DOWNLOAD Panasonic CS-A24BD / CS-A28BD / CS-A34BD / CS-A43BD / CS-A50BD / CU-A24BB / CU-A28BB / CU-A34BB / CU-A43BB / CU-A50BB / CU-C24BB / CU-C28BB / CU-C34BB / CU-C43BB / CU-C50BB Service Manual ↓ Size: 17.13 MB | Pages: 127 in PDF or view online for FREE

Model
CS-A24BD CS-A28BD CS-A34BD CS-A43BD CS-A50BD CU-A24BB CU-A28BB CU-A34BB CU-A43BB CU-A50BB CU-C24BB CU-C28BB CU-C34BB CU-C43BB CU-C50BB
Pages
127
Size
17.13 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
cs-a24bd-cs-a28bd-cs-a34bd-cs-a43bd-cs-a50bd-cu-a2.pdf
Date

Panasonic CS-A24BD / CS-A28BD / CS-A34BD / CS-A43BD / CS-A50BD / CU-A24BB / CU-A28BB / CU-A34BB / CU-A43BB / CU-A50BB / CU-C24BB / CU-C28BB / CU-C34BB / CU-C43BB / CU-C50BB Service Manual ▷ View online

Correction of cooling and heating capacities according to
the connecting pipe length.
The data of cooling capacities (marked on the name plate)
are based on 5 metres connecting pipe and horizontal
installation.
(Cooling)
Equivalent Length = actual pipe length +
number of elbow x ELE + number of oil
trap x ELO
ELE : equivalent length of elbow.
ELO : equivalent length of oil trap.
10.2. REFRIGERANT ADDITIONAL
CHARGE
 • 
The piping length exceeds 30 metres.
APPLICABLE FOR ALL MODELS
Before shipment, this air conditioner is filled with the rated
amount of refrigerant subject to 30m piping length. (The
rated amount of refrigerant is indicated on the name plate.)
But when the piping length exceeds 30m, additional charge
is required according to the following table.
For other pipe length of other installation multiply
by the following correction factor to determine the
revised cooling capacity.
(Heating)
Outer diameter of gas
side pipe mm (inch)
ELE
9.52
0.18
12.7 (1/2)
0.20
15.88 (5/8)
0.25
19.05 (3/4)
0.35
Model
Ref. Charge
2.5HP
20g per 1m
3~6HP
50g per 1m
Example :
CS-A24BD3P
In case of 30 m long pipe (one-way), the
amount of refrigerant to be replenished is:
(30 - 30) x 20 = 0g
CS-A43BD3P
In case of 50m long pipe (one-way), the
amount of refrigerant to be replenished is:
(50 - 30) x 50 = 1,000g
10 PIPE LENGTH
10.1. CORRECTION OF COOLING AND HEATING CAPACITIES
49
HIDE AWAY TYPE
10.3. Piping installation by existing piping
It is possible to use the existing piping by adjusting the refrigerant gas volume.
Please do correct piping installation referring to the table below.
Standard piping specification
Existing piping specification (Larger piping)
Heat pump
type
Cooling only
type
Liquid
piping
Gas
piping
Gas charge-
less length
Additional gas
volume
Liquid
piping
Gas piping
Gas charge-
less length
Additional gas
volume
(Ømm)
(Ømm)
(mm)
(g/m)
(Ømm)
(Ømm)
(m)
(g/m)
CU-
A24BBP5
CU-
C24BBP5
6.35
15.88
30
20
9.52
15.88
13
50
CU-
A28BBP5,8
CU-
C28BBP5,8
9.52
15.88
30
50
12.7
15.88
17
100
CU-
A34BBP5,8
CU-
C34BBP5,8
9.52
19.05
30
50
12.7
19.05
17
100
CU-
A43BBP8
CU-
C43BBP8
9.52
19.05
30
50
12.7
19.05
17
100
CU-
A50BBP8
CU-
C50BBP8
9.52
19.05
30
50
12.7
19.05
17
100
Attention
 • 
Please do not decrease the gas piping size. (It causes the breakdown of the compressor)
 • 
