6 Wiring Diagram
17
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
18
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Anti-Freezing Control
  • If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
  • Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
7 Operation Details
7.1. Cooling Mode Operation
  • When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.
  • When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
  • The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
  • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
▲ T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
  • Purpose is to prevent dew formation on indoor unit air discharge area.
  • When the following conditions occur for 30 minutes continuously, anti-dew formation is controlled by indoor fan speed shift to
low (Changed to HLo):
  − Indoor intake air temperature is more than 24°C and less than 30°C.
  − Remote Control setting temperature is less than 25°C.
  − Compressor is on.
  − Cooling operation mode.
  − Indoor Fan motor operate at Low fan speed.
  • This control is cancelled immediately when above condition is changed.
19
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
Compressor Protection Control
Automatic Fan Speed Mode
  • After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
  • If the above phenomenon is repeated for 3 times, the compressor will stop totally.
  • The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
When Automatic Fan Speed is selected at Remote Control during cooling operation.
  • Fan speed rotates in the range of Hi to Me.