DOWNLOAD LG LP-E5082HA_HL Service Manual ↓ Size: 3.96 MB | Pages: 127 in PDF or view online for FREE

Model
LP-E5082HA_HL
Pages
127
Size
3.96 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lp-e5082ha-hl.zip
Date

LG LP-E5082HA_HL Service Manual ▷ View online

6.6 Power Supply and Wiring
The unit is completely wired internally at the factory
according to general rule of electrical technology, but
local rules, if they are required, should be complied
with.
1) Power supply
Power source must fulfill the following conditions:
¤
The working voltage should be higher than 90%
and lower than 110% of the rated voltage marked
on the name plate.
¤Ł
The working voltage among the three phases
should be balanced with in a 3% deviation from
each phase voltage.
¤Ø
The starting voltage should be higher than 85% of
the rated voltage marked on the name plate.
2) Wiring
After the confirmation of the above conditions, 
prepare the wiring as follows:
¤
Never fail to have an individual power specialized
for the air conditioner. As for the method of wiring,
be guided by the circuit diagram pasted on the
inside of control box cover.
¤Ł
Provide a circuit brake switch between power
source and the unit.
¤Ø
The screws which fasten the wiring in the casing of
electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the
course of transportation. Check them and make
sure that they are all tightly fastened.
(If they are loose, it could give rise to burn-out of
the wires.)
¤Œ
Specification of power source.
¤º
Confirm that electrical capacity is sufficient.
¤
See to that the starting voltaged is maintained at
more than 90 percent of the rated voltage marked
on the name plate.
¤
Confirm that the cable thickness is as specified in
the power sources specification.
(Particularly note the relation between cable length
and thickness.)
¤
Never fail to equip a leakage brake where it is wet
or moist.
¤
The following troubles would be caused by voltage
drop-down.
• Vibration of a magnetic switch, damage on the 
contact point there of, fuse breaking, disturbance to
the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
3) Earthing work
Connect the cable of diameter 1.6mm or more to the
earthing terminal provided in the control box and do
earthing. In case of equipping the electrical
resistance will be reduced to 500
. But in case that
no earthing is required in particular, the electrical
resistance between the med is below 100
.
Also, the unit can be earthed to the water service
pipe buried under the ground where electrical
resistance of 3
or less is retained. Of course, the
earthing to pipes must be approved by the authority
of water supply.
– 43 –
Voltage
Time
Starting point
Power soure voltage
working voltage
Starting voltage
Earthing
Earthing
Indoor
Outdoor
Knife Switch
Main cables
Leakage
brake
7.1 Display 
1) 3HP
– 51 –
7. OPERATING
Start/Stop Button
Operation starts when this button is pressed
and stops when the button is pressed again.
Operation Mode Selection Button
Used to select the operation Mode.
Room Temperature Setting Buttons
Used to select the room temperature.
Indoor Fan Speed Selection
Used to select fan speed in three steps-low,
med, high.
Air Cleaner Operation Button(Option)
Used to purify the room air.
Cooling Operation Lamp
Soft Dry Operation Lamp
Fan Operation Lamp
Heating Operation Lamp
E/Heater Operation Lamp
(Option)
Auto Operation Lamp
Defrost Operation Lamp
Off Timer Operation Lamp
Auto Air Flow Operation Lamp
Air Cleaner Operation Lamp
(Option)
Outdoor Unit Operation Lamp
1
2
3
4
5
6
7
9
10
11
12
13
14
15
16
8
L
M
H
MOD
E
A/CL
A/CL
OUT
DOOR
ROOM TEMP SET TEMP
6
2
3
4
1
5
9
7
10 12 13 14
16
15
MOD
E
A/CL
A/CL
OUT
DOOR
ROOM TEMP SET TEMP
L
M
H
6
2
3
4
1
5
7
11
8
13
14
16
15
(Cooling & Heating Model)
(Cooling only Model)
– 52 –
2) 5HP, 8HP
L
M
H
MOD
E
POWER 
A/CL
A/CL
OUT DOOR
ROOM TEMP. SET TEMP.
L
M
H
MOD
E
POWER 
A/CL
A/CL
OUT DOOR
ROOM TEMP. SET TEMP.
8
2
3
4
16
1
9
5
17
10
7
6
13 12 14 15
8
2
3
4
16
1
5
11
7
6
13 12 14
Start/Stop Button
Operation starts when this button is pressed and
stops when the button is pressed again.
Operation Mode Selection Button
Used to select the operation Mode.
Room Temperature Setting Buttons
Used to select the room temperature.
Indoor Fan Speed Selection
Used to select fan speed in three steps-low, med,
high.
Air Cleaner Operation Button 
(Option)
(8HP:OFF TIMER Opertion Button,       )
Used to purify the Room air.
Air Circulation Lamp
Cooling Operation Lamp
Soft Dry Operation Lamp
Heating Operation Lamp
Defrost Operation Lamp
Auto Operation Lamp
Off timer Operation Lamp
Auto Air Flow Operation Lamp
Air Cleaner Operation Lamp
(Option)
E/Heater Operation Lamp
Outdoor Unit Operation Lamp
E/Heater Operation Button
(Option)
1
2
3
4
5
6
7
9
10
11
12
13
14
15
16
17
8
(Cooling & Heating Model)
(Cooling only Model)
– 53 –
7.2 Control (3HP, 5HP only)
⁄A
Signal Transmitter
• Transmits the signals to the package air conditioner
⁄B
Operation Display of the Remote Control
⁄C
Indoor Fan Speed Selection Button
• To select the desired fan speed in three steps [Low,
Med, High]
⁄D
Cooling ON Button
⁄E
Temperature Setting Buttons
⁄F
Power ON/OFF Button 
• Operation will start when this button is pressed, and
stops when the button is pressed again.
⁄G
Timer Set Button 
• Each time the button is pressed, the mode is
changed in the following process.
Timer set (1, 2, 3, 4, 5, 6, 7 hours)
If you select “0:00” the off Timer function will be
cancelled.
⁄H
Auto Airflow Direction Control Button
• The vertical louvers swing left and right.
• The horizontal louvers can be adjusted manually.
⁄I
Auto Mode Operation Button (Cooling Model Only)
⁄J
Plasma Air purifying Button (Option)
⁄K
Indoor Fan Operation Button (Cooling Model Only)
⁄L
Heating Button (Heat Pump Model Only)
⁄M
Electric Heater ON/OFF Button (Option)
⁄N
Soft Dry Operation Button
2
14
8
13
3
6
10
7
A/CL
12
9
4
1
11
5
Handling the remote control
• Aim at the signal receptor on the package air conditioner when operating.
• The remote control signal can be received at a distance of up to about 7meters.
• Be sure that there are no obstructions between the remote controller and the signal receptor.
• Do not drop or throw the remote controller.
• Do not place the remote controller in a location exposed to direct sunlight, or next to a heating unit, or
other heat source.
Wireless Remote Control Puts all functions at your fingertips
Page of 127