DOWNLOAD LG LWC1264AAG_AAN_ACE_ACF_ACN_ACP_BAG_BCF_BCG_BCS_ACG / LWC1264PAG_PAN_PCG_QAG_QAS_QAE / LWC1264AHE_AHF_AHG_ABG_BBG / LWC1264PBG_PHG_QBG_VBS / LWC126CGAB0 / LWC1264BAE / W12LH Service Manual ↓ Size: 1.43 MB | Pages: 52 in PDF or view online for FREE

Model
LWC1264AAG_AAN_ACE_ACF_ACN_ACP_BAG_BCF_BCG_BCS_ACG LWC1264PAG_PAN_PCG_QAG_QAS_QAE LWC1264AHE_AHF_AHG_ABG_BBG LWC1264PBG_PHG_QBG_VBS LWC126CGAB0 LWC1264BAE W12LH
Pages
52
Size
1.43 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lwc1264aag-aan-ace-acf-acn-acp-bag-bcf-bcg-bcs-acg.zip
Date

LG LWC1264AAG_AAN_ACE_ACF_ACN_ACP_BAG_BCF_BCG_BCS_ACG / LWC1264PAG_PAN_PCG_QAG_QAS_QAE / LWC1264AHE_AHF_AHG_ABG_BBG / LWC1264PBG_PHG_QBG_VBS / LWC126CGAB0 / LWC1264BAE / W12LH Service Manual ▷ View online

