JBL ON TOUR (serv.man6) EMC - CB Certificate ▷ View online
IEC 60950 3rd. Ed, 1999
- Page 1 of 5 -
Order No. 23172
APPENDIX: US DEVIATIONS
Test results according to CB BULLETIN No. 105A, May 2003.
Clause
Requirement - Test
Result - Remark
Ver-
dict
The United States of America and Canada have adopted a single, bi-
national standard, CAN/CSA C22.2 No. 60950/UL60950, Third Edition,
based on IEC 60950, Third Edition
national standard, CAN/CSA C22.2 No. 60950/UL60950, Third Edition,
based on IEC 60950, Third Edition
—
The following is a summary of the key national differences based on
national regulatory requirements, such as the National Electrical Code
(NEC) ANSI/ NFPA 70-1999, which are referenced in legislation and
which form the basis for the rules and practices followed in the
electrical and building installations. The bi-national standard referenced
above should be consulted for further details on the national differences
summarized below.
national regulatory requirements, such as the National Electrical Code
(NEC) ANSI/ NFPA 70-1999, which are referenced in legislation and
which form the basis for the rules and practices followed in the
electrical and building installations. The bi-national standard referenced
above should be consulted for further details on the national differences
summarized below.
—
1.1.1
All equipment is to be designed to allow
installations in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70, and,
unless marked or otherwise identified, the
standard for the Protection of Electronic
Computer/Data -Processing Equipment,
ANSI/NFPA 75.
installations in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70, and,
unless marked or otherwise identified, the
standard for the Protection of Electronic
Computer/Data -Processing Equipment,
ANSI/NFPA 75.
Class III equipment.
N
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
For length 3.05m or less, external
interconnecting flexible cord and cable
assemblies which are not types specified in the
NEC are required to have special construction
features and identification markings.
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
For length 3.05m or less, external
interconnecting flexible cord and cable
assemblies which are not types specified in the
NEC are required to have special construction
features and identification markings.
Class III equipment.
N
1.7.1
Equipm ent for use on supply systems with a
neutral and more than one phase conductor
(e.g. 120/240 V, 3-wire) require a special
marking format for electrical ratings.
A voltage rating that exceeds an attachment
plug cap rating is only permitted if it does not
e xceed the extreme operating conditions in
Table 2 of CAN/CSA C22.2 No. 235, and if it is
part of a range that extends into the Table 2
“Normal Operating Conditions”. Likewise, a
voltage rating shall not be lower than the
specified “Normal Operating Conditions”,
unless it is part of a range that extends into the
“Normal Operating Conditions”.
neutral and more than one phase conductor
(e.g. 120/240 V, 3-wire) require a special
marking format for electrical ratings.
A voltage rating that exceeds an attachment
plug cap rating is only permitted if it does not
e xceed the extreme operating conditions in
Table 2 of CAN/CSA C22.2 No. 235, and if it is
part of a range that extends into the Table 2
“Normal Operating Conditions”. Likewise, a
voltage rating shall not be lower than the
specified “Normal Operating Conditions”,
unless it is part of a range that extends into the
“Normal Operating Conditions”.
Class III equipment.
N
2.5
Where a fuse is used to provide Class 2,
Limited Power Source (or TNV) current
limiting, it shall not be operator-accessible
unless it is not interchangeable.
Limited Power Source (or TNV) current
limiting, it shall not be operator-accessible
unless it is not interchangeable.
No such fuse used.
N
IEC 60950 3rd. Ed, 1999
- Page 2 of 5 -
Order No. 23172
2.7.1
Suitable NEC branch circuit protection is
required for all standard supply outlets,
receptacles and medium -base or smaller
lampholders if the supply branch circuit
protection is not suitable.
Power distribution transformers distributing
power at 100 V or more, and rated 10 kVA or
more, require transformer overcurrent
protection.
required for all standard supply outlets,
receptacles and medium -base or smaller
lampholders if the supply branch circuit
protection is not suitable.
Power distribution transformers distributing
power at 100 V or more, and rated 10 kVA or
more, require transformer overcurrent
protection.
Class III equipment.
