37
• Timer control
- When ON timer activates when unit stops, previous operation resumes without e-ion operation.
- When ON timer activates during any operation, no change and carry on current operation.
- When OFF timer activates during any operation, all operation stops.
• Indicator
- When e-ion operation starts, e-ion indicator ON.
• Remote Control Receiving Sound
• Power failure
- During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation resumes
immediately.
- During combination operation, if power failure occurs, after power resumes, combination operation resume immediately.
- e-ion operation status is not memorized after OFF the unit. After OFF, when the operation is ON again, air conditioner
operates without e-ion operation.
• e-ion Check Mode
- To check if e-ion is malfunctioning, during e-ion operation press e-ion button for 15 seconds and release to enter e-ion Check
Mode and supplies power to the e-ion AIR PURIFYING SYSTEM.
- If abnormal discharge is detected at filter (short-circuited) due to water or dust adhesion, etc., the e-ion indicator blinks
immediately.
• Error Detection Control
When e-ion indicator blink, it indicates error listed below:
1. e-ion AIR PURIFYING SYSTEM PCB main connector open:
• Judgment Method
- During e-ion operation (include during Patrol operation), e-ion AIR PURIFYING SYSTEM main connector to PCB is
opened.
• Troubleshooting Methods
- Connect the connector or stop operation (include during Patrol operation) to cancel the blinking.
2. Abnormal Discharge error:
• Judgment Method
- During e-ion operation, feedback voltage is-Lo (at micro controller) is detected, it is judged abnormal discharge and stops
power supplies to the e-ion AIR PURIFYING SYSTEM.
- Abnormal discharge is caused by ionizer or filter’s high voltage power supply short-circuits due to water or dust adhesion,
and so forth.
- When abnormal discharge occurred, every 30 minutes the unit supplies power to the e-ion AIR PURIFYING SYSTEM.
- When abnormal discharge occurs for 24 times continuously, e-ion indicator blinks (not applicable for e-ion Check Mode,
where the error will shows immediately despite the 24 times counter)
• Troubleshooting Method
- Press “e-ion” button or “OFF/ON” button to stop the operation and check the e-ion AIR PURIFYING SYSTEM main
connector to PCB.
- After that, press “e-ion” button again to confirm the e-ion indicator not blinking.
- The 24 times counter will be clear after 10 minutes of normal operation or when operation stops.
• Error Reset Method
- Press “OFF/ON” button to OFF the operation.
- Press AUTO OFF/ON button at indoor unit to OFF the operation.
- OFF Timer activates.
- Press “e-ion” button during e-ion individual mode.
- Power supply reset.
Normal Operation
→ e-ion Operation  
: Beep
e-ion Operation
→ Normal Operation  
: Beep
Stop
→ e-ion individual operation
: Beep
e-ion individual operation  
→ Stop
: Long Beep
38
3. Active e-ion air purifying system breakdown error:
• Judgment Method
- When hi-feedback voltage (at micro controller) supplied to filter during e-ion stop, e-ion AIR PURIFYING SYSTEM
breakdown error shows immediately.
- It is due to indoor PCB or filter’s high voltage power supply damage.
- Operations except e-ion continue. Both Timer indicator and e-ion indicator blink.
• Troubleshooting Method
- Press “e-ion” button or “OFF/ON” button to stop the operation.
- Change main circuit board or filter's high voltage power supply.
- When lo-feedback voltage supplied to e-ion AIR PURIFYING SYSTEM during e-ion operation, e-ion indicator and Timer
indicator stop blinking.
39
13 Protection Control
13.1. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
13.3. 60 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
13.4. Starting Current Control
• When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
• The reason of the difference is to reduce the starting current flow.
13.5. Freeze Prevention Control
• If the temperature of the indoor heat exchanger falls below 2
°C continuously for 4 minutes or more, the compressor turns off. The
fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
• Compressor will restart again when the indoor heat exchanger temperature rises to 10
°C (Recovery).
• Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
40
13.6. Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5
°C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
T = Intake air temperature - Indoor heat exchanger temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
• If this condition happens continuously for 5 times within 50 minutes, unit will turn OFF with TIMER LED blinks.
• The 5 times counter can be reset when either one of the following condition happen:
- Unit is OFF by remote control or AUTO OFF/ON button.
- Indoor intake temperature - Indoor piping temperature > 5
°C for 1 minute or more.
- Operation mode change.
• The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
• TIMER LED blinking will be reset if:
- Indoor intake temperature - indoor pipe temperature > 5
°C for 1 minute or more
- Power supply reset.
13.7. Dew Prevention control
• To prevent dew formation at indoor unit discharge area.
• This control start if:-
- Cooling mode or Queit mode is activated.
- Remote Control setting temperature is less than 25
°C.
- Fan speed is at Lo or QLo.
- Room temperature is constant (±1
°C) for 30 minutes.
- Compressor is continuously running.
• Fan speed will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode and Lo fan speed.
• Dew prevention stop condition.
- Remote Control setting temperature is less than 25
°C.
- Fan speed is at Lo or QLo.
- Select Powerful operation.