2.4 REFRIGERATING CYCLE
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 4 screws which fasten the
brace.(Refer to section 2.2.1)
3. Remove the 5 screws which fasten the condenser
and shroud.
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the condenser
connections.
5. Remove the condenser.
6. Re-install the component by referring to notes.
(See Figure 17)
2.4.2 EVAPORATOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 2 screws which fasten the evaporator.
3. Move the evaporator sideways carefully.
(Refer to section 2.2.1)
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the evaporator
connections.
5. Remove the evaporator.
6. Re-install the component by referring to notes.
(See Figure 18)
2.4.3 CAPILLARY TUBE
1. Remove the cabinet. (Refer to section 2.1.2)
2. After discharging the refrigerant completely,
unbraze the interconnecting tube at the capillary
tube.(See caution above)
3. Remove the capillary tube.
4. Re-install the component by referring to notes.
—13—
Figure 18
Figure 17
Discharge the refrigerant system using a
Freon
TM
Recovery System.
If there is no valve to attach the recovery 
system, install one (such as a WATCO A-1)
before venting the Freon
TM
. Leave the valve in
place after servicing the system.
CAUTION
—14—
— Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to
Discharge the refrigerant system using a Freon
TM
recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the Freon
TM
. Leave the valve in place after 
servicing the system.
2. After discharging the unit completely, remove the
desired component, and unbraze the pinch-off
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated figure
19A.
2) Start the vacuum pump, slowly open manifold 
valves A and B with two full turns
counterclockwise and leave the valves open.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
3) Operate the vacuum pump for 20 to 30 minutes, 
until 600 microns of vaccum is obtained. Close 
valves A and B, and observe vacuum gauge for 
a few minutes. A rise in pressure would 
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop 
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure
19B.
Open valve C.
Discharge the line at the manifold connection.
5) The system is now ready for final charging.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from
the High-side. If the total charge cannot be put 
in the High-side, the balance will be put in the 
suction line through the access valve which you 
installed as the system was opened.
2) Connect the charging cylinder as shown in figure 
19B.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to 
enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not 
take it. Close valve A.
5) With the unit running, open valve B and add the 
balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to 
rise to 30 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps b. and c. until the balance of the 
charge is in the system.
6) When satisfied the unit is operating correctly, 
use the pinch-off tool with the unit still running 
and clamp on to the pinch-off tube. Using a tube 
cutter, cut the pinch-off tube about 2 inches from 
the pinch-off tool. Use sil-fos solder and solder 
pinch-off tube closed. Turn off the unit, allow it to 
set for a while, and then test the leakage of the 
pinch-off connection.
NOTES
If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.
CAUTION
—15—
Equipment needed: Vacuum pump, Charging cylinder,  Manifold gauge, Brazing equipment. Pin-off tool capable
of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
A
COMPOUND GAUGE
EVAPORATOR
(LOW PRESSURE SIDE)
COMPRESSOR
CAPILLARY TUBE
CONDENSER
(HIGH PRESSURE SIDE)
SEE INSETS
BELOW
MANIFOLD
GAUGE
B
A
B
COMPOUND GAUGE
EVAPORATOR
(LOW PRESSURE SIDE)
SEE INSETS
BELOW
CONDENSER
(HIGH PRESSURE SIDE)
MANIFOLD
GAUGE
COMPRESSOR
CAPILLARY TUBE
A
B
EXTERNAL
VACUUM PUMP
A
CHARGING
CYLINDER
LOW HI
B
C
Figure 19A-Pulling 
Vacuum
(Cooling Model)
(Heating Model)
Figure 19B-Charging
—16—
3. INSTALLATION
3.1 SELECT THE BEST LOCATION
1.To prevent vibration and noise, make sure the unit is
installed securely and firmly.
2.Install the unit where the sunlight does not shine directly
on the unit.
3.The outside of the cabinet must extend outward for at
least 12" and there should be no obstacles, such as a
fence or wall, within 20" from the back of the cabinet
because it will prevent heat radiation of the condenser.
Restriction of outside air will greatly reduce the cooling
efficiency of the air conditioner.
4.Install the unit a little slanted so the back is slightly lower
than the front (about 
1
/
2
"). This will help force con-densed
water to the outside.
5.Install the unit from the bottom about 30"~60" above the
floor level.
3.2 CHECK OF INSTALLATION
The setting conditions must be checked prior to initial
starting. The undermentioned items are especially important
checking points when the installation is finished.
1. Grounding wire (Green or Green and Yellow) is provided
in the power cord. The green wire must be grounded.
2. Connect to a single-outlet 15A circuit.
(or 20A circuit for Electric Heater Model)
3. To avoid vibration or noise, make sure the air
conditioner is installed securely.
4 Avoid placing furniture or draperies in front of the air inlet
and outlet.
3.3. HOW TO DRAIN
(When using drain pipe)
The air conditioner must be installed horizontally or tilted
slightly to the outside for proper water drainage.
On exceptionally hot and humid days the air conditioner
may overflow conclensed water.
If the air conditioner is used in hot and a high humidity
zone, exchange the 
HOLE RUBBER for the 
DRAIN
PIPE.(See figure 21, figure 22.)
3.4 HOW TO ATTACH DRAIN PAN
The air conditioner employs a proper drain method whereby
the condensate water (moisture removed from the air) is
drained to the outside. In very humid weather, (and for
reverse cycle models in the reverse mode) excessive
condensate water removed from the air may cause some
water to collect. To remove this excess water you can install
the drain pan as detailed below.
1. Remove the hole rubber from the base-pan(for some models).
2. Install the drain pan to the left corner of the cabinet 
with 4 (or 2) screws.
3. Connect the drain hose to the outlet located at the
bottom of the drain pan.
You can purchase the drain hose or tubing locally to
satisfy your particular needs. (Drain hose is not supplied)
All side louvers of the cabinet must remain exposed
to the outside of the structure.
AWNING
COOLED AIR
HEAT
RADIATION
30"~60"
ABOUT 
1
/
2
"
Over 20"
FENCE
BASE PAN
HOLE RUBBER
DRAIN PIPE
1
BOTTOM
2
BASE PAN
BOTTOM
SCREW
CABINET
DRAIN PAN
DRAIN HOSE
Figure 22
Figure 23
Figure 21
Figure 20
CAUTION
Page of 52
Display

Click on the first or last page to see other LWC1264AAG_AAN_ACE_ACF_ACN_ACP_BAG_BCF_BCG_BCS_ACG / LWC1264PAG_PAN_PCG_QAG_QAS_QAE / LWC1264AHE_AHF_AHG_ABG_BBG / LWC1264PBG_PHG_QBG_VBS / LWC126CGAB0 / LWC1264BAE / W12LH service manuals if exist.