the button (up or down) will 
increase abnormality numbers and transmit 
abnormality code signal to the main unit. 
6  When the latest abnormality code on the main 
unit and code transmitted from the remote 
controller are matched, power LED will light 
up for 30 seconds and a beep sound 
(continuously for 4 seconds) will be heard. If 
no codes are matched, power LED will light up 
for 0.5 seconds and no sound will be heard. 
7  The breakdown diagnosis mode will be 
canceled unless pressing the CHECK button 
continuously for 5 seconds or operating the 
unit for 30 seconds. 
8  The same diagnosis can be repeated by 
turning power on again. 
 
 
 
16.2.4  To Clear Memorized Error 
(Protective Operation) status 
after Repair 
1  Turn power on (in standby condition). 
2  Press the AUTO button for 5 seconds (A beep 
receiving sound) on the main unit to operate 
the unit at Forced Cooling Operation modes. 
3  Press the CHECK button on the remote 
controller for about 1 second with a pointed 
object to transmit signal to main unit. A beep 
sound is heard from main unit and the data is 
cleared. 
16.2.5  Temporary Operation (Depending 
On Breakdown Status) 
1  Press the AUTO button (A beep receiving 
sound) on the main unit to operate the unit. 
(Remote control will become possible.) 
2  The unit can temporarily be used until 
repaired. 
 
 
 
 
 
 
 
 