Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference
: approx. 0°C
Current
: less than 80% of
rated current
Temp. difference
: approx. 8°C
Current
: less than 80% of
rated current
Temp. difference
: less than 8°C
Current
: over the rated
current
Temp. difference
: over 8°C
Operating Current
All amount of refrigerant leaked out
Check refrigeration cycle
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
Excessive amount of refrigerant
Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice :
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
Defective compressor
Current is low
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of
operation
Insufficient amount of
Current is low
Lower
Higher
refrigerant (Leakage)
Clogging
Current is low
High
Higher
–38–
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference
: approx. 0°C
Current
: less than 80% of
rated current
Temp. difference
: approx. 8°C
Current
: less than 80% of
rated current
Temp. difference
: less than 8°C
Current
: over the rated
current
Temp. difference
: over 8°C
Operating Current
All amount of refrigerant leaked out
Check refrigeration cycle
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
Excessive amount of refrigerant
Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice :
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
Defective compressor
Current is low
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of
operation
Insufficient amount of
Current is low
Lower
Higher
refrigerant (Leakage)
Clogging
Current is low
High
Higher
–38–
Electronic Parts Troubleshooting Guide
1) No Cooling operation performed
: The unit does not operate.
Possible Trouble 1
–39–
YES
YES
YES
NO
YES
Is the input voltage
of transformer AC220V?
Is the input voltage
of IC01D DC14V?
Check the FUSE
and the wiring diagram.
Is the output voltage 
of IC01D DC12V?
Is the PIN 55,64 of
MICOM. DC5V?
Exchange MICOM
YES
NO
Check the main P.C.B
pattern
NO
NO
Check the D02D~D05D
NO
YES
Exchange 
the transformer
Is shorted the
transformer output?
NO
YES
Is the output voltage 
of IC03D DC5V?
NO
Exchange IC01D
Exchange IC03D
Is the output voltage
of transformer about AC14V?
Check the 
5V P.C.B pattern.
Possible Trouble 2
: The indoor fan does not operate.
NO
Is IC03M operated
normally?
Check the fan motor
and connector.
(CN-MOTOR)
YES
Is the each Relay
any problem?
NO
YES
Exchange IC03M
Exchange Relay
–40–
2) No heating operation works
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
Reset the power
ON/OFF S/W ON
Is the AC220V
(AC 240 V) between connector
(CN-outunit)
and
of Main
P.C.B
Is the input power AC220V
(AC240V) at COMP magnetic coil
contactor?
Is it heating mode?
Room temp <Set temp?
Is the DC5V
at 14 pin of terminal MICOM
Is the DC5V
at 18 pin of terminal MICOM
Is the DC12V
at each terminal?
(RY-4WAY COIL)
Is the
AC220V (AC 240 V) between
connector(4WAY) and CN-outunit of
Main
P.C.B
Is the DC12V at
each terminal? (RY-COMP
COIL)
Replacement RY-4WAY
Replacement IC02M
Replacement RY-COMP
Is the AC220V
(AC 240 V) between connector(CN-outunit)
and of Main
P.C.B
Check the wiring diagram.
Replacement MICOM
Replacement IC02M
Room temp. < Set temp. Setting
Replacement MICOM
Select the heating operation mode.
Check the COMP magnetic
contactor of outdoor unit.
Check the wiring
connection
Is the unit operating?
Page of 52