– 50 –
6.11 Running Test and Maintenance Record
JOB NUMBER:
POWER SUPPLY : Main Power_______ V, ________ Hz
Accessory Attached :
CUSTOMER'S NAME AND ADDRESS :
(PHONE NO.:                 )
INSTALLED BY:
DATE:
START UP BY:
DATE:
❐ 
1. Does the operation switch function properly?
❐ 
2. Is the rotating direction of the evaporator fan correct?
❐ 
3. Is the rotating direction of the condenser fan correct?
❐ 
4. Is the evaporator airflow sufficient?
❐ 
5. Are there any abnormal sounds?
❐ 
6. Has the unit been operated at least twenty (20) minutes?
❐ 
7. Check indoor temperatures :
Inlet : DB __________ °C, WB _______________°C
Outlet : DB __________ °C, WB _______________°C
❐ 
8. Check outdoor temperatures :
Inlet : DB __________ °C
Outlet : DB __________ °C
❐ 
9. Check pressures :
Discharge pressure:________kg/cm
2
Suction pressure: ____kg/cm
2
❐ 
10. Check voltage :
Rated voltage:________ V
Operating voltage:R-S __________ V, S-T _____ V, T-R ______V.
Starting voltage: _____ V (
0.85 x Rated Voltage)
Phase unbalance : 1-V/V mean = ______ (-0.03 
Imbalance 
+0.03)
❐ 
11. Check running current:
packaged air conditioner: ____ A
❐ 
12. Do the control devices function properly?
❐ 
13. Do the protective devices function correctly?
❐ 
14. Is the refrigerant charge adequate?
❐ 
15. Is the drain line draining properly?
❐ 
16. Is the air filter clean?
❐ 
17. Are the evaporator coil and condenser coil clean?
❐ 
18. Are all cabinet panels fixed?
❐ 
19. Are all cabinet panels free from rattles?
Indoor Unit
Outdoor Unit
Model
(            V,            Hz)
(                V,                  Hz)
Production No.
– 36 –
2) Indoor Unit installation
¥L
The mounting floor should be strong and solid
enough to prevent it from vibration.
¥M
Drill the piping hole with 70mm diameter hole-core
drill at either the right or the left of indoor unit. The
hole should be sightly slant to the outdoor side.
¥N
Insert the plastic tube through the hole.
¥O
Cut the extruded outside part of the plastic tube, if
necessary.
3) Outdoor unit Installation
¥L
Install the outdoor unit on the concrete or any solid
base securely and horizontally by securing it with
bolts (Ø12mm) and nuts.
¥M
If there is any vibration transmitted to the building,
mount the rubber underneath the outdoor unit.
4) Refrigerant amount
Before shipment, this air conditioner is filled with the
rated amount of refrigerant including additional
amount required for air-purging, subject to 5m piping
length. (The rated amount of refrigerant is indicated
on the name plate.) But when the piping length
exceeds 5 meters, additional charge is required
according to the following table.
(Unit: g)
Example)  In case of 10m long pipe(one-way), the
amount of refrigerant to be replenished is:
(10 - 5) x 70 = 350g
Wall
Core Drill
Tilt 
Cut if necessary
More than 15mm
Wall
Plastic tube
(Bushing)
INSIDE
OUTSIDE
200mm
70mm
70mm
89mm
REFRIGERANT CHARGE
30 per 1m
40 per 1 m
50 per 1 m
MODEL
3HP
5HP
8HP
– 37 –
6.2 Installation Method
1) Procedure
No.
Installation works
Descriptions
1
Preparation of tools and installation parts
Preparation of installation
2
Flaring the pipes
To insert the flare nuts, mounted on the connection 
parts of both indoor and outdoor unit, onto the 
copper pipes.
3
Pipe bending
To reduce the flow resistance of refrigerant.
4
Connection of installation parts
Connection of long piping
(elbows, socket etc)
5
Tighten the flare nut (outdoor) 
Connecting the pipings of the outdoor unit.
6
Blowing the pipings
To remove dust and scale in working.
7
Tighten the flare nut (indoor)
Connecting the pipings of the indoor unit.
8
Check the gas-leakage of the connecting 
part of the pipings.
9
Air purging of the piping and indoor unit
The air which contains moisture and which
remains in the refrigeration cycle may cause malfunction 
on the compressor
10
Open the 3-way (liquid side) and 
3-way (gas side) valves.
11
Form the pipings
To prevent heat loss and sweat
12
Checking the drainage (indoor unit) 
To ensure if water flows drain hose of indoor unit.
13
Connecting the cable between outdoor and 
Preparation of the operating
indoor unit 
14
Connecting the main cable to outdoor unit
15
Supply the power to the crankcase heater
To prevent the liquid back to the compressor. 
(before the operating the unit)
(Heat pump only)
16
Cooling operation, Heating operation
To confirm the operation of the unit.
(Use the remote controller or display of the indoor unit)
– 38 –
No.
Installation Parts, Tools
Use
1
Flaring tool (Ø 6,35 - Ø 19,05)
Flaring the pipes
2
Reamer
Remove burrs from cut edges of pipes.
3
Pipe cutter (Max 35mm Copper pipe)
Cutting the pipings
4
Wrench (H5, H4 hexagonal wrench)
To open the service valve
5
Pipe bender
Bending the pipings
6
Leak detector
Check the gas-leakage of connecting part of the pipings
7
Manifold gauge
To measure the pressure, to charge the refrigerant
8
Charge-nipple
To connect the bombe
9
Vacuum pump
To remove the air in the pipe.
10
Charge cylinder balance 
To measure the refrigerant amount
11
Bombe (Freon-22)
Gas charge
Air purge
Cleaning the pipe
12
Spanner
To tighten the connecting parts of the pipings
13
Monkey spanner
14
Driver(    ,    )
15
Benchi (150mm)
Cutting the wires
16
Tapeline
To measure the length
17
Core drill
To make holes through the concrete to wall and blocks
18
voltmeter, Amperemeter, Clampmeter 
To measure the current and voltage
19
Insulation resistance tester
To measure the insulation resistance
20
Glass thermometer
To measure the intake and outlet air temperature of 
the indoor unit
21
Copper tubes
To use the connecting pipings
22
Insulation material
To cover the connecting pipings
23
Tape
To finish the connecting pipings
24
Electrical leakage Breaker
To shut off the main power
25
Cable
To connect the cable from outdoor unit to indoor unit
26
Drain hose sockets, elbows
To remote the condensing water
2) Preparation of installation parts and tools