3. Gas Charging 
(After Evacuation)
• Procedure 
(1) Connect the charge hose to the charging
cylinder. 
–  Connect the charge hose which you dis-
connected from the vacuum pump to the valve
at the bottom of the cylinder. 
– If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid. 
(2) Purge the air from the charge hose.   
–  Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid
refrigerant).  The procedure is the same if
using a gas cylinder. 
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
–  If the system can not be charged with the
specified amount of refrigerant, it can be
charged with a little at a time (approximately
150g each time) while operating the air
conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1
minute and then repeat the procedure
(pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port. 
–  Stopping partway will allow the gas to be
discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose. 
(5) Mount the valve stem nuts and the service
port nut. 
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage. 
\
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner. 
Lo
Charging
cylinder 
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
3-Way
valve
3-Way
valve
OPEN
Open
Check valve
(1)
–29–
Cycle Troubleshooting Guide 
Trouble analysis 
1. Check temperature difference between intake and discharge air and operating current. 
Temp. Difference 
Temp. difference   :   approx. 0°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   approx. 8°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   less than 8°C
Current                  :   over the rated
current 
Temp. difference   :   over 8°C 
Operating Current 
All amount of refrigerant leaked out
Check refrigeration cycle
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor 
Excessive amount of refrigerant
Normal 
Notice : 
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger. 
2. Check temperature and pressure of refrigeration cycle. 
Notice : 
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition. 
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty. 
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
Defective compressor
Current is low
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of 
operation
Insufficient amount of 
Current is low
Lower 
Higher
refrigerant (Leakage)
Clogging
Current is low 
High 
Higher  
–30–
Electronic Parts Troubleshooting Guide
: The unit does not operate.
Possible Trouble 1
–31–
YES
YES
YES
NO
YES
Is the input voltage
of transformer AC220V?
Is the input voltage
of IC01D DC14V?
Check the FUSE
and the wiring diagram.
Is the output voltage 
of IC01D DC12V?
Is the PIN 31,32 of
MICOM. DC5V?
Exchange MICOM
YES
NO
Check the main P.C.B
pattern
NO
NO
Check the D02D~D05D
NO
YES
Exchange 
the transformer
Is shorted the
transformer output?
NO
YES
Is the output voltage 
of IC02D DC5V?
NO
Exchange IC01D
Exchange IC02D
Is the output voltage
of transformer about AC14V?
Check the 
5V P.C.B pattern.
–32–
Possible Trouble 2
: The indoor fan does not operate.
NO
NO
Is it the HOT
START mode?
Is IC01M operated
normally?
Check the fan motor
and connector.
(CN-MOTOR)
YES
Is the each Relay
any problem?
YES
NO
YES
It is normal operation.
Exchange IC01M
Exchange Relay
NO
YES
YES
YES
Is the LCD operated
normally?
Is the terminal of wired
Remocon T2 DC12V
Is the pin 31, 32 of
Micom DC 5V
Change the wired Remocon.
Check the wired Remocon 
PCB and DC 12V pattern.
NO
NO
Check the parts of 
communication.
Connector CN-Remo, and 
terminals of wired 
Remocon exactly.
Possible Trouble 3
: Wired remote controller does not operate.