N
3.2
Wiring methods (terminals, leads etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC.
the connection of the equipment to the mains
shall be in accordance with the NEC.
Class III equipment.
N
3.2.1
Power supply cords are required to have
attachment plugs rated not less than 125
percent of the rated current of the equipment.
attachment plugs rated not less than 125
percent of the rated current of the equipment.
Class III equipment.
—
3.2.3
Permanent connection of equipment to the
mains supply by a power supply cord is not
permitted.
mains supply by a power supply cord is not
permitted.
Not permanently connected
equipment.
equipment.
N
3.2.5
Power supply cords are required to be no
longer than 4.5m in length.
Flexible power supply cords are required to be
compatible with Article 400 o f the NEC.
longer than 4.5m in length.
Flexible power supply cords are required to be
compatible with Article 400 o f the NEC.
Class III equipment.
N
3.2.8
Permanently connected equipment is required
to have a suitable wiring compartment and wire
bending space.
to have a suitable wiring compartment and wire
bending space.
Not permanently connected
equipment.
equipment.
N
3.3
Wiring terminals and associated spacings for
field wiring c onnections shall comply with CSA
C22.2 No. 0.
field wiring c onnections shall comply with CSA
C22.2 No. 0.
Class III equipment.
N
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3mm
conductors larger than 10 AWG (5.3mm
2
).
No conductors larger than 10 AWG.
__
3.3.4
Terminals for permanent wiring, including
protective earthing terminals are required to be
suitable for U.S./Canadian wire gauge sizes,
rated 125 percent of the equipment rating, and
specially marked when specified (1.7.7).
protective earthing terminals are required to be
suitable for U.S./Canadian wire gauge sizes,
rated 125 percent of the equipment rating, and
specially marked when specified (1.7.7).
Class III equipment.
N
3.4.2
Motor control devices are required for co rd-
connected equipment with a motor if the motor
(a) has a nominal voltage rating greater than
120 V, (b) is rated more than 12 A, or (c) is
rated more than 1/3hp (locked rotor current
over 43 A).
connected equipment with a motor if the motor
(a) has a nominal voltage rating greater than
120 V, (b) is rated more than 12 A, or (c) is
rated more than 1/3hp (locked rotor current
over 43 A).
No such motors in the equipment.
N
3.4.8
Vertically-mounted disconnect switches and
circuit breakers are required to have the “on”
position indicated by the handle in the up
position.
circuit breakers are required to have the “on”
position indicated by the handle in the up
position.
No disconnect switch provided.
N
3.4.10
For computer room applications, equipment
with battery systems capable of supplying 750
VA for five minutes are required to have a
battery disconnect means that may be
connected to the computer room remote
power-off circuit.
with battery systems capable of supplying 750
VA for five minutes are required to have a
battery disconnect means that may be
connected to the computer room remote
power-off circuit.
No such battery in the equipment.
N
IEC 60950 3rd. Ed, 1999
- Page 3 of 5 -
Order No. 23172
4.3.12
The maximum quantity of flammable liquid
stored in equipment is req uired to comply with
NFPA 30.
stored in equipment is req uired to comply with
NFPA 30.
No flammable liquids within the
equipment.
equipment.
N
4.3.13
Equipment with lasers is required to meet
Code of Federal Regulations 21CFR 1040 and
Canadian Radiation Emitting Devices Act,
REDR C1370.
Code of Federal Regulations 21CFR 1040 and
Canadian Radiation Emitting Devices Act,
REDR C1370.
No lasers, LED’s defused type.
N
4.7.1
For computer room applications, automated
information storage systems with combustible
media greater than 27 cubic feet are required
to have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an e xtended
discharge.
information storage systems with combustible
media greater than 27 cubic feet are required
to have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an e xtended
discharge.
The equipment has no combustible
area greater than 27 cubic feet.
area greater than 27 cubic feet.
N
4.7.3.1
For computer room applications, enclosures
with combustible material measuring greater
than 0.9 m
with combustible material measuring greater
than 0.9 m
2
or a single dimension greater than
1.8 m, are required to have a flame spread
rating of 50 or less. For other applications,
enclosures with the same dimensions require a
flame spread rating of 200 or less.
rating of 50 or less. For other applications,
enclosures with the same dimensions require a
flame spread rating of 200 or less.
