DOWNLOAD LG LS-Q076ABL_BBG_BEL_ABG / LS-Q096ABL_BBG_BEL_AEL / LS-Q096ACG_ADG_ADL_BDL / LS-Q096AHG_ABG_ABM / LS-Q096BAG_BDG / LS-Q096ACL_AAG / LS-Q082BAG_BAM / LS-Q082AAL_ACG_ACL_ACM Service Manual ↓ Size: 7.78 MB | Pages: 127 in PDF or view online for FREE

Model
LS-Q076ABL_BBG_BEL_ABG LS-Q096ABL_BBG_BEL_AEL LS-Q096ACG_ADG_ADL_BDL LS-Q096AHG_ABG_ABM LS-Q096BAG_BDG LS-Q096ACL_AAG LS-Q082BAG_BAM LS-Q082AAL_ACG_ACL_ACM
Pages
127
Size
7.78 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-q076abl-bbg-bel-abg-ls-q096abl-bbg-bel-ael-ls-q.zip
Date

LG LS-Q076ABL_BBG_BEL_ABG / LS-Q096ABL_BBG_BEL_AEL / LS-Q096ACG_ADG_ADL_BDL / LS-Q096AHG_ABG_ABM / LS-Q096BAG_BDG / LS-Q096ACL_AAG / LS-Q082BAG_BAM / LS-Q082AAL_ACG_ACL_ACM Service Manual ▷ View online

