DOWNLOAD LG LS-M3061HL Service Manual ↓ Size: 5.42 MB | Pages: 81 in PDF or view online for FREE

Model
LS-M3061HL
Pages
81
Size
5.42 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-m3061hl.zip
Date

LG LS-M3061HL Service Manual ▷ View online

- 33 -
1) Checking the drainage
1. Remove the right side panel.
2. Remove the lower panel by the arrow.
3. Remove the left side panel.
(Remove the two screws.)
4. To check the drainage.
Pour a glass of water on the drain pan.
Ensure the water flows through the drain hose of
the indoor unit without any leakage and goes out
the drain exit.
5. Drain piping
The drain hose should point downward for easy
drain flow.
Do not make drain piping.
Right side panel
Downward slope
Do not raise
Accumulated
drain water
Tip of drain hose 
dipped in water
Air
Waving
Water
leakage
Water
leakage
Ditch
Less than 
50mm gap
Water
leakage
Lower panel
Left side panel
- 34 -
2) Form the piping
1. Form the piping by wrapping the connecting por-
tion of the indoor unit with insulation material and
secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose,
the end of the drain outlet should be routed above
the ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below
the indoor unit perform the following.
Tape the piping, drain hose and connecting cable
from down to up.
Secure the tapped piping along the exterior wall
using saddle or equivalent.
3. In cases where the Outdoor unit is installed above
the Indoor unit perform the following.
Tape the piping and connecting cable from down
to up.
Secure the taped piping along the exterior wall.
Form a trap to prevent water entering the room.
Fix the piping onto the wall by saddle or equiva-
lent.
;;
;;
Taping
Drain
hose
Pipings
Connecting
cable
Trap is required to prevent water
from entering into electrical parts.
Seal small openings
around pipings with a
gum type sealer.
Trap is required to prevent water from entering 
into electrical parts.
Seal a small opening
around the pipings
with gum type sealer.
Drain hose
Taping
Pipings
Connecting
cable
Power supply
cord
;;
;;
Seal a small opening 
around the pipings 
with gum type sealer.
Trap
Trap
Seal a small opening 
around the pipings 
with gum type sealer.
Trap
Trap
30K, 32K
36K, 38K
30K, 32K
36K, 38K
- 35 -
4. AIR PURGING 
1) Air purging
Air and moisture remaining in the refrigerant system
have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and
block capillary tubing.
Water may lead to corrosion of parts in the refrig-
eration system.
Therefore, the indoor unit and tubing between the
indoor and outdoor unit must be leak tested and
evacuated to remove any noncondensables and
moisture from the system.
2) Air purging with vacuum pump
1. Preparation
Check that each tube(both liquid and gas side
tubes) between the indoor and outdoor units have
been properly connected and all wiring for the test
run has been completed. Remove the service
valve caps from both the gas and the liquid side
on the outdoor unit. Note that both the liquid and
the gas side service valves on the outdoor unit
are kept closed at this stage.
2. Leak test
Connect the manifold valve(with pressure gauges)
and dry nitrogen gas cylinder to this service port
with charge hoses.
Pressurize the system to no more than 150 P.S.I.G.
with dry nitrogen gas and close the cylinder valve
when the gauge reading reached 150 P.S.I.G.
Next, test for leaks with liquid soap.
Do a leak test of all joints of the tubing(both indoor
and outdoor) and both gas and liquid side service
valves. 
Bubbles indicate a leak. Be sure to wipe off the
soap with a clean cloth.
After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder.
When the system pressure is reduced to normal,
disconnect the hose from the cylinder.
Be sure to use a manifold valve for air purging. If it is not
available, use a stop valve for this purpose. The "Hi"
knob of the manifold valve must always be kept close.
CAUTION
To avoid nitrogen entering the refrigerant system in a
liquid state, the top of the cylinder must be higher than
its bottom when you pressurize the system. Usually,
the cylinder is used in a vertical standing position.
CAUTION
Lo
Hi
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
Pressure 
gauge
30K, 32K
36K, 38K
- 36 -
3. Evacuation
Connect the charge hose end described in the 
preceding steps to the vacuum pump to evacuate
the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with tubing
length and capacity of the pump. The following
table shows the time required for evacuation.
When the desired vacuum is reached, close the
"Lo" knob of the manifold valve and stop the 
vacuum pump.
4. Finishing the job
With a service valve wrench, turn the valve stem
of liquid side valve counter-clockwise to fully
open the valve.
Turn the valve stem of gas side valve
counter-clockwise to fully open the valve.
Loosen the charge hose connected to the gas
side service port slightly to release the pressure,
then remove the hose.
Replace the flare nut and its bonnet on the gas
side service port and fasten the flare nut securely
with an adjustable wrench. This process is very
important to prevent leakage from the system.
Replace the valve caps at both gas and liquid
side service valves and fasten them tight.
This completes air purging with a vacuum pump. 
The air conditioner is now ready to test run.
(1) Remove the caps from the gas side and liquid side valves.
(2) Remove the service-port cap from the gas side valve.
(3) To open the gas side valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec, and
close it.
(4) Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a
soft brush to check for leakage of the connecting points of
the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
3-way valve
(Open)
3-way valve
(Close)
Required time for evacuation 
when 30 gal/h vacuum pump is used
10 min. or more
15 min. or more
If tubing length is less
than 10m (33 ft).
If tubing length is longer
than 10m (33 ft).
Indoor unit
Outdoor unit
Lo
Hi
Manifold valve
Vacuum pump
Pressure 
gauge
Open
Close
Indoor unit
Outdoor unit
30K, 32K
36K, 38K
Page of 81
Display

Click on the first or last page to see other LS-M3061HL service manuals if exist.