21
10.1.2.
Power Printed Circuit Board
TOP VIEW
BOTTOM VIEW
22
10.1.3.
Indicator
TOP VIEW
BOTTOM VIEW
23
11 Installation Instruction
11.1. Select The Best Location
11.1.1.
Indoor Unit
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
11.1.2.
Outdoor Unit
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
Example: For C7HKD
If the unit is installed at a 10m distance, the quantity of
additional refrigerant should be 25g ...... (10 - 7.5)m x 10g/m = 
25g.
11.1.3.
Indoor/Outdoor  Unit Installation
Diagram
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
Piping size
Rated
Length
(m)
Max
Elevation
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Model
Gas
Liquid
C7HKD/
C9HKD
3/8”
1/4”
7.5
5
10
10
C12HKD
1/2”
1/4”
7.5
5
15
10
24
11.2. Indoor Unit
11.2.1.
How To Fix Installation Plate
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 450 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit's left side is 74 mm.
From installation plate right edge to unit's right is 94 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the left and right side edge of the 
installation plate. The meeting point of the extended line
is the centre of the hole. Another method is by putting 
measuring tape at position as shown in the diagram
above. The hole centre is obtained by measuring the dis-
tance namely 150 mm and 125 mm for left and right hole
respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
11.2.2.
To Drill A Hole  In  The  Wall  And
Install A Sleeve Of Piping
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.2.3.
Indoor Unit Installation
11.2.3.1. For the right rear piping
11.2.3.2. For the right and right bottom
piping
:
:
:
For left side piping, piping connection for liquid should be
about 15 mm from this line.
For left side piping, piping connection for gas should be
about 45 mm from this line.
For left side piping, piping connection cable should be
about 800 mm from this line.
Caution
When the wall is hollow, please be sure to use the sleeve for tube
ass’y to prevent dangers caused by mice biting the connecting cable.