LG LS-D2461HL Service Manual ▷ View online

4. Gas Charging 
(After Evacuation)
• Procedure 
(1) Connect the charge hose to the charging
cylinder. 
–  Connect the charge hose which you dis-
connected from the vacuum pump to the valve
at the bottom of the cylinder. 
– If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid. 
(2) Purge the air from the charge hose.   
–  Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid
refrigerant).  The procedure is the same if
using a gas cylinder. 
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
–  If the system can not be charged with the
specified amount of refrigerant, it can be
charged with a little at a time (approximately
150g each time) while operating the air
conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1
minute and then repeat the procedure
(pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port. 
–  Stopping partway will allow the gas to be
discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose. 
(5) Mount the valve stem nuts and the service
port nut. 
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage. 
\
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner. 
Lo
Charging
cylinder 
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way
valve
3-Way
valve
OPEN
Open
Check valve
(1)
ƒ¡
54
ƒ¡
Cycle Trouble Shooting Guide 
Trouble analysis 
1. Check temperature difference between intake and discharge air and operating current. 
Temp. Difference 
Temp. difference   :   approx. 0°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   approx. 8°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   less than 8°C
Current                  :   over the rated
current 
Temp. difference   :   over 8°C 
Operating Current 
All amount of refrigerant leaked out
Check refrigeration cycle
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor 
Excessive amount of refrigerant
Normal 
Notice : 
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger. 
2. Check temperature and pressure of refrigeration cycle. 
Notice : 
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition. 
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty. 
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
Defective compressor
Current is low
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of 
operation
Insufficient amount of 
Current is low
Lower 
Higher
refrigerant (Leakage)
Clogging
Current is low 
High 
Higher  
ƒ¡
55
ƒ¡
Electronic Parts Trouble Shooting Guide
: The unit does not operate
1) Check Outdoor Unit 
Possible Trouble 1
ƒ¡
56
ƒ¡
YES
YES
YES
NO
YES
Is the trans input power
AC220-240V?
Is the trans 
output (red part) about 
AC38V?
Is the trans output
(blue part) about AC13V?
Check the fuse, check
wiring connection.
Is input voltage of
IC2 DC15V?
Is output voltage of
IC3 DC5V?
Exchange IC1
YES
NO
Check the main P.C.B
pattern.
NO
NO
Exchange BD1
NO
YES
Exchange the trans.
Is shorted the
trans output?
NO
YES
Is output voltage of
IC2 DC12V?
NO
Is the voltage of pin NO64
of IC1 DC5V?
YES
Exchange IC2
Exchange IC3
NO
Check P.C.B pattern
Is the trans 
output (red part) about 
AC25V?
18K
24K,26K,28K,30K
WARNING :
1. When servicing the unit, remove the power cord of outdoor unit.
2. The FAN MOTOR of outdoor unit operates intermittently for the reliability of the unit during operation.
2) Check Indoor Unit 
ƒ¡
57
ƒ¡
YES
YES
YES
Is the voltage between
NO.4 and NO.2 pin of CN-DC/DC
DC40V?
Is the input voltage
of IC2 about DC22V?
Is the output of IC2 DC12V?
Check the voltage of the
counter part of the outdoor
main P.C.B assembly.
Is the output of IC3 DC5V?
Is the connection
between main P.C.B and CN-Display 
P.C.B correct?
Exchange IC1
YES
Exchange TR01 and ZD01
NO
Exchange IC3
NO
Exchange IC2
YES
Is the output of NO.43 pin 
of IC1 DC5V?
NO
Is the voltage of NO.64 pin
of IC1 DC5V?
YES
Exchange IC4
Connect correctly
NO
Check P.C.B pattern
NO
NO
Is the voltage between
NO.4 and NO.2 pin of CN-DC/DC
DC28V?
24K, 26K, 28K, 30K
18K
Is the input voltage
of IC2 about DC18V?
NO
YES
Page of 75