10.4.6. Brazing
As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting
dry nitrogen gas (N
2
) flow.
<Brazing Method for Preventing Oxidation>
 1. Attach a reducing valve to the nitrogen gas cylinder.
 2. Apply a seal onto the clearance between the piping and inserted pipe for the nitrogen gas in order to prevent the nitrogen gas
from flowing backward.
 3. When the nitrogen gas is flowing, be sure to keep the piping end open.
 4. Adjust the flow rate of nitrogen gas so that it is lower than 0.05 m
3
/h, or 0.02 MPa (0.2 kgf/cm
2
) by means of the reducing valve.
 5. After taking the steps above, keep the nitrogen gas flowing until the piping cools down to a certain extent (i.e. temperature at
which pipes are touchable with finger).
 6. Completely remove the flux after brazing.
Fig. 14 Prevention of Oxidation during Brazing
Cautions during brazing
 1. General Cautions
 a. The brazing strength should be high as required.
 b. After operation, airtightness should be kept under pressurized condition.
 c. 
During brazing do not allow component materials to become damaged due to overheating.
 d. The refrigerant pipe work should not become blocked with scale or flux.
 e. The brazed part should not restrict the flow in the refrigerant circuit.
 f. 
No corrosion should occur from the brazed part.
 2. Prevention of Overheating
Due to heating, the interior and exterior surfaces of treated metal may oxidize. Especially, when the interior of the refrigerant
circuit oxidizes due to overheating, scale occurs and stays in the circuit as dust, thus exerting a fatally adverse effect. So,
make brazing at adequate brazing temperature and with minimum of heating area.
 3. Overheating Protection
In order to prevent components near the brazed part from overheating damage or quality deterioration due to flame or heat,
take adequate steps for protection such as (1) by shielding with a metal plate, (2) by using a wet cloth, and (3) by means
of heat absorbent.
 4. Movement during Brazing
Eliminate all vibration during brazing to protect brazed joints from cracking and breakage.
 5. Oxidation Preventative
In order to improve the brazing efficiency, various types of antioxidant are available on the market. However, the
constituents of these are widely varied, and some are anticipated to corrode the piping materials, or adversely affect HFC
refrigerant, lubricating oil, etc. Exercise care when using an oxidation preventive.
10.4.7. Servicing Tips
The drier must also be replaced whenever replacing the refrigerant cycle parts. Replacing the refrigerant cycle parts first
before replacing the drier. The drier is supplied in a vacuum pack. Perform brazing immediately after opening the vacuum
pack, and then start the vacuum within two hours. In addition, the drier also needs to be replaced when the refrigerant has
leaked completely. (Applicable for drier models only)
57
CS-E24DKD CU-E24DKD
11 Installation Instructions
Required tools for Installation Works
1.
Philips screw driver
5.
Spanner
9.
Gas leak detector
13. Multimeter
2.
Level gauge
6.
Pipe cutter
10. Measuring tape
14. Torque wrench
18 N.m (1.8 kgf.m)
55 N.m (5.5 kgf.m)
65 N.m (6.5 kgf.m)
3.
Electric drill, hole core drill
(ø70 mm)
7.
Reamer
11. Thermometer
15. Vacuum pump
4.
Hexagonal wrench (4 mm)
8.
Knife
12. Megameter
16. Gauge manifold
11.1. Safety Precautions
  • Read the following “SAFETY PRECAUTIONS” carefully before installation.
  • Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit
for the model to be installed.
  • The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classified by the symbols:
Symbol with background white denotes item that is PROHIBITED from doing.
  • Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
WARNING
1.
Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2.
Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3.
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5.
For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6.
Use the specified cable (2.5 mm
2
) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no
external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8.
When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into
refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion
and injury.
9.
When connecting the piping, do not allow air or any substances other than the specified refrigerant (R410A) to enter the
refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and
possibly result in explosion and injury.
10.
  • When connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause
abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only
R410A materials.
  • Thickness of copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8
mm.
  • It is desirable that the amount of residual oil is less than 40 mg/10 m.
11. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with
other electrical appliances. Otherwise, it will cause fire or electrical shock.
58
CS-E24DKD CU-E24DKD
CAUTION
1.
This equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2.
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
ATTENTION
1.
Selection of the installation location.
Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
2.
Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains using one of the following method.
Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency.
In some countries, permanent connection of this room air conditioner to the power supply is prohibited.
 1. 
Power supply connection to the receptacle using a power plug.
Use an approved 20A power plug with earth pin for connection to the receptacle.
 2. 
Power supply connection to a circuit breaker for the permanent connection. Use an approved 20A circuit breaker for the permanent
connection. It must be a double pole switch with a minimum 3.5 mm contact gap.
3.
Do not release refrigerant.
Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the
liquid refrigerant, it may cause frostbite.
4.
Installation work.
It may need two people to carry out the installation work.
5.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
59
CS-E24DKD CU-E24DKD
Attached accessories
Applicable piping kit
CZ-52F5, 7, 10BP (E24DK)
Select the best location
INDOOR UNIT
  • There should not be any heat source or steam near
the unit.
  • There should not be any obstacles blocking the air
circulation.
  • A place where air circulation in the room is good.
  • A place where drainage can be easily done.
  • A place where noise prevention is taken into
consideration.
  • Do not install the unit near the door way.
  • Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
  • Recommended installation height for indoor unit
shall be at least 2.5 m.
OUTDOOR UNIT
  • If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
  • There should not be any animal or plant which could
be affected by hot air discharged.
  • Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
  • Do not place any obstacles which may cause a short
circuit of the discharged air.
  • If piping length is over 7.5 m, additional refrigerant
should be added as shown in the table.
Indoor/Outdoor Unit Installation Diagram
  • This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
60
CS-E24DKD CU-E24DKD