Operation Details
(1) The function of main control
1. Time Delay Safety Control
• 3min… The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 5sec… Vertical air flow direction control louvers open in 5 seconds to prevent noise between louvers and wind.
• 30sec… The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode while compress is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Airflow Direction Control
• This function is to swing the louver up and down automatically and to set it at the desired position.
• The procedure is as the following.
1st ; Press the ON/OFF Button to operate the product.
2nd ; Press the Airflow Direction Control Button to swing the louver up and down automatically.
3nd ; Repress the Airflow Direction Control Button to set the louver as the desired position.
MODE 0
1
2
3
4
5
6
7
135
°
Cooling
MODE
MODE
MODE
MODE
MODE
MODE
MODE
9
MODE
(CLOSE)
Heating
OPEN
135
°
12
°
Cooling
Heating
Heating
Heating
MODE 1
MODE 2
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
CLOSE
OPEN
135
°
12
°
Cooling
Heating
Heating
Heating
MODE 1
MODE 2
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
CLOSE
Heating
OPEN
135
°
12
°
Cooling
Heating
Heating
Heating
MODE 1
MODE 2
MODE 3
MODE 4
MODE 5
MODE 6
MODE 7
MODE 8
MODE 9
CLOSE
–13–
※
For Heating Model
• Airflow direction control figure when installed on
the floor.
• Airflow direction control figure when installed
under the ceiling.
3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following
4. Cooling or Heating Mode with Sleep Mode Auto Operation
• When selecting the Cooling( ) or the Heating(
) combined with the Sleep Mode Auto Operation(
), the
operation diagram is as following.
■
Cooling Mode with the Sleep Mode
• The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
■
Heating Mode with the Sleep Mode.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air temp.
COMP. ON
(SET TEMP.+0.5°C)
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP. -0.5°C)
(SET TEMP. -0.5°C)
More than
More than
3 minutes
3 minutes
INDOOR FAN
Low
Low
Low
Low
Low
COMPRESSOR
ON
OFF
ON OFF
ON
30 minutes
30 minutes
1°C
1°C
–14–
Setting Temp. +3°C
(Compressor OFF)
(Compressor OFF)
Setting Temp.
(Compressor ON)
(Compressor ON)
Indoor Fan
Low.
Low.
Low.
Low.
Low.
Low.
Compressor
ON
OFF
ON
OFF
ON
OFF
Intake Air temp.
COMP. ON
(SET TEMP.+0.5°C)
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP. -0.5°C)
(SET TEMP. -0.5°C)
More than
More than
3 minutes
3 minutes
Selecting
Selecting
Selecting
fan speed
fan speed
fan speed
COMPRESSOR
ON
OFF
ON OFF
ON
INDOOR FAN
Low Low
5. Auto Operation
• The operation procedure is as following. (Cooling & Heating Model)
*
If initial mode is decided, that mode is continued without the room temperature changing.
*
For cooling operation mode over 24°C setting temperature and fan speed are same as cooling only model.
• Auto Operation for Cooling. (Cooling only Model)
–15–
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode
Indoor fan speed
are automatically decided by Fuzzy rule.
Setting temperature
Intake-air
temperature
Operation Mode
Heating
Soft Dry
Cooling
Operation Condition
Intake-air Temperature
Setting temperature
Fan speed
Air Direction Control
Over 26°C
25°C
Over 24°C~below 26°C
Intake air -1°C
Over 22°C~below 24°C
Intake air -0.5°C
Over 20°C~below 22°C intake air temperture
below 20°C
20°C
Over 20°C~below 30°C
Fuzzy control
below 20°C
20°C
over 30°C
30°C
below 21°C
below
24°C
~
Over 24°C
Over
21°C
When Auto Operation
initial start
When pressing room temp-
erature setting button
during Auto Operation
Controlled
by Fuzzy logic
In this mode, when
pressing the verti-
cal air diretion con-
trol.
Button, louvers
moves to 1/f
rhythm (refer to
page 17)
pressing the verti-
cal air diretion con-
trol.
Button, louvers
moves to 1/f
rhythm (refer to
page 17)
Intake-Air temp
Setting Temp. +0.5°C
(Compressor OFF)
(Compressor OFF)
Setting Temp.-0.5°C
(Compressor ON)
(Compressor ON)
Indoor Fan
Compressor
ON
ON
OFF
OFF
Fuzzy Speed
• Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
- Compressor OFF temperature; Setting temperature -0.5°C
• Auto Operation for Heating.
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature +3°C
- Compressor OFF temperature; Setting temperature +3°C
• 1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button, lou-
ver moves as following cycle.
–16–
Intake Air temp.
below 20°C over
20
℃
~below 21°C
Setting temp.
20°C
Intake air temp. +0.5°C
21.5°C
20°C
20°C
Intake-Air temp.
Setting temp.
20.5°C
21°C
MODE0
MODE1
MODE2
MODE3
MODE4
MODE5
MODE6
MODE9
(CLOSED)
End
Start