Harman Kardon GO PLAY MICRO (serv.man4) EMC - CB Certificate ▷ View online
Page 61 of 70
Report No.: JGZ0512196-3
IEC 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
TRF
No.:IEC60950_1A
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China
Tel: (86 20) 8396 6868 Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com
If this insulation forms part of a semiconductor
component (e.g. an optocoupler), there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that
component (e.g. an optocoupler), there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that
CLEARANCES
AND CREEPAGE DISTANCES
do not exist, if the
component passes the electric strength test in
accordance with the compliance clause below
and in addition
- passes the tests and inspection criteria of
2.10.8 with an electric strength test of 1,5 kV
multiplied by 1,6 (the electric strength test of
2.10.7 shall be performed using 1,5 kV), and
- is subject to
accordance with the compliance clause below
and in addition
- passes the tests and inspection criteria of
2.10.8 with an electric strength test of 1,5 kV
multiplied by 1,6 (the electric strength test of
2.10.7 shall be performed using 1,5 kV), and
- is subject to
ROUTINGE TESTING
for electric
strength during manufacturing, using a test
voltage of 1,5 kV.
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to
EN 132400:1994, may bridge this insulation
under the following conditions:
- the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in
EN 60950:2000, 6.2.2.1;
- the additional testing shall be performed on all
the test specimens as described in EN 132400;
- the impulse test of 2,5 kV is to be performed
before the endurance test in EN 132400, in the
sequence of tests as described in EN 132400.
voltage of 1,5 kV.
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to
EN 132400:1994, may bridge this insulation
under the following conditions:
- the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in
EN 60950:2000, 6.2.2.1;
- the additional testing shall be performed on all
the test specimens as described in EN 132400;
- the impulse test of 2,5 kV is to be performed
before the endurance test in EN 132400, in the
sequence of tests as described in EN 132400.
N/A
6.1.2.2
The exclusions are applicable for
PERMANENTLY
CONNECTED EQUIPMENT
and
PLUGGABLE
EQUIPMENT TYPE
B and equipment intended to be
used in a
RESTRICTED ACCESS LOCATION
where
equipotential bonding has been applied, e.g. in a
telecommunication centre, and which has
provision for a permanently connected
telecommunication centre, and which has
provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR
and is provided
with instructions for the installation of that
conductor by a service person.
conductor by a service person.
N/A
7.1
Requirements according to this annex, 6.1.2.1
and 6.1.2.2 apply with the term
and 6.1.2.2 apply with the term
TELECOMMUNICATION NETWORK
in 6.1.2 being
replaced by the term
CABLE DISTRIBUTION SYSTEM
.
N/A
Page 62 of 70
Report No.: JGZ0512196-3
IEC 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
TRF
No.:IEC60950_1A
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China
Tel: (86 20) 8396 6868 Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com
(US) USA Deviation
The United States of America and Canada have adopted a single, bi-national
standards, CAN/CSA C22.2 No. 60950-1/UL60950-1, First Edition, which is based
on IEC60950-1, First Edition. This bi-national standard should be consulted for
further details on the national conditions and difference summarized below.
The following is a summary of the key national differences based on national
regulatory requirements, such as the National Electrical Code (NEC), ANSI/NFPA
70-2002, which are referenced in legislation and which form the basis for the rules
and practices followed in electrical and building installations.
standards, CAN/CSA C22.2 No. 60950-1/UL60950-1, First Edition, which is based
on IEC60950-1, First Edition. This bi-national standard should be consulted for
further details on the national conditions and difference summarized below.
The following is a summary of the key national differences based on national
regulatory requirements, such as the National Electrical Code (NEC), ANSI/NFPA
70-2002, which are referenced in legislation and which form the basis for the rules
and practices followed in electrical and building installations.
P
1.1.1
All requirement is to be designed to allow
installation in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70, the
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Date-Processing
Equipment, ANSI/NFPA 75.
installation in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70, the
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Date-Processing
Equipment, ANSI/NFPA 75.
