DOWNLOAD JBL ON AIR WIRELESS (serv.man2) Service Manual ↓ Size: 2.27 MB | Pages: 62 in PDF or view online for FREE

Model
ON AIR WIRELESS (serv.man2)
Pages
62
Size
2.27 MB
Type
PDF
Document
EMC - CB Certificate
Brand
Device
Audio
File
on-air-wireless-sm2.pdf
Date

JBL ON AIR WIRELESS (serv.man2) EMC - CB Certificate ▷ View online

ATTACHMENT 
 
Report No: U1011006-610 
National Differences 
 
Page 8 of 12 
 
National Differences 
Clause 
Requirement + Test 
Result - Remark 
Verdict 
 
 
Korean National Differences 
 
Korean National Differences 
 
Corresponding National Standard: K 60950-1 
1.5.101 
Addition: 
Plugs for the connection of the apparatus to the 
supply mains shall comply with the Korean 
requirement (KSC 8305). 
Not directly connected to the 
mains. 
N/A 
Addition: EMC 
The apparatus shall comply with the relevant 
CISPR standards. 
It shall be checked with the 
compliance during national 
approval. 
N/A 
ATTACHMENT 
 
Report No: U1011006-610 
National Differences 
 
Page 9 of 12 
 
National Differences 
Clause 
Requirement + Test 
Result - Remark 
Verdict 
 
US National Differences 
 
US National Differences 
SPECIAL NATIONAL CONDITIONS BASED ON FEDERAL REGULATIONS 
1.1.1  
All equipment is to be designed to allow 
installation in accordance with the National 
Electrical Code (NEC), ANSI/NFPA 70, and when 
applicable, the National Electrical Safety Code, 
IEEE C2.  Also, unless marked or otherwise 
identified, installation is allowed per the Standard 
for the Protection of Electronic Computer/Data-
Processing Equipment, ANSI/NFPA 75.  
EUT in compliance with 
requirements of IEC 60950-1. 
Overall acceptance shall be 
evaluated during national 
approval. 
N/A 
1.4.14  
For Pluggable Equipment Type A, the protection 
in the installation is assumed to be 20A.  
Class III equipment. Not directly 
connected to the mains. 
N/A 
1.5.5  
For lengths exceeding 3.05 m, external 
interconnecting flexible cord and cable 
assemblies are required to be a suitable cable 
type specified in the NEC. For lengths 3.05 m or 
less, external interconnecting flexible cord and 
cable assemblies that are not types specified in 
the NEC are required to have special construction 
features and identification markings.  
No such consideration. 
N/A 
1.7.1  
Equipment for use on a.c. mains supply systems 
with a neutral and more than one phase 
conductor (e.g. 120/240 V, 3-wire) require a 
special marking format for electrical ratings.  
Class III equipment. Not directly 
connected to the mains. 
N/A 
2.5  
Where a fuse is used to provide Class 2, Limited 
Power Source, or TNV current limiting, it shall not 
be operator-accessible unless it is not 
interchangeable.  
No such fuse. 
N/A 
2.7.1  
Suitable NEC branch circuit protection rated at 
the maximum circuit rating is required for all 
standard supply outlets and receptacles (such as 
supplied in power distribution units) if the supply 
branch circuit protection is not suitable.  Power 
distribution transformers distributing power at 100 
volts or more, and rated 10 kVA or more, require 
special transformer overcurrent protection.  
Class III equipment. Not directly 
connected to the mains. 
N/A 
3.2  
Wiring methods (terminals, leads, etc.) used for 
the connection of the equipment to the mains 
shall be in accordance with the NEC.  
Class III equipment. Not directly 
connected to the mains. 
N/A 
3.2.1  
Power supply cords are required to have 
attachment plugs rated not less than 125 percent 
of the rated current of the equipment.  
Same as above. 
N/A 
3.2.1.2  
Equipment connected to a centralized d.c. power 
system, and having one pole of the DC mains 
input terminal connected to the main protective 
earthing terminal in the equipment, is required to 
comply with special earthing, wiring, marking and 
installation instruction requirements.  
Same as above. 
N/A 
3.2.3  
Permanent connection of equipment to the mains 
supply by a power supply cord is not permitted, 
except for certain equipment, such as ATMs.  
Not such equipment. 
N/A 
ATTACHMENT 
 
