49
14.3. Remote Control Button
14.3.1.
SET BUTTON
• To check current remote control transmission code
- Press for more than 10 seconds
• To change the air quality sensor sensitivity
- Press and release with pointer.
- Press the Timer Decrement button to select sensitivity:
1. Low Sensitivity
2. Standard (Default)
3. Hi Sensitivity
- Confirm setting by pressing Timer Set button, a “Beep” sound will be heard. LCD returns to original display after 2 seconds.
- LCD returns to original display if remote control does not operate for 30 seconds
14.3.2.
CLOCK BUTTON
• To change the remote control’s time format.
- Press for more than 5 seconds
14.3.3.
RESET
• To clear and restore the remote control setting to factory default
- Press once to clear the memory.
14.3.4.
TIMER 
• To change indoor unit indicator’s LED intensity
- Press continuously for 5 seconds.
14.3.5.
TIMER 
• To change remote control display from Degree Celsius (
°C) to Degree Fahrenheit (°F).
- Press continuously for 10 seconds.
50
15 Troubleshooting Guide
15.1. Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table on the right.
51
15.1.1.
Relationship between the condition of the air conditioner and pressure and electric
current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
15.1.2.
Diagnosis methods of a malfunction of a compressor and 4-Way Valve
Cooling Mode
Heating Mode
 
Low Pressure
High Pressure
Electric current 
during operating
Low Pressure
High Pressure
Electric current 
during operating
Condition of the air 
conditioner
Insufficient refrigerant
(gas leakage)
Clogged capillary tube
or Strainer
Short circuit in the
indoor unit
Heat radiation deficiency
of the outdoor unit
Inefficient compression
Nature of fault
Symptom
Insufficient compressing of a compressor
• Electric current during operation becomes approximately 20% lower than the normal value.
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
• The difference between high pressure and low pressure becomes almost zero.
Locker compressor
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
• The compressor has a humming sound.
Insufficient switches of the 4-way valve
• Electric current during operation becomes approximately 80% lower than the normal value.
• The temperature different between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.
52
16 Disassembly and Assembly Instructions
16.1. Indoor Electronic Controllers and Control Board Removal Procedures
WARNING
• Cautions! When handling electronic controller, be careful of electrostatic discharge.
• Be sure to return the wiring to its original position.
• There are many high voltage components within the heat sink cover so never touch the interior during operation. Wait at least two minutes after
power has been turned off.
Page of 69