Service Manual  49
Troubleshooting Guide 
Required tools :  hexagonal wrench, adjustable wrench,
torque wrenches, wrench to hold the
joints, and gas leak detector. 
The additional gas for air purging has been charged
in the outdoor unit.
However, if the flare connections have not be done
correctly and there gas leaks, a gas cylinder and the
charge set will be needed. 
The air in the indoor unit and in the piping must be
purged. If air remains in the refrigeration pipes, it will
affect the compressor, reduce to cooling capacity,
and could lead to a malfunction. 
• Procedure 
(1) Recheck the piping connections.
(2) Open the valve stem of the 2-way valve coun-
terclockwise approximately 90°, wait 10 sec-
onds, and then set it to closed position. 
–  Be sure to use a hexagonal wrench to operate
the valve stem. 
(3) Check for gas leakage.
–  Check the flare connections for gas leakage. 
(4) Purge the air from the system. 
–  Set the 2-way valve to the open position and
remove the cap from the 3-way valve’s service
port.
–  Using the hexagonal wrench to press the valve
core pin, discharge for three seconds and then
wait for one minute. Repeat this three times. 
(5) Use torque wrench to tighten the service port
nut to a torque of 1.8kg.cm. 
(6) Set the 3-way valve to the back seat. 
(7) Mount the valve stem nuts to the 2-way and 3-
way valves. 
(8) Check for gas leakage. 
–  At this time, especially check for gas leakage
from the 2-way and 3-way valve’s stem nuts,
and from the service port nut. 
Service port nut:
Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the
gas leakage from the refrigeration cycle.
CAUTION: Do not leak the gas in the air during Air purging. 
CAUTION: If gas leakage are discovered
in step (3) above, take the following
mesures : 
If the gas leaks stop when the piping connections
are tightened further, continue working from step (4). 
If the gas leaks do not stop when the connections
are retightened, repair the location of the leak, dis-
charge all of the gas through the service port, and
then recharge with the specified amount of gas from
a gas cylinder. 
Liquid side
Outdoor unit
3-way
valve
Gas side
Indoor unit
2-way
valve
Open
Clsed
Air purging
50 Room Air Conditioner
Troubleshooting Guide 
• Procedure 
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.  
–  Remove the valve stem caps and confirm that
the valve stems are in the raised position. 
– Be sure to use a hexagonal wrench to operate
the valve stems. 
(2) Operate the unit for 10 to 15 minutes. 
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of
the 3-way valve.
–  Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
–  Open the low-pressure valve on the charge set
slightly to air purge from the charge hose. 
(5) Set the 2-way valve to the closed position. 
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates
1kg/cm
2
g.
(7) Immediately set the 3-way valve to the closed
position.
–  Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm
2
g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valve’s stem nuts and the ser-
vice port nut. 
–  Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m. 
–  Be sure to check for gas leakage. 
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way
valve
3-Way
valve
CLOSE
Pumping Down 
Service Manual  51
Troubleshooting Guide 
Re-air Purging 
(Re-installation)
• Procedure 
(1) Confirm that both the liquid side valve and the
gas side valve are set to the closed position. 
(2) Connect the charge set and a gas cylinder to
the service port of the Gas side valve. 
–  Leave the valve on the gas cylinder closed. 
(3) Air purging. 
–  Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare
nut on the liquid side valve approximately 45°
for 3 seconds then closing it for 1 minute;
repeat 3 times. 
– After purging the air, use a torque wrench to
tighten the flare nut on liquid side valve.
(4) Check for gas leakage.
–  Check the flare connections for gas leakage.  
(5) Discharge the refrigerant. 
–  Close the valve on the gas cylinder and dis-
charge the refrigerant until the gauge indicates
3 to 5 kg/cm
2
g. 
(6) Disconnect the charge set and the gas cylin-
der, and set the Liquid side and Gas side
valves to the open position.
–  Be sure to use a hexagonal wrench to operate
the valve stems. 
(7) Mount the valve stem nuts and the service
port nut.
–  Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.  
CAUTION: Do not leak the gas in the air
during Air Purging.
Lo
Closed
OPEN
Closed
Gas cylinder
R22
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
3-Way
valve
3-Way
valve
52 Room Air Conditioner
Troubleshooting Guide 
Balance Refrigerant of the 3-way Valve  
(Gas leakage)
• Procedure 
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat. 
(2) Connect the charge set to the 3-way valve’s
port.  
–  Leave the valve on the charge set closed. 
– Connect the charge hose to the service port.  
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi-
cates 0 kg/cm
2
G.
–  If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running
is higher than 1 kg/cm
2
G), discharge the refrig-
erant until the gauge indicates 0.5 to 1
kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin. 
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged. 
Lo
Open
Open
3-Way
valve
3-Way
valve
Gas side
CLOSE
OPEN
Outdoor unit
Liquid side
Indoor unit