11. Auto restarting operation
• When the power is restarted after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• The slide switch on the indoor unit of the appliance should be on the AUTO RESTART position in order that
the Auto restarting operation is available.
• Operation mode that is kept on the memory
— State of operation ON/OFF
— Operation mode/setting temp./selected airflow speed
— Sleep timer mode/remaining time of sleep timer
• If no input by the remote control or no switching of the slide 
switch within 7 hours after the appliance operates by the 
Auto restarting operation, the appliance is forced to stop 
at the moment of 7-hr elapse.
12. Forced operation
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• The operation condition is set according to the outdoor temp. and intake air temperature as follows.
-22-
Outdoor temp.
over 24°C
21~24°C
18~21°C
below 18°C
Setting temp.
22°C
23°C
23°C
24°C
24°C
Setting speed of
indoor fan
High speed
Operating Mode
Cooling
Healthy Dehumidification
Intake air temp. 
25°C 
Dehumidification
Intake air temp. < 25°C 
Heating
Heating
FORCED
OPERATION
AUTO
RESTART
REMOTE
CONTROL
Slide Switch of indoor unit
13. Power relay control
• Power relay turns on 1 second later after the power is input to the outdoor unit.
• Control sequence : power on 
PTC operating 
➔ 
power relay on 
14. Protection from total current control
CT1 control
• If the operating current reaches I1, the operating frequency of the compressor decrease.
• After decreasing the operating frequency by 1step, if operating current is below I1 for 24 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs twice within 1hour, the appliance turn off and display ERROR CODE 7.
-23-
Model
LS-J0760NL
LS-J0961NL/NT
LS-J0820NL
Cooling
Heating
7.5A
8.0A
11.5A
7.5A
8.0A
11.5A
Cooling
Heating
8.5A
10A
13.5A
8.5A
10A
13.5A
Cooling
Heating
10.5A
12A
13.5A
10A
11.5A
13.5A
Operating mode
below 38°C
(outdoor temp.)
I1
I2
I1
I2
over 38°C
(outdoor temp.)
LS-L1260NL/NT
LS-L1220NL
Condition
I1:Current of operating frequency down
I2: Current of compressor cut off
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Control table
15. Protection from DC Peak Current
DC Peak Current Error by a fault signal of IPM
• If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
• If DC PEAK occurs 3 times within 1 hour, the appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the compressor lock
• If the DC LINK voltage below DC 350V occurs 5 times within 1 hour while the compressor is operating, the
appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the Outdoor Fan Lock
• If it’s 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is
operating, the appliance turns off and display ERROR CODE 6.
16. Portection from overheating of power module
• If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
• It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
• It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
17. Portection from overheating of compressor
• If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
• It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
-24-
Comp. off
Comp. free
Fc-1
Target
frequency
Toff (84˚C)
Ts (79˚C) = Ton + 5˚C
Ton (74˚C)
130˚C
113˚C
105˚C
98˚C
-13˚C
-30˚C
101˚C
93˚C
Fhmin
OFF
OFF
0Hz
Fc-2
Fc-1
Setting frequency
[The control graph from heat–sink TH]
18 . Defrosting control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing,
reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• Defrosting control is available 45 minutes later since heating cycle started and the pipe temperature of out-
door unit reaches below -6°C.
-25-
45 min
Setting frequency
Setting speed
Setting
speed
OFF
OFF
ON
OFF
OFF(Cooling cycle)
Setting
frequency
30 sec
Fc-1 step
Operating
frequency
of compressor
4 Way valve
Outdoor fan
Indoor fan
Defrost LED
Fc-1
Fh+1
OFF
ON
ON(Heating cycle)
ON
ON
Low
(FhMAX-2 or
FhMAX-3)
30 sec
30 sec
8 min or
over 25˚C(120sec)
30 sec
1 min
Page of 74