DOWNLOAD Harman Kardon GO PLAY MICRO (serv.man4) Service Manual ↓ Size: 1.43 MB | Pages: 81 in PDF or view online for FREE

Model
GO PLAY MICRO (serv.man4)
Pages
81
Size
1.43 MB
Type
PDF
Document
EMC - CB Certificate
Brand
Device
Audio
File
go-play-micro-sm4.pdf
Date

Harman Kardon GO PLAY MICRO (serv.man4) EMC - CB Certificate ▷ View online

 
 
 
 
Page 61 of 70 
Report No.: JGZ0512196-3 
IEC 60950-1 
Clause 
Requirement – Test   
Result – Remark   
Verdict 
 
  
TRF 
No.:IEC60950_1A 
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
 
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China 
Tel: (86 20) 8396 6868    Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com 
 
 
If this insulation forms part of a semiconductor 
component (e.g. an optocoupler), there is no 
distance through insulation requirement for the 
insulation consisting of an insulating compound 
completely filling the casing, so that 
CLEARANCES 
AND CREEPAGE DISTANCES
 do not exist, if the 
component passes the electric strength test in 
accordance with the compliance clause below 
and in addition 
- passes the tests and inspection criteria of 
2.10.8 with an electric strength test of 1,5 kV 
multiplied by 1,6 (the electric strength test of 
2.10.7 shall be performed using 1,5 kV), and 
- is subject to 
ROUTINGE TESTING
 for electric 
strength during manufacturing, using a test 
voltage of 1,5 kV. 
It is permitted to bridge this insulation with a 
capacitor complying with EN 132400:1994, 
subclass Y2. 
A capacitor classified Y3 according to 
EN 132400:1994, may bridge this insulation 
under the following conditions: 
- the insulation requirements are satisfied by 
having a capacitor classified Y3 as defined by 
EN 132400, which in addition to the Y3 testing, is 
tested with an impulse test of 2,5 kV defined in 
EN 60950:2000, 6.2.2.1; 
- the additional testing shall be performed on all 
the test specimens as described in EN 132400; 
- the impulse test of 2,5 kV is to be performed 
before the endurance test in EN 132400, in the 
sequence of tests as described in EN 132400. 
 N/A 
6.1.2.2 
The exclusions are applicable for 
PERMANENTLY 
CONNECTED EQUIPMENT
 and
 PLUGGABLE 
EQUIPMENT TYPE 
B and equipment intended to be 
used in a 
RESTRICTED ACCESS LOCATION
 where 
equipotential bonding has been applied, e.g. in a 
telecommunication centre, and which has 
provision for a permanently connected 
PROTECTIVE EARTHING CONDUCTOR 
and is provided 
with instructions for the installation of that 
conductor by a service person. 
 N/A 
7.1 
Requirements according to this annex, 6.1.2.1 
and 6.1.2.2 apply with the term 
TELECOMMUNICATION NETWORK
 in 6.1.2 being 
replaced by the term 
CABLE DISTRIBUTION SYSTEM
 N/A 
 
 
 
 
 
Page 62 of 70 
Report No.: JGZ0512196-3 
IEC 60950-1 
Clause 
Requirement – Test   
Result – Remark   
Verdict 
 
  
TRF 
No.:IEC60950_1A 
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
 
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China 
Tel: (86 20) 8396 6868    Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com 
 
 
(US) USA Deviation   
 
The United States of America and Canada have adopted a single, bi-national 
standards, CAN/CSA C22.2 No. 60950-1/UL60950-1, First Edition, which is based 
on IEC60950-1, First Edition. This bi-national standard should be consulted for 
further details on the national conditions and difference summarized below. 
The following is a summary of the key national differences based on national 
regulatory requirements, such as the National Electrical Code (NEC), ANSI/NFPA 
70-2002, which are referenced in legislation and which form the basis for the rules 
and practices followed in electrical and building installations. 
1.1.1 
All requirement is to be designed to allow 
installation in accordance with the National 
Electrical Code (NEC), ANSI/NFPA 70, the 
Canadian Electrical Code (CEC), Part I, 
CAN/CSA C22.1, and when applicable, the 
National Electrical Safety Code, IEEE C2. Also, 
unless marked or otherwise identified, installation 
is allowed per the Standard for the Protection of 
Electronic Computer/Date-Processing 
Equipment, ANSI/NFPA 75.   
 P 
1.4.14 
For Pluggable Equipment Type A, the protection 
in the installation is assumed to be 20A. 
 P 
1.5.5 
For lengths exceeding 3.05m, external 
interconnecting flexible cord and cable 
assemblies are required to be a suitable cable 
type (e.g. DP, CL2) specified in the NEC. 
For lengths 3.05 m or less, external 
interconnecting flexible cord and cable 
assemblies that are not type specified in the NEC 
are required to have special construction features 
and identification markings. 
 N/A 
1.7.1 
Equipment for use on a.c. mains supply systems 
with a neutral and more than one phase 
conductor (e.g. 120/240 V, 3-wire) require a 
special marking format for electrical ratings. 
A voltage rating that exceeds an attachment plug 
cap rating is only permitted if it does not exceed 
the extreme operating conditions in Table2 of 
CAN/CSA C22.2 No.235, and if it is part of a 
range that extends into the Table 2 “Normal 
Operation Conditions.” Likewise, a voltage rating 
shall not be lower than the specified “Normal 
Operation Conditions,” unless it is part of a range 
that extends into the “Normal Operation 
Conditions.” 
 N/A 
2.5 
Where a fuse is used to provide Class 2, LPS, or 
TNV current limiting. It shall not be operator-
accessible unless it is not interchangeable.   
 N/A 
 
