DOWNLOAD Panasonic CS-C7DKD / CU-C7DKD / CS-C9DKD / CU-C9DKD / CS-C12DKD / CU-C12DKD Service Manual ↓ Size: 7.64 MB | Pages: 85 in PDF or view online for FREE

Model
CS-C7DKD CU-C7DKD CS-C9DKD CU-C9DKD CS-C12DKD CU-C12DKD
Pages
85
Size
7.64 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
cs-c7dkd-cu-c7dkd-cs-c9dkd-cu-c9dkd-cs-c12dkd-cu-c.pdf
Date

Panasonic CS-C7DKD / CU-C7DKD / CS-C9DKD / CU-C9DKD / CS-C12DKD / CU-C12DKD Service Manual ▷ View online

 • 
When the batteries are inserted for the first time or the
batteries are replaced, you may notice the indications at
remote control’s display screen blink continuously and not
functionable. If this condition happens, try to reset the
remote control by pushing the reset terminal with a pointing
device.
 • 
You may also do the reset to erase the setting at remote
control and restore back the default setting.
12.4.2. Remote Control Transmission Code
 • 
There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor unit. The indoor unit
will only operate when received signal with same transmission code from remote control. This could prevent signal interference
when there are 2 or more indoor unit installed nearby together.
 • 
To change remote control transmission code, short or open jumpers at the remote control printed circuit board.
 • 
Under various setting mode, after select the transmission code combination of remote control, press any button of remote
control to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.
 • 
After signal is received, the various setting mode is cancelled and return to normal operation.
12.5. Remote Control Reset
65
CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD
13.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there is no
electrical problem before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of compressor or fan motor.
The normal outlet air temperature and pressure of the
refrigeration cycle depend on various conditions, the standard
values for them are shown in the table to the right.
13 Troubleshooting Guide
66
CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD
13.2. Relationship between the condition of the air conditioner and
pressure and electric current
Cooling Mode
Condition of the air
conditioner
Low Pressure
High Pressure
Electric current during operation
Insufficient refrigerant (gas
leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of
the outdoor unit
Inefficient compression
 • 
Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
13.3. Diagnosis methods of a malfunction of a compressor
Nature of fault
Symptom
 • 
Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
 • 
The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
 • 
The difference between high pressure and low pressure becomes almost zero.
 • 
Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
 • 
The compressor has a humming sound.
67
CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD
14 Technical Data
14.1. Thermostat characteristics
14.2. Sensible Capacity Chart
CS-C7DKD
220V
Outdoor Temp.
Indoor wet
bulb temp.
30°C
35°C
40°C
46°C
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
1.98
1.50
0.54
1.85
1.44
0.58
1.72
1.39
0.62
1.57
1.32
0.67
19.0°C
2.00
0.59
19.5°C
2.18
1.57
0.55
2.04
1.51
0.59
1.89
1.46
0.63
1.72
1.39
0.68
22.0°C
2.37
1.63
0.56
2.22
1.57
0.60
2.06
1.51
0.64
1.88
1.44
0.70
230V
Outdoor Temp.
Indoor wet
bulb temp.
30°C
35°C
40°C
46°C
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.00
1.52
0.59
1.87
1.46
0.63
1.74
1.40
0.67
1.58
1.33
0.73
19.0°C
2.02
0.64
19.5°C
2.20
1.59
0.60
2.06
1.53
0.64
1.91
1.47
0.69
1.74
1.40
0.74
22.0°C
2.40
1.65
0.61
2.24
1.59
0.65
2.08
1.53
0.70
1.89
1.46
0.75
CS-C9DKD
220V
Outdoor Temp.
Indoor wet
bulb temp.
30°C
35°C
40°C
46°C
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.58
1.96
0.73
2.41
1.88
0.79
2.24
1.80
0.84
2.04
1.71
0.91
19.0°C
2.60
0.80
19.5°C
2.83
2.05
0.75
2.65
1.97
0.80
2.46
1.89
0.86
2.24
1.80
0.93
22.0°C
3.09
2.12
0.76
2.88
2.04
0.82
2.68
1.97
0.87
2.44
1.88
0.94
230V
Outdoor Temp.
Indoor wet
bulb temp.
30°C
35°C
40°C
46°C
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.63
1.99
0.76
2.46
1.91
0.81
2.28
1.84
0.87
2.08
1.75
0.94
19.0°C
2.65
0.83
68
CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD
Page of 85