41
• Indicator
- When e-ion operation starts, e-ion indicator ON.
• Remote Control Receiving Sound
- Normal Operation
o e-ion Operation
: Beep
- e-ion Operation
o Normal Operation
: Beep
- Stop
o e-ion individual Operation
: Beep
- e-ion individual Operation
o Stop
: Long Beep
• Power failure
- During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation resumes
immediately.
- During combination operation, if power failure occurs, after power resumes, combination operation resume immediately.
- e-ion operation status is not memorized after OFF the unit. After OFF, when the operation is ON again, air conditioner
operates without e-ion operation.
• e-ion Check Mode
- To check if e-ion is malfunctioning, during e-ion operation press e-ion button for 15 seconds and release to enter e-ion Check
Mode and supplies power to the Active e-ion Air Purifying System.
- If abnormal discharge is detected at filter (short-circuited) due to water or dust adhesion, etc., the e-ion indicator blinks
immediately.
• Error Detection Control
When e-ion indicator blink, it indicates error listed below:
- Active e-ion Air Purifying system PCB main connector open:
• Judgment Method
- During e-ion operation (include during Patrol operation), active e-ion Air Purifying system main connector to PCB is
opened.
• Troubleshooting Methods
- Connect the connector or stop operation (include during Patrol operation) to cancel the blinking.
- Abnormal Discharge error:
• Judgment Method
- During e-ion operation, feedback voltage is-Lo (at microcontroller) is detected, it is judged abnormal discharge and
stops power supplies to the active e-ion Air Purifying system.
- Abnormal discharge is caused by ionizer or filter’s high voltage power supply short-circuits due to water or dust
adhesion, and so forth.
- When abnormal discharge occurred, every 30 minutes the unit supplies power to the active e-ion Air Purifying system.
- When abnormal discharge occurs for 24 times continuously, e-ion indicator blinks (not applicable for e-ion Check Mode,
where the error will shows immediately despite the 24 times counter)
• Troubleshooting Method
- Press “e-ion” button or “OFF/ON” button to stop the operation and check the active e-ion Air Purifying system main
connector to PCB.
- After that, press “e-ion” button again to confirm the e-ion indicator not blinking.
- The 24 times counter will be clear after 10 minutes of normal operation or when operation stops.
• Error Reset Method
- Press “OFF/ON” button to OFF the operation.
- Press “AUTO OFF/ON” button at indoor unit to OFF the operation.
- OFF Timer activates
- Press “e-ion” button during e-ion individual mode.
- Power supply reset
- Active e-ion Air Purifying system breakdown error:
• Judgment Method
- When hi-feedback voltage (at microcontroller) supplied to filter during e-ion stop, active e-ion Air Purifying system
breakdown error shows immediately.
- It is due to indoor PCB or filter’s high voltage power supply damage.
- Operations except e-ion continue. Both Timer indicator and e-ion indicator blink.
• Troubleshooting Method
- Press “e-ion” button or “OFF/ON” button to stop the operation.
- Change main circuit board or filter’s high voltage power supply.
- When lo-feedback voltage supplied to active e-ion Air Purifying system during e-ion operation, e-ion indicator and Timer
indicator stop blinking.
42
13 Protection Control
(For 13.1. to 13.7. information applies only to Cooling and Soft Dry Operation)
13.1. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
- Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature and compressor OFF temperature during the period.
• This phenomenon is to reduce the built up humidity inside a room.
13.3. 60 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and return
back to the outdoor unit.
13.4. Starting Current Control
• When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
• The reason of the difference is to reduce the starting current flow.
13.5. Freezing Prevention Control
• If the temperature of the indoor heat exchanger falls below 2
qC continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
• Compressor will restart again when the indoor heat exchanger temperature rises to 10
qC (Recovery).
• Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
43
13.6.
Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5
qC or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
s T = Intake air temperature - Indoor heat exchanger temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
13.7. Dew Prevention Control
• To prevent dew formation at indoor unit discharge area.
• This control starts if:
- Cooling mode or Quiet mode is activated.
- Remote Control setting temperature is less than 25
qC.
- Fan speed is at Lo or QLo.
- Room temperature is constant (±1
qC) for 30 minutes.
- Compressor is continuously running.
• Fan speed, angle of horizontal louver (vertical airflow angle) and angle of vertical louver (horizontal airflow angle) will be adjusted
accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode and Lo fan speed.
- The angle of horizontal louver will be changed as table below:
- The angle of vertical louver will be changed as table below:
• Dew prevention stop condition
- Remote control setting temperature is more than 25
qC.
- Fan speed is not set to Lo or QLo.
- Select Powerful operation.
(For 13.8 to 13.14 information applies only to Heating Operation)
13.8. Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
13.9. Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between indoor heat
exchanger and intake air is 5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
s T = Indoor heat exchanger temperature - Intake air temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
44
13.10. Overload Protection Control
• Outdoor Fan Control
- If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor
Heat Exchanger temperature is Tb or more according to Outdoor Air Temperature region as table below:
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
• Compressor High Pressure Control
- If the indoor heat exchanger becomes 68°C or more, the compressor will stop and restart automatically.
- Time Delay Safety Control is activated before the compressor restart.
13.11. 4-Way Valve Control
• 4-way valve always on during Heating operation. (except deicing operation)
• When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
• This is to prevent the refrigerant flow process sound for being occur.
13.12. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.
Page of 64