1) Selection of the best location
1. Indoor unit
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in front of
the unit.
• Make sure that condensation drainage can be conve-
niently routed away.
Do not install near a doorway.
• Ensure that the space around the left and right of the
unit is more than "A". The unit should be installed as
high on the wall as possible, allowing a minimum of
"B" from ceiling.
• Use a stud finder to locate studs to prevent unneces-
sary damage to the wall.
2. Outdoor unit
• If an awning is built over the unit to prevent direct sun-
light or rain exposure, make sure that heat radiation
from the condenser is not restricted.
• Ensure that the space around the back and sides is
more than 10cm. The front of the unit should have
more than 70cm of space.
• Do not place animals and plants in the path of the
warm air.
• Take the air conditioner weight into account and select
a place where noise and vibration are minimum.
• Select a place so that the warm air and noise from the
air conditioner do not disturb neighbors.
2) Piping length and elevation
Installation 
1. Installation of indoor, Outdoor unit 
-20-
More than "A"
More than "B"
More than 2.3m
More than "B"
More than 10 cm
More than 10 cm
More than 70 cm
Install the indoor unit on the wall where the height
from the floors more than 2.3 meters.
CAUTION
• Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters.
CAUTION
Grade
Clearance(cm)
A
B
7K~28K
10
5
30K~38K
30
12
Pipe Size
Capacity
(Btu/h)
GAS
LIQUID
Max. 
Length
(m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B
(m)
Standard
Length
(m)
7k~14k
3/8"(Ø9.52)
1/4"(Ø6.35)
4 or 7.5
7
15
20
1/2"(Ø12.7)
1/4"(Ø6.35)
4 or 7.5
7
15
20
1/2"(Ø12.7)
1/4"(Ø6.35)
4 or 7.5
15
30
20
18k~28k
5/8"(Ø15.88)
1/4"(Ø6.35)
4 or 7.5
15
30
20
5/8"(Ø15.88)
3/8"(Ø9.52)
4 or 7.5
15
30
30
30k~38k
5/8"(Ø15.88)
3/8"(Ø9.52)
7.5
15
30
30
3/4"(Ø19.05)
3/8"(Ø9.52)
7.5
15
30
50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
-21-
3) How to fix installation plate
The wall you select should be strong and solid enough
to prevent vibration
1. Mount the installation plate on the wall with four
type A screws. If mounting the unit on a concrete
wall, use anchor bolts.
• Mount the installation plate horizontally by aligning
the centerline using a level.
2. Measure the wall and mark the centerline. It is
also important to use caution concerning the
location of the installation plate-routing of the
wiring to power outlets is through the walls typi-
cally. Drilling the hole through the wall for piping
connections must be done safely.
4) Drill a hole in the wall
• Drill the piping hole with a ø70mm hole core drill. Drill
the piping hole at either the right or the left with the
hole slightly slanted to the outdoor side.
Installation Plate
Type "A" screw
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Installation plate
Ø70mm
Left rear piping
Right rear piping
C
D
B
A
Ø70mm
Ø70mm
Left rear piping
Right rear piping
C
E
A
B
D
Installation plate
Installation plate
A
B
C
D
SJ
90
20
80
20
SL, SK
45
40
80
20
SQ
75
12
80
12
SR
0
40
20
40
ST
105
0
210
0
CHASSIS
(Grade)
Distance (mm)
A
B
C
D
E
SM
180
115
-
115
50
SN
180
115
195
115
-
CHASSIS
(Grade)
Distance (mm)
-22-
2. Flaring Work and Connection of Piping
1) Flaring work
Main cause for refrigerant leakage is due to defect in
the flaring work. Carry out correct flaring work using the
following procedure.
1. Cut the pipes and the cable.
• Use the piping kit accessory or pipes purchased locally.
• Measure the distance between the indoor and the 
outdoor unit.
• Cut the pipes a little longer than the measured 
distance.
• Cut the cable 1.5m longer than the pipe length.
2. Burr removal
• Completely remove all burrs from the cut cross sec-
tion of pipe/tube.
• Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid drop-
ping burrs into the tubing.
3. Putting nut on
• Remove flare nuts attached to indoor and outdoor
unit, then put them on pipe/tube having completed
burr removal.
(not possible to put them on after flaring work)
4. Flaring work
• Firmly hold copper pipe in a die in the dimension
shown in the table above.
• Carry out flaring work using flaring tool as shown
below.
5. Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Copper
pipe
90
°
Slanted   Uneven  Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
mm
inch
mm
Ø6.35
1/4
0~0.5
Ø9.52
3/8
0~0.5
Ø12.7
1/2
0~0.5
Ø15.88
5/8
0~1.0
Ø19.05
3/4
1.0~1.3
Outside diameter
-23-
2) Connection of piping Indoor
• Preparing the indoor unit's piping and drain hose for
installation through the wall.
• Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
• Replace the plastic tubing holder in the original posi-
tion.
1. Route the indoor tubing and the drain hose in the
direction of rear right.
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy 
connection later.
3. Tape the tubing, drain hose, and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
NOTE: If the drain hose is routed inside the room, 
insulate the hose with an insulation material* so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
4. Indoor unit installation
• Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the instal-
lation plate.) Ensure that the hooks are properly seat-
ed on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
4. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
• Align the center of the pipes and sufficiently tighten
the flare nut by hand.
For right rear piping
CAUTION
When install, make sure
that the remaining parts
must be removed clearly
so as not to damage the
piping and drain hose,
especially power cord
and connecting cable.
Tubing holder
Connecting 
cable
Loop
Gas side
piping
Liquid side
piping
Drain hose
Drain hose
Connecting
cable
Indoor unit tubing
Flare nut
Pipes
Drain hose
Page of 127