P
1.4.14
For Pluggable Equipment Type A, the protection
in the installation is assumed to be 20A.
in the installation is assumed to be 20A.
P
1.5.5
For lengths exceeding 3.05m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not type specified in the NEC
are required to have special construction features
and identification markings.
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not type specified in the NEC
are required to have special construction features
and identification markings.
N/A
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table2 of
CAN/CSA C22.2 No.235, and if it is part of a
range that extends into the Table 2 “Normal
Operation Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operation Conditions,” unless it is part of a range
that extends into the “Normal Operation
Conditions.”
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table2 of
CAN/CSA C22.2 No.235, and if it is part of a
range that extends into the Table 2 “Normal
Operation Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operation Conditions,” unless it is part of a range
that extends into the “Normal Operation
Conditions.”
N/A
2.5
Where a fuse is used to provide Class 2, LPS, or
TNV current limiting. It shall not be operator-
accessible unless it is not interchangeable.
TNV current limiting. It shall not be operator-
accessible unless it is not interchangeable.
N/A
Page 63 of 70
Report No.: JGZ0512196-3
IEC 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
TRF
No.:IEC60950_1A
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China
Tel: (86 20) 8396 6868 Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com
2.7.1
Suitable NEC/CEC branch circuit protection rated
at the maximum circuit rating is required for all
standard supply outlets, receptacles and
medium-base or smaller lampholders if the
supply branch circuit protection is not suitable.
Power distribution transformers distributing
power at 100 volts or more, and rated 10kVA or
more, require transformer overcurrent protection.
at the maximum circuit rating is required for all
standard supply outlets, receptacles and
medium-base or smaller lampholders if the
supply branch circuit protection is not suitable.
Power distribution transformers distributing
power at 100 volts or more, and rated 10kVA or
more, require transformer overcurrent protection.
N/A
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
N/A
3.2.1
Power supply cords are required to have
attachment plugs rated not less than 125 percent
at the rated current of the equipment.
attachment plugs rated not less than 125 percent
at the rated current of the equipment.
N/A
3.2.3
Permanent connection of equipment to the mains
supply by a power supply cord is not permitted,
except for certain equipment, such as ATMs.
supply by a power supply cord is not permitted,
except for certain equipment, such as ATMs.
Transportable equipment
N/A
3.2.5
Power supply cords are required to be no longer
than 4.5m in length. Flexible power supply cords
are required to be compatible with Article 400 of
the NEC, and Tables 11 and 12 of the CEC.
than 4.5m in length. Flexible power supply cords
are required to be compatible with Article 400 of
the NEC, and Tables 11 and 12 of the CEC.
Appliance inlet used
N/A
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
have a suitable wiring compartment and wire
bending space.
N/A
3.3
Wiring terminals and associated spacings for
field wiring connections shall comply with CSA
C22.2 No. 0.
field wiring connections shall comply with CSA
C22.2 No. 0.
N/A
3.3.3
Wire bending screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm
conductors larger than 10 AWG (5.3 mm
2
).
N/A
3.3.4
Terminals for permanent wiring, including
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes,
rated 125 percent of the equipment rating. And
be specially marked when specified (1.7.7).
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes,
rated 125 percent of the equipment rating. And
be specially marked when specified (1.7.7).
N/A
3.4.2
Motor control devices are required for cord-
connected equipment with a motor if the
equipment is rated more than 12 A, or if the
motor has a nominal voltage rating greater than
120 V, or is rated more than 1/3 hp (locked rotor
current over 43A).
connected equipment with a motor if the
equipment is rated more than 12 A, or if the
motor has a nominal voltage rating greater than
120 V, or is rated more than 1/3 hp (locked rotor
current over 43A).
N/A
3.4.8
Vertically-mounted disconnect switches and
circuit breakers are required to have the “on”
position indicated by the handle in the up
position.
circuit breakers are required to have the “on”
position indicated by the handle in the up
position.
