11. Installation 
Instruction 
11.1  Select the Best Location 
11.1.1 Indoor 
Unit 
  Do not install the unit in excessive oil fume area 
such as kitchen, workshop and etc. 
  There should not be any heat source or steam 
near the unit. 
  There should not be any obstacles blocking the air 
circulation. 
  A place where air circulation in the room is good. 
  A place where drainage can be easily done. 
  A place where noise prevention is taken into 
consideration. 
  Do not install the unit near the door way. 
  Ensure the spaces indicated by arrows from the 
wall, ceiling, fence or other obstacles. 
  Recommended installation height for indoor unit 
shall be at least 2.5 m. 
11.1.2 Outdoor 
Unit 
  If an awning is built over the unit to prevent direct 
sunlight or rain, be careful that heat radiation from 
the condenser is not obstructed. 
  There should not be any animal or plant which 
could be affected by hot air discharged. 
  Keep the spaces indicated by arrows from wall, 
ceiling, fence or other obstacles. 
  Do not place any obstacles which may cause a 
short circuit of the discharged air. 
  If piping length is over the [piping length for 
additional gas], additional refrigerant should be 
added as shown in the table. 
 
Piping size 
Model 
Horse 
Power 
(HP) 
Gas Liquid 
Std. 
Length 
(m) 
Max 
Eleva-
tion (m)
Min.    
Piping 
Length 
(m) 
Max.   
Piping 
Length 
(m) 
Addi-
tional 
Refri-
gerant 
(g/m)
Piping 
Length 
for add. 
gas (m)
E7*** 3/4HP 
15 
15  20
7.5 
E9*** 1.0HP 
15 
15  20
7.5 
E12**
1.5HP 
9.52 
mm 
(3/8”) 
15 3 15 
20
7.5 
E15**
1.75HP 15 
15 
20
7.5 
E18**
2.0HP 
12.7 
mm 
(1/2”) 
15 3 20 
20
7.5 
E24**
2.5HP 20 
30 
30
10 
E28**
3.0HP 
15.88 
mm 
(5/8”) 
6.35 
mm 
(1/4”) 
20 3 30 
30
10 
Example: For E9*** 
If the unit is installed at 10 m distance, the quantity of 
additional refrigerant should be 50 g .... (10-7.5) m x  
20 g/m = 50 g. 
 
 
 
 
 
 
 
 
 
 
 
 
 
11.1.3  Indoor/Outdoor Unit Installation 
Diagram 
 
 
 
 
 
 
 
  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 107