The equivalent piping length and the cooling and heating capacity change rate are same as the standard piping
specification.
50
HIDE AWAY TYPE
11 OPERATING CHARACTERISTIC
11.1. OPERATING CHARACTERISTIC
HEAT PUMP MODEL
Model
Main Power
Compressor Motor
Indoor Unit
Outdoor Unit
Source
Fan Motor
Fan Motor
Voltage
Frequency
S.C.
R.C.(A)
IPT(kW)
R.C.
IPT
R.C.
IPT
(V)
(Hz)
(A)
COOL/HEAT
COOL/HEAT
(A)
(kW)
(A)
(kW)
CS-A24BD3P
220
50
49
10.6 / 10.5
2.31 / 2.30
0.66
0.15
0.50
0.11
CU-A24BBP5
230
50
51
10.2 / 10.1
2.31 / 2.30
0.66
0.15
0.50
0.11
240
50
52
9.8 / 9.8
2.31 / 2.30
0.66
0.15
0.50
0.11
CS-A28BD3P
220
50
50
11.35 / 11.05
2.49 / 2.41
0.84
0.19
0.50
0.11
CU-A28BBP5
230
50
52
11.05 / 10.75
2.49 / 2.41
0.84
0.19
0.50
0.11
240
50
54
10.75 / 10.45
2.49 / 2.41
0.84
0.19
0.50
0.11
CS-A28BD3P
380
50
28
4.18 / 3.98
2.49 / 2.41
0.66
0.15
0.50
0.11
CU-A28BBP8
400
50
29
4.13 / 3.93
2.49 / 2.41
0.66
0.15
0.50
0.11
415
50
30
4.08 / 3.88
2.49 / 2.41
0.66
0.15
0.50
0.11
CS-A34BD3P
220
50
94
15.3 / 15.1
3.23 / 3.18
0.84
0.19
1.00
0.22
CU-A34BBP5
230
50
99
15.4 / 15.2
3.23 / 3.18
0.84
0.19
1.00
0.22
240
50
103
15.5 / 15.3
3.23 / 3.18
0.84
0.19
1.00
0.22
CS-A34BD3P
380
50
39
5.13 / 5.23
2.93 / 3.03
0.97
0.22
1.00
0.22
CU-A34BBP8
400
50
41
5.13 / 5.23
2.93 / 3.03
0.97
0.22
1.00
0.22
415
50
42
5.13 / 5.23
2.93 / 3.03
0.97
0.22
1.00
0.22
CS-A43BD3P
380
50
58
6.63 / 6.33
3.82 / 3.67
1.15
0.26
1.10
0.23
CU-A43BBP8
400
50
58
6.63 / 6.33
3.82 / 3.67
1.15
0.26
1.10
0.23
415
50
58
6.63 / 6.33
3.82 / 3.67
1.15
0.26
1.10
0.23
CS-A50BD3P
380
50
69
7.90 / 7.80
4.54 / 4.52
1.31
0.30
1.20
0.25
CU-A50BBP8
400
50
69
7.90 / 7.80
4.56 / 4.54
1.31
0.30
1.20
0.25
415
50
69
7.90 / 7.80
4.54 / 4.52
1.31
0.30
1.20
0.25
COOLING ONLY MODEL
CS-A24BD3P
220
50
49
10.6
2.31
0.66
0.15
0.50
0.11
CU-C24BBP5
230
50
51
10.2
2.31
0.66
0.15
0.50
0.11
240
50
52
9.8
2.31
0.66
0.15
0.50
0.11
CS-A28BD3P
220
50
50
11.35
2.49
0.84
0.19
0.50
0.11
CU-C28BBP5
230
50
52
11.05
2.49
0.84
0.19
0.50
0.11
240
50
54
10.75
2.49
0.84
0.19
0.50
0.11
CS-A28BD3P
380
50
28
4.08
2.49
0.66
0.15
0.50
0.11
CU-C28BBP8
400
50
29
4.03
2.49
0.66
0.15
0.50
0.11
415
50
30
3.98
2.49
0.66
0.15
0.50
0.11
CS-A34BD3P
220
50
94
15.3
3.23
0.84
0.19
1.00
0.22
CU-C34BBP5
230
50
99
15.4
3.23
0.84
0.19
1.00
0.22
240
50
103
15.5
3.23
0.84
0.19
1.00
0.22
CS-A34BD3P
380
50
39
5.13
2.93
0.97
0.22
1.00
0.22
CU-C34BBP8
400
50
41
5.13
2.93
0.97
0.22
1.00
0.22
415
50
42
5.13
2.93
0.97
0.22
1.00
0.22
CS-A43BD3P
380
50
58
6.63
3.82
1.15
0.26
1.10
0.23
CU-C43BBP8
400
50
58
6.63
3.82
1.15
0.26
1.10
0.23
415
50
58
6.63
3.82
1.15
0.26
1.10
0.23
CS-A50BD3P
380
50
69
7.90
4.54
1.31
0.30
1.10
0.25
CU-C50BBP8
400
50
69
7.90
4.54
1.31
0.30
1.10
0.25
415
50
69
7.90
4.54
1.31
0.30
1.10
0.25
Legend: S.C. : Starting Current
R.C. : Running Current
IPT : Power Consumption
51
HIDE AWAY TYPE
12 FAN PERFORMANCE
52
HIDE AWAY TYPE
Page of 127
Display

Click on the first or last page to see other CS-A24BD / CS-A28BD / CS-A34BD / CS-A43BD / CS-A50BD / CU-A24BB / CU-A28BB / CU-A34BB / CU-A43BB / CU-A50BB / CU-C24BB / CU-C28BB / CU-C34BB / CU-C43BB / CU-C50BB service manuals if exist.