DOWNLOAD Panasonic CS-E24JKES / CU-E24JKE / CS-E28JKES / CU-E28JKE Service Manual ↓ Size: 8.53 MB | Pages: 108 in PDF or view online for FREE

Model
CS-E24JKES CU-E24JKE CS-E28JKES CU-E28JKE
Pages
108
Size
8.53 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-e24jkes-cu-e24jke-cs-e28jkes-cu-e28jke.pdf
Date

Panasonic CS-E24JKES / CU-E24JKE / CS-E28JKES / CU-E28JKE Service Manual ▷ View online

81
15.5.24. F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
• During cooling, compressor frequency = Fcmax.
• During heating, compressor frequency > Fhrated.
• During cooling and heating operation, running current: 0.65A < I < 1.65A.
• During cooling, indoor intake - indoor pipe < 4
qC.
• During heating, indoor pipe - indoor intake < 5
qC.
Multi Models Only
- Gas shortage detection 1: A gas shortage is detected by checking the CT-detected input current value and the compressor
running frequency. During startup and operating of cooling and heating, input current < 8.78/256 (A/Hz) 
u compressor
running frequency + 0.25.
- Gas shortage detection 2: A gas shortage is detected by checking the difference between indoor pipe temperature and indoor
intake air temperature during cooling and heating.
Malfunction Caused
• Refrigerant shortage (refrigerant leakage).
• Poor compression performance of compressor.
• 2/3 way valve closed.
• Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting
82
15.5.25. F93 (Compressor Rotation Failure)
Malfunction Decision Conditions
A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit.
Malfunction Caused
• Compressor terminal disconnect.
• Outdoor PCB malfunction.
Troubleshooting
83
15.5.26. F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61
qC) is detected by the outdoor pipe
temperature sensor.
Malfunction Caused
• Outdoor pipe temperature rise due to short circuit of hot discharge air flow.
• Outdoor pipe temperature rise due to defective of outdoor fan motor.
• Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor.
• Outdoor pipe temperature rise due to defective outdoor unit PCB.
Troubleshooting
84
15.5.27. F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling and heating, when IPM temperature data (100
qC) is detected by the IPM temperature sensor.
Multi Models Only
• Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated.
• Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat
sink temperature sensor.
Malfunction Caused
• IPM overheats due to short circuit of hot discharge air flow.
• IPM overheats due to defective of outdoor fan motor.
• IPM overheats due to defective of internal circuitry of IPM.
• IPM overheats due to defective IPM temperature sensor.
Multi Models Only
• Compressor OL connector poor contact.
• Compressor OL faulty.
Troubleshooting
Page of 108
Display

Click on the first or last page to see other CS-E24JKES / CU-E24JKE / CS-E28JKES / CU-E28JKE service manuals if exist.