20 Room Air Conditioner
Installation
3. Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connec-
tion later.
4. Tape the drain hose and the connecting cable.
• Connecting cable
5. Indoor unit installation
• Hang the indoor unit from the hooks at the top of
the installation plate.
• Insert the spacer etc. between the indoor unit and
the installation plate and separate the bottom of
the indoor unit from the wall.
6. Connecting the pipings to the indoor unit and
the drain hose to drain pipe.
• Align the center of the pipes and sufficiently tight-
en the flare nut by hand.
• Tighten the flare nut with a wrench.
• When extending the drain hose at the indoor unit,
install the drain pipe.
7. Wrap the insulation material around the con-
necting portion.
• Overlap the connection pipe heat insulation and
the indoor unit pipe heat insulation material. Bind
them together with vinyl tape so that there is no
gap.
• Wrap the area which accommodates the rear pip-
ing housing section with vinyl tape.
mm
inch
kg.m
Ø6.35
1/4
1.8
Ø9.52
3.8
4.2
Ø12.7
1/2
5.5
Ø15.88
5/8
6.6
Ø19.05
3/4
6.6
Outside diameter
Torque
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection
pipe
Connecting cable
Indoor 
unit piping
Pipe
Vinyl tape
(wide)
Wrap with vinyl tape
Installation plate
Spacer
Indoor unit
8cm
Indoor unit tubing
Flare nut
Pipes
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
Service Manual 21
Installation
• Bundle the piping and drain hose together by
wrapping them with cloth tape over the range with-
in which they fit into the rear piping housing sec-
tion.
8. Reroute the pipings and the drain hose across
the back of the chassis.
9. Set the pipings and the drain hose to the back of
the chassis with the tubing holder.
• Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be
engaged at the bottom of chassis.
10. Indoor unit installation
• Remove the spacer.
• Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
slots(clicking sound).
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the
arrow on the wrench.
mm
inch
kg.m
Ø6.35
1/4
1.8
Ø9.52
3/8
4.2
Ø12.7
1/2
5.5
Ø15.88
5/8
6.6
Ø19.05
3/4
6.6
Outside diameter
Torque
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with 
vinyl tape(wide)
Piping for
passage through
piping hole
Outdoor unit 
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
Tubing holder
Drain hose
Connecting
cable
Connection of the Pipes-Outdoor
22 Room Air Conditioner
Installation
• Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in
dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
Air 
Conditioner
Main power source
Circuit Breaker
Use a circuit
breaker or time
delay fuse.
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
 
CAUTION
The power connecting cable connected to 
the indoor and outdoor unit should be 
complied with the following specifications
(Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit 
should be complied with the following 
specifications(Type "B" approved by HAR or 
SAA).
7k~14k
18k
24k~28k
30k, 32k
36k, 38k
1.0
1.5
2.5
2.5
5.5
Unit(A)
Indoor
Indoor
Indoor
Outdoor
Outdoor
Cable Type(B) H05VV-F H05VV-F H05VV-F H05RN-F H05RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
7k~14k
18k
24k~28k
1.0
1.5
2.5
Cable Type(B) H07RN-F H07RN-F H07RN-F
NORMAL
CROSS
-SECTIONAL
AREA
Grade
30k, 32k
36k, 38k
0.75
0.75
Cable Type(B) H07RN-F H07RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm
2
)
(mm
2
)
(mm
2
)
CAUTION:
• The above circuit diagram is subject to change
without notice.
• Be sure to connect wires according to the wiring
diagram.
• Connect the wires firmly, so that not to be pulled
out easily.
• Connect the wires according to color codes by
referring the wiring diagram.
• When installing, refer to the circuit diagram on the
Control Box of Indoor Unit.
• When installing, refer to the wiring diagram on the
Control Cover Inside Outdoor Unit.
Connect the Cable to the Indoor Unit.
CAUTION:
If a power plug is not to be used, provide a circuit
breaker between power source and the unit as shown
below.
Service Manual 23
Installation
1. Remove the control cover from the unit by loos-
ening the screw.
Connect the wires to the terminals on the control
board individually.
2. Secure the cable onto the control board with the
cord clamp.
3. Refix the control cover to the original position
with the screw.
4. Use a recognized circuit breaker "A"
between the power source and the unit.
A disconnecting device to adequately disconnect
all supply lines must be fitted.
Terminal block
Over 5mm
Cover control
Connecting cable
Connecting cable
CAUTION: After the confirmation of the above conditions, prepare the wiring as
follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring,
be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations
to which the unit is subjected during the course of transportation. Check them and make sure that they are
all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 22))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air
gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor Unit
7k~14k
18k
24k~28k 30k, 32k 36k, 38k
15
20
30
30
40
Circuit
Breaker
(A)
Grade
Connect the Cable to the Outdoor Unit
Page of 119