N/A
3.4.11
For computer room applications, equipment with
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
N/A
Page 64 of 70
Report No.: JGZ0512196-3
IEC 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
TRF
No.:IEC60950_1A
Intertek Testing Services Shenzhen Ltd. Guangzhou GDD Branch
3/F., Hengyun Building, 728 Kaifa Ave., Guangzhou Economic & Technological Development District, Guangzhou, China
Tel: (86 20) 8396 6868 Fax: (86 20) 8222 8170 Website: www.china.intertek-etlsemko.com
4.3.12
The maximum quantity of flammable liquid stored
in equipment is required to comply with NFPA 30.
in equipment is required to comply with NFPA 30.
N/A
4.3.13
Equipment with lasers is required to meet the
Code of Federal Regulations 21 CFR 1040 (and
the Canadian Radiation Emitting Devices Act,
REDR C1370).
Code of Federal Regulations 21 CFR 1040 (and
the Canadian Radiation Emitting Devices Act,
REDR C1370).
LED used to indicate the
operation in secondary circuit
operation in secondary circuit
N/A
4.7
For computer room applications, automated
information storage systems with combustible
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended
discharge.
information storage systems with combustible
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended
discharge.
N/A
4.7.3.1
For computer room applications, enclosures with
combustible material measuring greater than 0.9
m
combustible material measuring greater than 0.9
m
2
or a single dimension greater than 1.8 m are
required to have a flame spread rating of 50 or
less. For other applications, enclosures with the
same dimensions require a flame spread rating
of 200 or less.
less. For other applications, enclosures with the
same dimensions require a flame spread rating
of 200 or less.
N/A
Annex H
Equipment that produces ionizing radiation is
required to comply with the Code of Federal
regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
required to comply with the Code of Federal
regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
N/A
The following key national differences are based on requirements other than
national regulatory requirements.
national regulatory requirements.
1.5.1
Some components and materials associated with
the risk of fire, electric shock, or personal injury
are required to have component or material
ratings in accordance with the applicable national
(U.S. and Canadian) component or material
requirements. These components include:
attachment plugs, battery packs (rechargeable
type, used with transportable equipment),
cathode ray tubes, circuit breakers,
communication circuit accessories, connectors
(used for current interruption of non-LPS circuits),
cord sets and power supply cords, direct plug-in
equipment, enclosures (outdoor), flexible cords
and cables, fuses (branch circuit), fuseholders,
ground-fault current interrupters, industrial control
equipment, insulating tape, interconnecting
cables, lamperholders, limit controls, printed
wiring, protectors for communications circuits,
receptacles, solid state controls, supplementary
protectors, surge suppressors, switches
(including interlock switches), thermal cutoffs,
thermostats, multi-layer transformer winding wire,
tubing, wire connectors, and wire and cables.
the risk of fire, electric shock, or personal injury
are required to have component or material
ratings in accordance with the applicable national
(U.S. and Canadian) component or material
requirements. These components include:
attachment plugs, battery packs (rechargeable
type, used with transportable equipment),
cathode ray tubes, circuit breakers,
communication circuit accessories, connectors
(used for current interruption of non-LPS circuits),
cord sets and power supply cords, direct plug-in
equipment, enclosures (outdoor), flexible cords
and cables, fuses (branch circuit), fuseholders,
ground-fault current interrupters, industrial control
equipment, insulating tape, interconnecting
cables, lamperholders, limit controls, printed
wiring, protectors for communications circuits,
receptacles, solid state controls, supplementary
protectors, surge suppressors, switches
(including interlock switches), thermal cutoffs,
thermostats, multi-layer transformer winding wire,
tubing, wire connectors, and wire and cables.
See table 1.5.1
P
Click on the first or last page to see other GO PLAY MICRO (serv.man4) service manuals if exist.