Panasonic CS-E24NKDS / CS-E28NKDS / CU-E24NKD / CU-E28NKD Service Manual ▷ View online
29
11.2 Indoor Unit
11.2.1 How to Fix Installation Plate
The mounting wall shall be strong and solid enough to prevent it from vibration.
Dimension
Model
1 2 3 4 5 6
E7***, E9***, E12***, E15***
485 mm
82 mm
165 mm
158 mm
43 mm
95 mm
E18***, E24***, E28***
585 mm
82 mm
165 mm
158 mm
169 mm
219 mm
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate left edge to unit’s left side is 3.
From installation plate right edge to unit’s right is 4.
B
: For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1 Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
o Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2 Drill the piping plate hole with ø70 mm hole-core drill.
o
Line according to the left and right side of the installation plate. The meeting point of the extended line is
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 128 mm for left and right hole
respectively.
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 128 mm for left and right hole
respectively.
o
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side.
side.
11.2.2 To Drill a Hole in the Wall and
Install a Sleeve of Piping
1 Insert the piping sleeve to the hole.
2 Fix the bushing to the sleeve.
3 Cut the sleeve until it extrudes about 15 mm
2 Fix the bushing to the sleeve.
3 Cut the sleeve until it extrudes about 15 mm
from the wall.
CAUTION
When the wall is hollow, please be sure to use
the sleeve for tube assembly to prevent dangers
caused by mice biting the connection cable.
caused by mice biting the connection cable.
4 Finish by sealing the sleeve with putty or
caulking compound at the final stage.
30
11.2.3 Indoor Unit Installation
11.2.3.1 For the Right Rear Piping
11.2.3.2 For the Right and Right
Bottom Piping
11.2.3.3 For the Embedded Piping
(This can be used for left rear piping and bottom
piping also.)
piping also.)
31
11.2.4 Connect the Cable to the Indoor Unit
1 The inside and outside connection cable can be
connected without removing the front grille.
2 Connection cable between indoor unit and
outdoor unit shall be approved polychloroprene
sheathed 4 x 1.5 mm
sheathed 4 x 1.5 mm
2
flexible cord, type
designation 245 IEC 57 or heavier cord.
3 Bind all the indoor and outdoor connection
cable with tape and route the connection cable
via the escapement.
via the escapement.
4 Remove the tapes and connect the connection
cable between indoor unit and outdoor unit
according to the diagram below.
according to the diagram below.
Note:
Secure the connection cable onto the control board with the holder.
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
32
11.2.5 Wire Stripping and Connecting Requirement
11.2.6 Cutting and Flaring the Piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
Click on the first or last page to see other CS-E24NKDS / CS-E28NKDS / CU-E24NKD / CU-E28NKD service manuals if exist.