The machine does not function
with remote controller 
Push button "OI" on the wireless 
remote controller.
Is transmitting
indicator of the remote 
controller active ?
Is indicator lamp of
indoor unit proper ?
Replace the 
PWB  with a 
new one.
Does beep sound
from the indoor unit ?
Using a tester,
measure the voltage
between terminals
of resistor R26
on the PWB ass'y.
Push the button "OI".
Are batteries of the
wireless remote controller 
proper ?
Replace the batteries 
with new ones.
Replace the wireless
remote controller.
When the signal is
received, does the voltage
change ?
Replace the PWB with a new 
one.
PWB is normal.
Inspect the outdoor unit.
NO
YES
NO
YES
Replace the photo 
detector unit with a new 
one.
NO
YES
AH-AP18CS
AH-AP24CS
AU-A18CS
AU-A24CS
18
The room is not cooled at all
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
Push the button "AUX." on 
the  indoor unit, for more than 5 sec.
Is the voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
Are the resistances
conformed Fig. 1 ?
Replace the thermistor ass'y 
with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
Fig. 1
Using a tester, measure voltage at
the terminals on the terminal board.
100
80
60
40
20
0
-10
0
10
20
30
40
Resistance
Thermistor
Room temperature
Heat exchange
Color
Yellow
Orange
To measure the resistance, first remove 
the connector as shown at right.
Room temperature 
thermistor TH1
Tester
Connector
No. 3 to 4
No. 1 to 2
Fig. 1 Temperature properties of  indoor thermistors
K
Heat exchange thermistor 
TH2 (orange)
25
°C resistance 15 K 
Room temperature 
thermistor TH1 (yellow)
25
°C resistance 10 K
Heat exchange 
thermistor TH2
Tester
4
1
CN4
The control circuit is normal.
   The compressor may be defective.
   The running capacitor may be 
   defective.
   Refrigerant may be leaked.
   The outdoor fan motor may be 
   defective.
   The outdoor fan motor capacitor 
   may be defective.
19
AH-AP18CS
AH-AP24CS
AU-A18CS
AU-A24CS
For AH-AP24CS / AU-A24CS
The room is not cooled at all
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
   The compressor may be defective.
   The running capacitor may be 
   defective.
   Refrigerant may be leaked.
   The outdoor fan motor may be 
   defective.
   The outdoor fan motor capacitor 
   may be defective.
Push the button " AUX." on  
the indoor unit, for more than 5 sec.
Is the voltage
between terminal of black 
lead wire on the relay in the outdoor unit 
and terminal "N"  on the terminal board the 
power suuply voltage ? 
Are the resistances
conformed Fig. 1 ?
Replace the thermistor 
ass'y with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
Using a tester, measure voltage at
the terminals on the terminal board.
Replace the relay in the outdoor unit with 
a new one.
Is the voltage
between terminal " N " and
" 2 " in the outdoor unit 
the power supply 
voltage ?
YES
NO
AH-AP18CS
AH-AP24CS
AU-A18CS
AU-A24CS
20
Cycle temperature and service port pressure
REFRIGERATION CYCLE
Figure R-1. Refrigeration Cycle for AH-AP18CS/AH-AP24CS
1
2
Capillary tube
3
Outdoor unit
Condenser
Evaporator
Indoor unit
Compressor
Flare coupling
Flare coupling
4
3-way
valve
2-way
valve
Accumulator
SASO condition
Dimension of Capillary tube
O.D.
I.D.
L
Capillary tube
ø 3.5
ø 2.2
900
O.D.
I.D.
L
Capillary tube 
ø 3.2
ø 2.0
700
AH-AP18CS
AH-AP24CS
Indoor side
Outdoor side
Temperature (˚C)
Temperature (˚C)
Relative humididity (%)
Relative humididity (%)
29
39
46
14
Cooling
AH-AP18CS
AH-AP24CS
Cooling
Cooling
Model
NO. Condition
SASO Cooling Condition (at 220V refrigerant pipes length 7.5m)
1
2
3
4
Service port pressure
104˚C
103˚C
55˚C
52˚C
14˚C
23˚C
6˚C
6˚C
0.56MPa
0.59MPa
Page of 36