Report No: U1011006-610 
National Differences 
 
Page 10 of 12 
 
National Differences 
Clause 
Requirement + Test 
Result - Remark 
Verdict 
 
US National Differences 
3.2.5  
Power supply cords are required to be no longer 
than 4.5 m in length and minimum length shall be 
1.5 m. Flexible power supply cords are required to 
be compatible with Article 400 of the NEC.  
Class III equipment. Not directly 
connected to the mains. 
N/A 
3.2.9  
Permanently connected equipment must have a 
suitable wiring compartment and wire bending 
space.  
Not such equipment. 
N/A 
3.3.3  
Wire binding screws are not permitted to attach 
conductors larger than 10 AWG (5.3 mm2).  
No such consideration. 
N/A 
3.3.4  
Terminals for permanent wiring, including 
protective earthing terminals, must be suitable for 
U.S wire gauge sizes, rated 125 percent of the 
equipment rating, and be specially marked when 
specified (1.7.7).  
No such consideration. 
N/A 
3.4.2  
Motor control devices are required for cord-
connected equipment with a motor if the 
equipment is rated more than 12 A, or if the motor 
has a nominal voltage rating greater than 120 V, 
or is rated more than 1/3 hp (locked rotor current 
over 43 A).  
No such consideration. 
N/A 
3.4.8  
Vertically-mounted disconnect switches and 
circuit breakers are required to have the "on" 
position indicated by the handle in the up position.  
No such consideration. 
N/A 
3.4.11  
For computer room applications, equipment with 
battery systems capable of supplying 750 VA for 
five minutes are required to have a battery 
disconnect means that may be connected to the 
computer room remote power-off circuit.  
Not such equipment. 
N/A 
4.3.12  
The maximum quantity of flammable liquid stored 
in equipment is required to comply with NFPA 30.  
No such consideration. 
N/A 
4.3.13.5  
Equipment with lasers is required to meet the 
Code of Federal Regulations 21 CFR 1040.  
No laser. 
N/A 
4.7  
For computer room applications, automated 
information storage systems with combustible 
media greater than 0.76 m3 (27 cu ft) are 
required to have a provision for connection of 
either automatic sprinklers or a gaseous agent 
extinguishing system with an extended discharge.  
No such consideration. 
N/A 
4.7.3.1  
For computer room applications, enclosures with 
combustible material measuring greater than 0.9 
m2  (10 sq ft) or a single dimension greater than 
1.8 m  (6 ft) are required to have a flame spread 
rating of 50 or less.  For other applications, 
enclosures with the same dimensions require a 
flame spread rating of 200 or less.   
No such consideration. 
N/A 
Annex H  
Equipment that produces ionizing radiation must 
comply with Federal Regulations, 21 CFR 1020  
No CRT. 
N/A 
ATTACHMENT 
 
Report No: U1011006-610 
National Differences 
 
Page 11 of 12 
 
National Differences 
Clause 
Requirement + Test 
Result - Remark 
Verdict 
 
US National Differences 
OTHER NATIONAL DIFFERENCES 
1.5.1  
Some components and materials associated with 
the risk of fire, electric shock, or personal injury 
are required to have component or material 
ratings in accordance with the applicable national 
(U.S. and Canadian) component or material 
requirements. These components include: 
attachment plugs, battery packs (rechargeable 
type, used with transportable equipment), cathode 
ray tubes, circuit breakers, communication circuit 
accessories, connectors (used for current 
interruption of non-LPS circuits), cord sets and 
power supply cords, direct plug-in equipment, 
enclosures (outdoor), flexible cords and cables, 
fuses (branch circuit), fuseholders, ground-fault 
current interrupters, industrial control equipment, 
insulating tape, interconnecting cables, 
lampholders, limit controls, printed wiring, 
protectors for communications circuits, 
receptacles, solid state controls, supplementary 
protectors, switches (including interlock switches), 
thermal cutoffs, thermostats, (multi-layer) 
transformer winding wire, transient voltage surge 
suppressors, tubing, wire connectors, and wire 
and cables.  
It shall be checked with the 
compliance during national 
approval. 
N/A 
1.6.1.2  
A circuit for connection to the DC Mains Supply is 
classified as either a SELV Circuit, TNV-2 Circuit 
or Hazardous Voltage Circuit depending on the 
maximum operating voltage of the supply. This 
maximum operating voltage it to include 
consideration of the battery charging “float 
voltage” associated with the intended supply 
system, regardless of the marked power rating of 
the equipment.  
Class III equipment. Not directly 
connected to the mains. 
N/A 
2.3.1  
For TNV-2 and TNV-3 circuits with other than 
ringing signals and with voltages exceeding 42.4 
Vpeak or 60 Vd.c., the max. acceptable current 
through a 2000 ohm resistor (or greater) 
connected across the voltage source with other 
loads disconnected is 7.1 mA peak or 30 mA d.c. 
under normal operating conditions.  
No TNV circuits. 
N/A 
2.3.2.1  
In the event of a single fault between TNV and 
SELV circuits, the limits of 2.2.3 apply to SELV 
Circuits and accessible conductive parts.  
No TNV circuits. 
N/A 
2.6.3.4  
Protective bonding conductors of non-standard 
protective bonding constructions (e.g., printed 
circuit traces) may be subjected to the additional 
limited short circuit test conditions specified.  
Class III equipment 
N/A 
4.2.8.1  
Enclosures around CRTs with a face diameter of 
160 mm or more are required to reduce the risk of 
injury due to the implosion of the CRT.  
No CRT. 
N/A 
Page of 62
Display

Click on the first or last page to see other ON AIR WIRELESS (serv.man2) service manuals if exist.