Installation of Unit
Installation Manual  7
ENGLISH
3. Piping length and the elevation
CAUTION:
• Capacity is based on standard length and maximum allowance length is on
the basis of reliability.
• Oil trap should be installed every 5~7 meters.
20K
5/8"
1/4"
25
15
28K/30K/40K
5/8"
3/8"
30
20
44K/48K/50K
3/4"
3/8"
40
25
80K
1"
5/8"
50
30
PIPE SIZE
MODEL
GAS SIDE
LIQUID SIDE
Max.
Length
A (m)
Max.
Elevation
B (m)
A
B
Indoor unit
Outdoor unit
Floor Standing type Air Conditioner
Installation of Unit
The Indoor Unit Installation
Outdoor unit Installation
200mm
70mm
70mm
90mm
Wall
Core Drill
Tilt 
Cut if necessary
More than 15mm
Wall
Plastic tube
(Bushing)
INSIDE
OUTSIDE
1. The mounting floor should be strong and solid
enough to prevent it from vibration.
2. Drill the piping hole with 70mm diameter hole-
core drill at either the right or the left of indoor
unit. The hole should be sightly slant to the
outdoor side.
3. Insert the plastic tube through the hole.
4. Cut the extruded outside part of the plastic
tube, if necessary.
1. Install the outdoor unit on the concrete or any solid base securely and horizontally by securing it
with bolts (Ø12mm) and nuts.
2. If there is any vibration transmitted to the building, mount the rubber underneath the outdoor unit.
Refrigerant amount
Before shipment, this air conditioner is filled
with the rated amount of refrigerant including
additional amount required for air-purging,
subject to 5m piping length. (The rated amount
of refrigerant is indicated on the name plate.)
But when the piping length exceeds 5 meters,
additional charge is required according to the
following table.
Example)  28K/30K
In case of 10m long pipe(one-way), the amount
of refrigerant to be replenished is:
(10 - 5) x 30 = 150g
(Unit: g)
REFRIGERANT CHARGE
30 per 1m
40 per 1m
80 per 1m
MODEL
20K/28K/30K/40K
(Btu/h) 
44K/48K/50K
(Btu/h)
80K
(Btu/h)
Installation Manual  9
ENGLISH
Installation of Unit
Installation Method
No.
Installation works
Descriptions
1
Preparation of tools and installation parts
Preparation of installation
2
Flaring the pipes
To insert the flare nuts, mounted on the 
connection parts of both indoor and 
outdoor unit, onto the copper pipes.
3
Pipe bending
To reduce the flow resistance of refrigerant.
4
Connection of installation parts
Connection of long piping
(elbows, socket etc)
5
Tighten the flare nut (outdoor) 
Connecting the pipings of the outdoor unit.
6
Blowing the pipings
To remove dust and scale in working.
7
Tighten the flare nut (indoor)
Connecting the pipings of the indoor unit.
8
Check a gas-leakage of the connecting 
part of the pipings.
9
Vacuum drying of the piping and indoor unit
The air which contains moisture and which
remains in the refrigeration cycle may cause a 
malfunction on the compressor
10
Open the 3-way (liquid side) and 
3-way (gas side) valves.
11
Form the pipings
To prevent heat loss and sweat
12
Checking the drainage (indoor unit) 
To ensure if water flow drain hose of indoor unit.
13
Connecting the cable between outdoor 
Preparation of the operating
and indoor unit 
14
Connecting the main cable to outdoor unit
15
Supply the power to the crankcase heater
To prevent the liquid back to the compressor.
(Before the operating the unit)
(Heat pump only)
16
Cooling operation
(Use the remote control or display of the
indoor unit)
êìëëäàâ
ü
áõä
LG Å˚ÚÓ‚ÓÈ Ì‡ÔÓθÌ˚È 
ÍÓ̉ˈËÓÌÂ
êìäéÇéÑëíÇé èé ùäëèãìÄíÄñàà
ÇÄÜçé
• èÂ‰ ÛÒÚ‡ÌÓ‚ÍÓȠˠ̇˜‡ÎÓÏ ˝ÍÒÔÎÛ‡Ú‡ˆËË ÍÓ̉ˈËÓÌÂ‡ 
‚ÌËχÚÂθÌÓ ËÁÛ˜ËÚ ̇ÒÚÓfl˘Â ÛÍÓ‚Ó‰ÒÚ‚Ó. 
• èÓÒΠ‚ÌËχÚÂθÌÓ„Ó ËÁÛ˜ÂÌËfl ÒÓı‡ÌËÚ ̇ÒÚÓfl˘Â 
ÛÍÓ‚Ó‰ÒÚ‚Ó Ò ˆÂθ˛ ÔÓÎÛ˜ÂÌËfl ‰ÓÔÓÎÌËÚÂθÌÓÈ 
ËÌÙÓχˆËË. 
ìÒÚ‡Ìӂ͇ ÍÓ̉ˈËÓÌÂ‡ ‰ÓÎÊ̇ ·˚Ú¸ 
Òӄ·ÒÓ‚‡Ì‡ Ò ÍÓÏÏÛ̇θÌÓÈ ÒÎÛÊ·ÓÈ, 
Ó·ÂÒÔ˜˂‡˛˘ÂÈ ÔÓ‰‡˜Û ˝ÎÂÍÚÓ˝ÌÂ„ËË 
(Ô‡‚Ë· Â‚ÓÔÂÈÒÍËı ÌÓÏ EN 61000-2, 
61000-3). 
BE01
Page of 127
Display

Click on the first or last page to see other LP-C508T / LP-H508T / LP-Z508T service manuals if exist.