DOWNLOAD LG LV-C3681CL_HL / LV-D4881CL_HL / LV-D6081CL_HL Service Manual ↓ Size: 2.24 MB | Pages: 43 in PDF or view online for FREE

Model
LV-C3681CL_HL LV-D4881CL_HL LV-D6081CL_HL
Pages
43
Size
2.24 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lv-c3681hl.zip
Date

LG LV-C3681CL_HL / LV-D4881CL_HL / LV-D6081CL_HL Service Manual ▷ View online

Dimensions
–5–
82.5
82.5
(1) Indoor Unit
Dim(mm) 
Model
A
B
C
36K Btu
1605
235
1440
38K, 60K Btu
1905
270
1740
(2) Outdoor Unit
–6–
H
W
D
H
W
D
Dim(mm) 
Model
W
H
D
36K, 48K Btu
950
950
370
60K Btu
950
1227
370
Refrigeration Cycle Diagram
• HEAT PUMP(LV-C3681HL, LV-D4881HL, LV-D6081HL)
• Rated performance for refrigerant line length of: 5.0m
• If 36K Capacity is installed at a distance of 15m, 500g of refrigerant 
should be added ....................................................(15-5.0) x 50g
–7–
INDOOR UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
HEAT
EXCHANGER
COMPRESSOR
GAS SIDE
LIQUID SIDE
COOLING
HEATING
REVERSING
VALVE
36K
3/4"
3/8"
5.0
20
5
10
50
48K
3/4"
1/2"
5.0
25
5
15
55
60K
3/4"
1/2"
5.0
30
5
20
60
Capacity
GAS
LIQUID
Rated
Max.
Rated
Max.
* Additional
refrigerant
(g/m)
Pipe Size
(Diameter:ø)
Length (m)
Elevation (m)
–8–
• COOLING ONLY(LV-C3681CL, LV-D4881CL, LV-D6081CL)
INDOOR UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
(CONDENSER)
HEAT
EXCHANGER
(CONDENSER)
COMPRESSOR
GAS SIDE
LIQUID SIDE
• Rated performance for refrigerant line length of: 5.0m
• If 36K Capacity is installed at a distance of 15m, 500g of refrigerant 
should be added ....................................................(15-5.0) x 50g
36K
3/4"
3/8"
5.0
20
5
10
50
48K
3/4"
1/2"
5.0
25
5
15
55
60K
3/4"
1/2"
5.0
30
5
20
60
Capacity
GAS
LIQUID
Rated
Max.
Rated
Max.
* Additional
refrigerant
(g/m)
Pipe Size
(Diameter:ø)
Length (m)
Elevation (m)
Page of 43
Display