-28-
2) Connect the cable to the outdoor unit
1. Remove the control cover from the unit by loos-
ening the screw.
Connect the wires to the terminals on the control
board individually.
2. Secure the cable onto the control board with the
cord clamp.
3. Refix the control cover to the original position
with the screw.
4. Use a recognized circuit breaker "A" 
between the power source and the unit. 
A disconnecting device to adequately disconnect
all supply lines must be fitted.
Connecting 
cable
Terminal block
(Pillar terminal)
Cover control
Outdoor unit
Outdoor unit
Over
5mm
Holder for 
connecting 
cable
Over 5mm
Terminal block
(Pillar terminal)
Holder for
power supply
cord
Cover control
Connecting cable
LS-Q096AAL
LS-Q096ABL
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 27))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal
function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an
air gap contact separation of at least 3mm in each active(phase) conductors.
CAUTION
7k~14k
18k
24k~28k 30k, 32k 36k, 38k
15
20
30
30
40
Circuit
Breaker
(A)
Grade
-29-
4. Checking the Drainage and Forming the Pipings
1) Checking the drainage
1. To remove the front panel from the indoor unit.
• Set the air direction louvers up-and-down to the posi-
tion(horizontally) by hand.
• Remove the securing screws that retain the front pan-
el. Pull the lower left and right sides of the grille
toward you and lift it off.
2. To check the drainage.
• Pour a glass of water on the evaporator.
• Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the drain
exit.
3. Drain piping
• The drain hose should point downward for easy drain
flow.
• Do not make drain piping.
2) Form the piping
1. Form the piping by wrapping the connecting por-
tion of the indoor unit with insulation material and
secure it with two kinds of vinyl tapes.
• If you want to connect an additional drain hose, the
end of the drain outlet should be routed above the
ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below
the indoor unit perform the following.
• Tape the piping, drain hose and connecting cable from
down to up.
• Secure the tapped piping along the exterior wall using
saddle or equivalent.
3. In cases where the Outdoor unit is installed above
the Indoor unit perform the following.
• Tape the piping and connecting cable from down to up.
• Secure the taped piping along the exterior wall. Form
a trap to prevent water entering the room.
• Fix the piping onto the wall by saddle or equivalent.
Pull the right and
the left side.
Taping
Drain
hose
Pipings
Connecting
cable
Trap is required to prevent water
from entering into electrical parts.
Seal small openings
around pipings with a
gum type sealer.
Taping
Drain hose
Pipings
Connecting
cable
LS-Q096AAL
LS-Q096ABL
Seal a small opening 
around the pipings 
with gum type sealer.
Trap
Trap
Downward slope
Do not raise
Accumulated
drain water
Tip of drain hose 
dipped in water
Air
Waving
Water
leakage
Water
leakage
Ditch
Less than 
50mm gap
Water
leakage
Details of 2002 LG Model Name
-3-
1
2
3
4
5
6
7
8
9
Code Type
Code 
of 
Model
Meaning
1,2
Type of Airconditioner
A~Z
LS: LG Split Type Airconditioner
3
Chassis
A~Z
Name of toll of Unit
Ex. LS-R 
S R Chassis
4,5
Capacity(Btu/h)
1~9
Cooling/Heating Capacity
Ex. "09" 
9,000Btu/h
6
Electric Range
1~9
Electric Standard
115V/60Hz
220~240V/50Hz
➔ 
220V/60Hz
110V, 50/60Hz
208~230V/60Hz 8 
380~415V/50Hz
200~220V/50Hz
380~415V/60Hz
7
Serial No.
0~9
A~Z
8
Cooling/Heating
A~Z
9
LG/OEM Brand
A~Z
L: LG Brand    
M: 1st OEM Brand
G: 2nd LG Brand
N: 2nd OEM Brand
-
Basic
A
0
Plasma Filter
B
1
Auto Swing + Plasma Filter
C
2
Telephone + LED Display
D
3
Telephone + LCD Display
E
4
Auto Swing + Plasma Filter + Telephone + LCD
F
5
Low Ambient + Ambient/change
G
6
Plasma Filter + Low Ambient + Ambient/change
H
7
Internet
J
8
Auto Swing + Plasma Filter + Oxygen Generator
K
9
Auto Swing + Soft Start
L
Z
Auto Swing + Star Rating
M
Y
Auto Swing + Star Rating + Plasma Filter
N
X
Auto Swing + Soft Start + Star Rating
P
W
Auto Swing + Soft Start + Star Rating 4 + Plasma
Q
V
Auto Swing + Telephone + LCD
R
U
Auto Swing + Telephone + LCD + Soft Start
S
T
C/O
C
A
D
G
K
H/P
H
B
E
J
L
E/H+C/O
X
5
7
-
-
E/H+H/P
Y
6
8
-
-
C/O
F
M
Q
-
-
H/P
R
P
S
-
-
C/O
V
W
1
3
H/P
N
Y
2
4
H/P
T
H/P
U
INDOOR
BASIC
BASIC
PLASMA
PLASMA
GOLD FIN
OUTDOOR
BASIC
GOLD FIN
GOLD FIN
BASIC
GOLD FIN
UNIT
R22
HFC
R22+AC INV.
HFC+AC
INV.
HFC+DC
INV.
-30-
1. Check that all tubing and wiring have been properly
connected.
2. Check that the gas and liquid side service valves are
fully open.
1. Prepare remote control
1. Remove the battery cover 
by pulling it according to the
arrow direction.
2. Insert new batteries making 
sure that the (+) and (–) of 
battery are installed correctly.
3. Reattach the cover by
pushing it back into position.
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use recharge-
able batteries.
• Remove the batteries from the remote control if the
system is not going to be used for a long time.
2.  Settlement of outdoor unit
• Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming
the influence of wind and earthquake.
• In the case when the vibration of the unit is conveyed
to the hose, secure the unit with an anti-vibration
bushing.
3. Evaluation of the performance
Operate unit for 15~20 minutes, then check the system
refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge
of air.
3. Ensure the difference between the intake tempera-
ture and the discharge is more than 8°C(46°F) (Cool-
ing) or (Heating).
4. For reference; the gas side pressure of optimum con-
dition is as below.(Cooling)
NOTE: If the actual pressure is higher than shown, the
system is most likely over-charged, and charge
should be removed. If the actual pressure are
lower than shown, the system is most likely
undercharged, and charge should be added.
The air conditioner is now ready for use.
Bolt
Tubing connection
Discharge 
temperature
Discharge air
Intake temperature
5. Test Running
R-22
35°C (95°F)
4~5kg/cm
2
G(56.8~71.0 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side 
service valve.
This is performed when the unit is to be relocated
or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the
outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the
unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to
the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge
the air from the manifold hose using the refrigerant
gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the
cooling operation.
5. When the low-pressure gauge reading becomes 1
to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the
gas side valve stem and then quickly turn off the
unit. At that time, Pump Down has been completed
and all refrigerant gas will have been collected in
the outdoor unit.
PUMP DOWN
Page of 127
Display

Click on the first or last page to see other LS-Q076ABL_BBG_BEL_ABG / LS-Q096ABL_BBG_BEL_AEL / LS-Q096ACG_ADG_ADL_BDL / LS-Q096AHG_ABG_ABM / LS-Q096BAG_BDG / LS-Q096ACL_AAG / LS-Q082BAG_BAM / LS-Q082AAL_ACG_ACL_ACM service manuals if exist.