6. Pipe length and the elevation
• Capicity is based on standard length and maximum allowance length is the basis of reliability.
• Oil trap should be installed per 5~7 meters.
• Numerical value in "(    )" is for Rotary Comp. model.
CAUTION
In case more than 5m
Max. Piping
Length
(m)
Capacity
(Btu/h)
7~12K
15
7
5
20
Max. 
Elevation 
(m)
Standard
Length(m)
Additional Refrig-
erant
(g/m)
-36-
7. Test running
Discharge air
Bolt
Tubing
connection
Battery Cover
Settlement of Outdoor Unit
• Anchor the outdoor unit with a bolt and nut
(ø10cm) tightly and horizontally on a concrete or
rigid mount.
• When installing on the wall, roof or rooftop, anchor
the mounting base securely with a nail or wire
assuming the influence of wind and earthquake.
• In the case when the vibration of the unit is con-
veyed to the house, settle the unit with an anti-
vibration rubber.
2) Evaluation of the performance
1. Measure the temperature of the intake and dis-
charge air.
2. Ensure the difference between the intake tem-
perature and the discharge one is more than 8
°C(Cooling) or reversely (Heating).
1) Connection of power supply
1. Connect the power supply cord to the inde-
pendent power supply.
• Circuitbreaker is required.
2. Prepare the remote controller.
• Insert two batteries provided.
Remove the battery cover from the remote con-
troller.
• Slide the cover according to the arrow direction.
Insert two batteries.
(Two "R03" or "AAA" dry-cell batteries or equiv-
alent.)
• Be sure that the (+) and (-) directions are cor-
rect.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
3. Operate the unit for fifteen minuites or more.
-22-
5-7mm
Indoor
Outdoor
WALL
Right rear piping
Installation plate
Marking-off line
Thread
Weight
Type "A" screw
Left rear piping
ø70mm
ø70mm
80mm
50mm
40mm
40mm
ø70mm
ø70mm
80mm
50mm
40mm
40mm
2) Indoor Unit Installation
The mounting wall should be strong and solid enough
to protect it from the vibration.
1.Mount the installation plate on the wall with four
Type "A" screws.
(if mounting the unit on the concrete wall, consider
using anchor bolts.)
• Always mount the Installation plate horizontally by
aligning the marking-off line by means of the
thread and a level.
2. Drill the piping hole with 70mm dia. holecore
drill.
• Line according to the arrows marked on lower the
left and the right side of the Installation Plate.
The meeting point of the extended line is the cen-
ter of the hole.
• Drill the Piping hole at either the right or the left
and the hole should be slightly slanted to the out-
door side.
The lower left and right side of Installation
Plate
-23-
2. Piping and Drainage of Indoor Unit
1) Preparation of Piping
1. Cut the pipes and the cable.
• Use the accessory piping kit or the pipes pur-
chased locally.
• Measure the distance between the indoor and the
outdoor unit.
• Cut the pipes a little longer than measured dis-
tance.
• Cut the cable 1.5m longer than the length of the
pipe.
2. Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end toward down to avoid the metal
powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leak-
age.
3. Flaring the pipes.
• Insert the flare nuts, mounted on the connection
ports of both indoor and outdoor unit, onto the
copper pipes. (When the flare nuts are removed
from the indoor unit.) Some gas may leak, as
some gas is charged to prevent the inside of the
pipe from rusting.
• Fit the copper pipe end into the Bar of flare tool
about 0~1.0mm higher. (See illustration)
• Flare the pipe ends.
4. Tape the flaring portion to protect it from the
dust or damages.
90
Slanted Rough
Pipe cutter
Pipe
Reamer
Point down
"A"
Bar
Bar
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Copper pipe
Inclined
Cracked
Uneven
thickness
Surface
damaged
= Improper flaring =
When properly flared, the internal surface of the flare will
evenly shine and be of even thickness.
After the flare part comes into contact with the connec-
tors, carefully check the flare finish.
"A"; ø15.88 mm (5/8") 
→0~
1.0 mm
ø12.7 mm (1/2") 
→ 0~
0.5 mm
ø9.52 mm (3/8") 
→ 0~
0.5 mm
ø6.35 mm (1/4") 
→ 0~
0.5 mm
Page of 127