COMPLAINT
CAUSE
REMEDY
If not running, determine the cause. Replace if
required.
Remove the cabinet, inspect the interior surface of
the condenser. If restricted, clean carefully with a
vacuum cleaner (do not damage fins) or brush.
Clean the interior base before re-assembling.
If the condenser fins are closed over a large area on
the coil surface, head pressures will increase,
causing the compressor to cycle.
Straighten the fins or replace the coil.
Test the capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean or replace.
Close if open.
Determine if the unit is properly sized for the area to
be cooled.
Check the set screw, or clamp. If loose or missing,
correct. If the blower or fan is hitting scroll or barrier,
rearrange the air handling parts.
Remove the cabinet and carefully rearrange the
tubing not to contact the cabinet, compressor,
shroud and barrier.
Fan motor
Condenser air flow
restriction
Condenser fins
(damaged)
Capacitor
Wiring
Refrigeration system
Air filter
Exhaust damper door
Unit undersized
Blower or fan
Copper tubing
Compressor cycles on
overload
Insufficient cooling
Excessive noise
—18—
4.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two kinds.
The one is called Starting Failure which is caused from an electrical defect. The other is Ineffective Air
Conditioning 
caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling is ineffective.
Ineffective Cooling 
Check of outdoor coil
(heat exchanger) & fan
operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the
unit is beyond repair.
Satisfactory operation with
temperature difference of
inlet & outlet air ; 
44~50°F(7~10°C) 
Check heat load 
increase.
Clean condenser.
Not on separate circuit
Check inside gas
pressure.
Adjusting of refrigerant
charge
Malfunction of compressor
Replacement of
compressor
Check of cold  air circulation
 for smooth flow.
Dirty indoor coil
(Heat exchanger)
Remove obstruction.
Check clogging in 
refrigeration circuit.
Repair clogging in 
refrigeration circuit.
Obstruction at air outlet
Clogged of air filter
Malfunction of fan
—19—
Fails to Start
Check of circuit breaker
and fuse.
Gas leakage of feeler bulb
of thermostat
Check of control switch.
Only fan fails to start.
Improper wiring
Defect of fan motor
capacitor
Resistance irregular motor 
(    ).
Insulation irregular motor 
(    ).
Replacement of fan motor
Regular but fails to start
Replacement of compressor
(Locking of rotor, metal)
Improper thermostat setting
Loose terminal connection
Improper wiring
Irregular motor resistance (   )
Irregular motor insulation (   )
Replacement of compressor
(Motor damaged)
Drop of power voltage
 Check capacitor.
Replacement
Only compressor fails to
start.
Defect of compressor
capacitor
Check of power source.
Check of control switch
setting.
—20—
Is the Trans output power
AC 220V?
Is the Trans output power
about AC 13V?
Is shorted the Trans. output?
Is output Voltage of IC2
DC 12V?
Is output Voltage of IC3
DC 5V?
Is the voltage No.20 of IC1
DC 5V?
Exchange Main PCB Ass'y.
Is the 
connection between
Main and Display 
all right?
Is the reset circuit all right?
(The No.16 of 
IC1 is 5V.)
• Check the Fuse.
• Check the wiring diagram.
• Check the Main 
  PCB pattern.
• Exchange the Trans.
• Exchange BD1.
• Exchange IC2.
• Exchange IC3.
• Exchange IC4, C07.
• Connect connector
  exactly.
• Check the PCB 
  pattern.
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
ELECTRIC PARTS TROUBLESHOOTING GUIDE 
(LW-B0967CL)
Possible Trouble 1
• The unit does not operate.
Page of 36