Installation
1. First, Check the side cover assembly
exactly, and fix the power cord in the
bottom groove of cover side left.
2. Assemble connecting lead wire with
controller, fix the upper part of panel
front, and match the lower part of panel
front.
3. Screw up panel front, and suspend the
hook of panel front in the groove.
Panel Front
Connector
Panel Front Assembly
26 Room Air Conditioner
Installation
1. Check that all tubing and wiring are properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote controller
1. Remove the battery cover by pulling it according to
the arrow direction.
2. Insert new batteries making sure that the (+) and (–)
of battery are installed correctly.
3. Reattach the cover by pushing it back into position.
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
• Remove the batteries from the remote controller if the
system is not used for a long time.
Settlement of outdoor unit
1. Anchor the outdoor unit with a bolt and nut(ø10mm)
tightly and horizontally on a concrete or rigid mount.
2. When installing on the wall, roof or rooftop, anchor
the mounting base securely with a nail or wire
assuming the influence of wind and earthquake.
3. If the vibration of the unit is transmitted to the hose,
secure the unit with an anti-vibration rubber.
Evaluation of the performance
Operate the unit for 15~20 minutes, then check the sys-
tem refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge
of air.
3. Ensure the difference between the intake tempera-
ture and the discharge is more than 8°C 
4. For reference; the gas side pressure of optimum con-
dition is as below.(Cooling)
The air conditioner is now ready for use.
NOTICE
Bolt
Tubing connection
Discharge air
Discharge 
temperature
Intake temperature
R-22
35°C (95°F)
4~5kg/cm
2
G(56.8~71.0 P.S.I.G.)
R-410A
35°C (95°F)
8.5~9.5kg/cm
2
G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side 
service valve.
Test Running
Service Manual  27
Installation
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be
removed. If the actual pressure are lower than shown, the system is most likely undercharged, and
charge should be added.
NOTICE
PUMP DOWN
This is performed when the unit is relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant.
CAUTION: Be sure to perform Pump Down procedure in the cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant.
3. Close the liquid side service valve(all the way).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm
2
G(14.2 to 7.1 P.S.I.G.), fully close the gas side
valve and then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected
into the outdoor unit.
28 Room Air Conditioner
Operation 
DISPLAY
1) C/O Model (high quality LCD remote controller supplied)
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled.
Comp. Running Indicator
• While in appliance operation, on while in outdoor unit compressor running, off while in compressor off
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
2) H/P Model (high quality LCD remote controller supplied)
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.  
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
Compressor OFF Temp => Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote controller. While in compressor
not running, operating with the low airflow speed regardless of the setting.