• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidifica-
tion operation and 4-min compressor off repeat.
Compressor ON Temp.
Setting Temp+0.5°C
Compressor OFF Temp.
Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation(H/P model)
• When the intake air temp reaches +3°…above the setting temp, the compressor is turned off.  When below
the setting temp, the compressor is turned on.
Compressor ON Temp.
Setting Temp.
Compressor OFF Temp.
Setting Temp.+3°C 
• While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper-
ates with Super-Low(while in sleep mode, with the medium airflow speed).
• While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
• While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control(H/P model)
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 60 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation or after the outdoor fan operates with-
in max. 2 minutes 30 seconds when the outdoor pipe temperature rises over 12°C even it before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 60 minutes passed
from  ending of the first defrost and more than 10 minutes operation of compressor.
 Cooling overload(except : LM-1963C2L/M, LM-1723C2L/M, LM-1723A2L, LM-2163C2L/M, LM-1460C2L/M)
• Control indoor fan by sensing outdoor pipe temperature.
• One step down from setting fan speed if pipe temperature is oven 50°C and if below 45°C, operate on setting
temperature.
Heating overload(H/P models)
• Outdoor fan ON/OFF by sensing outdoor pipe temperature.
• Outdoor fan is OFF if pipe temperature is over 6.5°C and outdoor fan is ON if pipe temperature is below 0°C.
• Outdoor fan is off if any one part is heating overload condition.
-29-
- 3 -
Functions
• Room temperature sensor. (THERMISTOR)
• Maintains the room temperature in accordance with the Setting Temp. 
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low, Chaos
--- Lights up in operation
--- Lights up in Sleep Mode
--- Lights up in Timer Mode
--- Lights up in Deice Mode(for Heat pump model)
--- Lights up in Compressor operation(for Cooling model)
• Intermittent operation of fan at low speed.
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The fan is switched to intermittent or irregular operation
• The fan speed is automatically switched from high to low speed. 
• The louver can be set at the desired position or swing 
up and down automatically. 
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
OUT
DOOR
Health Dehumidification Operation
• Both the indoor and outdoor fan
stops during deicing.
• Hot start after deice ends.
• The indoor fan stops until the 
evaporator piping temperature will be
reached at 28°C.
Sleep Mode Auto Control
Natural Air Control by CHAOS Logic
Airflow Direction Control
Deice (defrost) control (Heating)
Hot-start Control (Heating)
-30-
■ 
Fuzzy Operation (C/O Model)
• According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting
temp, the compressor is turned off. When 0.5°C or more above the setting temp, the compressor is turned on.
Compressor ON Temp   
Setting Temp + 0.5°C
Compressor OFF Temp 
Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C 
Intake Air Temp      
25°C
24°C 
Intake Air Temp < 26°C 
Intake Air Temp + 1°C
22°C 
Intake Air Temp < 24°C 
Intake Air Temp + 0.5°C
18°C 
Intake Air Temp < 22°C 
Intake Air Temp
Intake Air Temp<18°C
➲ 
18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule. 
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the 
temperature.
Fuzzy Operation (H/P Model)
• When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since
the operation off, the operation mode is selected.
• When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only
the indoor fan is operated for 15 seconds.  Then an operation mode is selected according to the intake air
temp at that moment as follows.
24°C 
Inatake Air Temp   
Fuzzy Operation for Cooling
21°C 
Inatake Air Temp<24°C
Fuzzy Operation for Dehumidification
Inatake Air Temp<21°C 
Fuzzy Operation for Heating
• If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10
sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.
1) Fuzzy Operation for Cooling
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off.  When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp  
Setting Temp +0.5°C
Compressor OFF Temp 
Setting Temp + 0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C
Intake Air Temp      
25°C
24°C
Intake Air Temp<26°C 
Intake Air Temp + 1°C
22°C
Intake Air Temp<24°C 
Intake Air Temp + 0.5°C
18°C
Intake Air Temp<22°C 
Intake Air Temp
Intake Air Temp<18°C       
18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the tem-
perature.
-31-
2) Fuzzy Operation for Dehumidification
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below
the setting temp, the compressor is turned off.  When 0.5°C or more above the setting temp, the compressor
is turned on.
Compressor ON Temp 
Setting Temp + 0.5°C
Compressor OFF Temp 
Setting Temp+0.5°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
26°C 
Intake Air Temp 
25°C
24°C 
Intake Air Temp<26°C 
Intake Air Temp+1°C
22°C 
Intake Air Temp<24°C 
➲ 
Intake Air Temp+0.5°C
18°C 
Intake Air Temp<22°C 
Intake Air Temp
Intake Air Temp<18°C    
18°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in
dehumidification operation.
3) Fuzzy Operation for Heating
• According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C or more above
the setting temp, the compressor is turned off.  When below the setting temp, the compressor is turned on.
Compressor ON Temp 
Setting Temp
Compressor OFF Temp 
Setting Temp + 3°C
• At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the
intake air temp at that time.
20°C
Intake Air Temp 
Intake Air Temp + 0.5°C
Intake Air Temp<20°C 
20°C
• When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the
Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature
automatically according to the Fuzzy rule.
• While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the
intake air temperature and the setting temperature.
■ 
Airflow Speed Selection
• The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow
speed selection key on the remote control.
On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input.  It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.