 
 
 
Page 63 of 70 
Report No.: JGZ0512196-3 
IEC 60950-1 
Clause 
Requirement – Test   
Result – Remark   
Verdict 
 
  
TRF 
No.:IEC60950_1A 
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
 
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China 
Tel: (86 20) 8396 6868    Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com 
 
2.7.1 
Suitable NEC/CEC branch circuit protection rated 
at the maximum circuit rating is required for all 
standard supply outlets, receptacles and 
medium-base or smaller lampholders if the 
supply branch circuit protection is not suitable. 
Power distribution transformers distributing 
power at 100 volts or more, and rated 10kVA or 
more, require transformer overcurrent protection. 
 N/A 
3.2 
Wiring methods (terminals, leads, etc.) used for 
the connection of the equipment to the mains 
shall be in accordance with the NEC/CEC. 
 N/A 
3.2.1 
Power supply cords are required to have 
attachment plugs rated not less than 125 percent 
at the rated current of the equipment. 
 N/A 
3.2.3 
Permanent connection of equipment to the mains 
supply by a power supply cord is not permitted, 
except for certain equipment, such as ATMs. 
Transportable equipment 
N/A 
3.2.5 
Power supply cords are required to be no longer 
than 4.5m in length. Flexible power supply cords 
are required to be compatible with Article 400 of 
the NEC, and Tables 11 and 12 of the CEC. 
Appliance inlet used 
N/A 
3.2.9 
Permanently connected equipment is required to 
have a suitable wiring compartment and wire 
bending space. 
 N/A 
3.3 
Wiring terminals and associated spacings for 
field wiring connections shall comply with CSA 
C22.2 No. 0. 
 N/A 
3.3.3 
Wire bending screws are not permitted to attach 
conductors larger than 10 AWG (5.3 mm
2
). 
 N/A 
3.3.4 
Terminals for permanent wiring, including 
protective earthing terminals, are required to be 
suitable for U.S./Canadian wire gauge sizes, 
rated 125 percent of the equipment rating. And 
be specially marked when specified (1.7.7). 
 N/A 
3.4.2 
Motor control devices are required for cord-
connected equipment with a motor if the 
equipment is rated more than 12 A, or if the 
motor has a nominal voltage rating greater than 
120 V, or is rated more than 1/3 hp (locked rotor 
current over 43A). 
 N/A 
3.4.8 
Vertically-mounted disconnect switches and 
circuit breakers are required to have the “on” 
position indicated by the handle in the up 
position. 
 N/A 
3.4.11 
For computer room applications, equipment with 
battery systems capable of supplying 750 VA for 
five minutes are required to have a battery 
disconnect means that may be connected to the 
computer room remote power-off circuit. 
 N/A 
 
 
 
 
Page 64 of 70 
Report No.: JGZ0512196-3 
IEC 60950-1 
Clause 
Requirement – Test   
Result – Remark   
Verdict 
 
  
TRF 
No.:IEC60950_1A 
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
 
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China 
Tel: (86 20) 8396 6868    Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com 
 
4.3.12 
The maximum quantity of flammable liquid stored 
in equipment is required to comply with NFPA 30.
 N/A 
4.3.13 
Equipment with lasers is required to meet the 
Code of Federal Regulations 21 CFR 1040 (and 
the Canadian Radiation Emitting Devices Act, 
REDR C1370). 
LED used to indicate the 
operation in secondary circuit 
N/A 
4.7 
For computer room applications, automated 
information storage systems with combustible 
media greater than 27 cubic feet are required to 
have a provision for connection of either 
automatic sprinklers or a gaseous agent 
extinguishing system with an extended 
discharge. 
 N/A 
4.7.3.1 
For computer room applications, enclosures with 
combustible material measuring greater than 0.9 
m
2
 or a single dimension greater than 1.8 m are 
required to have a flame spread rating of 50 or 
less. For other applications, enclosures with the 
same dimensions require a flame spread rating 
of 200 or less. 
 N/A 
Annex H 
Equipment that produces ionizing radiation is 
required to comply with the Code of Federal 
regulations, 21 CFR 1020 (and the Canadian 
Radiation Emitting Devices Act, REDR C1370). 
 N/A 
 
The following key national differences are based on requirements other than 
national regulatory requirements. 
 
1.5.1  
Some components and materials associated with 
the risk of fire, electric shock, or personal injury 
are required to have component or material 
ratings in accordance with the applicable national 
(U.S. and Canadian) component or material 
requirements. These components include: 
attachment plugs, battery packs (rechargeable 
type, used with transportable equipment), 
cathode ray tubes, circuit breakers, 
communication circuit accessories, connectors 
(used for current interruption of non-LPS circuits), 
cord sets and power supply cords, direct plug-in 
equipment, enclosures (outdoor), flexible cords 
and cables, fuses (branch circuit), fuseholders, 
ground-fault current interrupters, industrial control 
equipment, insulating tape, interconnecting 
cables, lamperholders, limit controls, printed 
wiring, protectors for communications circuits, 
receptacles, solid state controls, supplementary 
protectors, surge suppressors, switches 
(including interlock switches), thermal cutoffs, 
thermostats, multi-layer transformer winding wire, 
tubing, wire connectors, and wire and cables. 
See table 1.5.1 
Page of 81
Display

Click on the first or last page to see other GO PLAY MICRO (serv.man4) service manuals if exist.