The equipment has no combustible
material greater than 0.93m2 or
single dimension greater than 1.8m.
material greater than 0.93m2 or
single dimension greater than 1.8m.
N
Annex H
Equipment that produces ionizing radiation is
required to comply with Code of Federal
Regulations, 21 CFR 1020 and Canadian
Radiation Emitting Devices Act, REDR C1370.
required to comply with Code of Federal
Regulations, 21 CFR 1020 and Canadian
Radiation Emitting Devices Act, REDR C1370.
The equipment does not produce
ionizing radiation.
ionizing radiation.
N
IEC 60950 3rd. Ed, 1999
- Page 4 of 5 -
Order No. 23172
The following key national differences are based on requirements other than
national regulatory requirements. The bi-national standard referenced above
should be consulted for further details on the national differences summarized
below.
national regulatory requirements. The bi-national standard referenced above
should be consulted for further details on the national differences summarized
below.
—
1.5.1
Some components and materials associate d
with the risk of fire, electric shock, or personal
injury are required to have component or
material ratings in accordance with the
applicable national (U.S. and Canadian)
component or material requirements.
These components include:
attachment plugs, cathode ray tubes, circuit
breakers, communication circuit accessories,
cord sets and power supply cords, direct plug-
in equipment, enclosures (outdoor), flexible
cords and cables, fuses (branch circuit),
fuseholders, ground-fault current interrupters,
industrial control equipment, insulating tape,
interconnecting cables, lampholders, limit
controls, printed wiring, protectors for
communications circuits, receptacles, solid
state controls, supplementary protectors, surge
suppressors, switches (including interlock
switches), thermal cutoffs, thermostats,
transformer winding wire, tubing, wire
connectors and wire and cables
with the risk of fire, electric shock, or personal
injury are required to have component or
material ratings in accordance with the
applicable national (U.S. and Canadian)
component or material requirements.
These components include:
attachment plugs, cathode ray tubes, circuit
breakers, communication circuit accessories,
cord sets and power supply cords, direct plug-
in equipment, enclosures (outdoor), flexible
cords and cables, fuses (branch circuit),
fuseholders, ground-fault current interrupters,
industrial control equipment, insulating tape,
interconnecting cables, lampholders, limit
controls, printed wiring, protectors for
communications circuits, receptacles, solid
state controls, supplementary protectors, surge
suppressors, switches (including interlock
switches), thermal cutoffs, thermostats,
transformer winding wire, tubing, wire
connectors and wire and cables
All critical components are IEC, UL
or CSA certified. See list of critical
components in main CB report
(§1.5.01).
or CSA certified. See list of critical
components in main CB report
(§1.5.01).
P
2.3.1
For TNV-2 and TNV-3 circuits with other than
ringing signals and with voltages exceeding
42.4 Vp or 60 Vdc, the maximum acceptable
current through a 2000 ohm resistor (or
greater) connected across the voltage source
with other loads disconnected is 7.1 mA peak
or 30 mA dc under normal operating
conditions.
ringing signals and with voltages exceeding
42.4 Vp or 60 Vdc, the maximum acceptable
current through a 2000 ohm resistor (or
greater) connected across the voltage source
with other loads disconnected is 7.1 mA peak
or 30 mA dc under normal operating
conditions.
No TNV circuitry.
N
2.6.3.3
When subject to impedance testing, protective
earthing and bonding is required to be tested
subject per the specified test conditions that
originate in CSA C22.2 No. 0.4.
earthing and bonding is required to be tested
subject per the specified test conditions that
originate in CSA C22.2 No. 0.4.
Class III equipment.
N
4.2.8.1
Enclosures around CRT’s with a face area of
160 mm or more are required to reduce the
risk of injury due to the implosion of the CRT.
160 mm or more are required to reduce the
risk of injury due to the implosion of the CRT.
No CRTs in the equipment.
N
Click on the first or last page to see other ON TOUR (serv.man6) service manuals if exist.