Sharp AE-XM18CR (serv.man9) Service Manual ▷ View online
35
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
AY-XPM7/9/12CR
AE-XM18/24CR
TIPS ABOUT INDICATOR PANEL
The indicator panel will change each time you press
the DISPLAY button in the following manner.
the DISPLAY button in the following manner.
The room
temperature and
POWER MONITOR
are displayed.
temperature and
POWER MONITOR
are displayed.
The outdoor
temperature and
POWER MONITOR
are displayed.
temperature and
POWER MONITOR
are displayed.
No display.
POWER MONITOR
When the room temperature or the outdoor temperature is displayed, the POWER MONITOR
will light up in 4 levels for COOL and HEAT modes (3 levels for DRY mode), to indicate the
operation power. When the air conditioner is operating at maximum power in the COOL and
HEAT modes, "POWER" will light and "ECO" will turn off on the indicator panel.
will light up in 4 levels for COOL and HEAT modes (3 levels for DRY mode), to indicate the
operation power. When the air conditioner is operating at maximum power in the COOL and
HEAT modes, "POWER" will light and "ECO" will turn off on the indicator panel.
NOTES:
• The displayed temperatures are rough estimates and may vary from the actual tempera-
tures.
• Temperature display ranges
Room temperature: 0
°C ~ 40°C ( is displayed when less than 0°C and when higher
than 40
°C)
Outdoor temperature: -9
°C ~ 45°C ( is displayed when less than -9°C and when
higher than 45
°C)
•
is displayed during the first 120 seconds of operation while the temperatures are being
detected. (Temperature detection may more than 120seconds when other unit(s) is/are
already being operated.)
already being operated.)
•
is displayed for 5 seconds when the unit is not in operation.
DISPLAY
FULL
POWER
ECO
ECO
Room Temp.
Lamp
Lamp
Outdoor Temp.
Lamp
Lamp
temperature
Indiactor
Indiactor
POWER
MONITOR
MONITOR
ECO
ECO
Room Temp. Lamp
Outdoor Temp. Lamp
temperature
Indiactor
Indiactor
POWER MONITOR
(AY-XPM7CR/AY-XPM9CR/AY-XPM12CR)
(AY-XM7CR/AY-XM9CR/AY-XM12CR)
36
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
AY-XPM7/9/12CR
AE-XM18/24CR
".
• The red OPERATION lamp (
The red OPERATION lamp (
Press the SELF CLEAN button when the unit is not
operating.
operating.
) and the blue
PLASMACLUSTER lamp on the unit will light up.
• The unit will stop operation after forty minutes.
• The remaining operation time will be indicated on the
• The remaining operation time will be indicated on the
TEMPERATURE INDICATOR of the indoor unit in
minute decrements.
minute decrements.
TO CANCEL
Press the SELF CLEAN button.
Or, turn the unit off by pressing the ON/OFF button.
Or, turn the unit off by pressing the ON/OFF button.
• The red OPERATION lamp (
),the blue
PLASMACLUSTER lamp and the TEMPERATURE
INDICATOR on the unit will turn off.
INDICATOR on the unit will turn off.
1
When the unit is in operation, press the
PLASMACLUSTER button to select the mode.
PLASMACLUSTER button to select the mode.
PLASMACLUSTER AUTO
AIR CLEAN
REFRESHING
CANCEL
• In the AIR CLEAN operation, the blue
PLASMACLUSTER lamp on the unit will light up.
• In the REFRESHING operation, the green
PLASMACLUSTER lamp on the unit will light up.
TO CANCEL
Press the PLASMACLUSTER button until
PLASMACLUSTER symbol on the remote control
display goes off.
PLASMACLUSTER symbol on the remote control
display goes off.
• The PLASMACLUSTER lamp on the unit will turn off.
NOTE
:
• You cannot set the temperature, fan speed, air flow direction or timer setting during the SELF
CLEAN operation.
1
SWING
CLEAN
FAN
SET/C
AM
NOTES:
You can choose PLASMACLUSTER AUTO OPERATION, AIR CLEAN OPERATION or
REFRESHING OPERATION
REFRESHING OPERATION
• Setting of the PLASMACLUSTER operation will be memorized and will operate in the same
mode, the next time you turn on the air conditioner.
• To turn off the PLASMACLUSTER lamp, press the DISPLAY button.
• When the PLASMACLUSTER button is pressed while the unit is not operating, the
• When the PLASMACLUSTER button is pressed while the unit is not operating, the
PLASMACLUSTER operation will be performed without accompanying air conditioning mode
(eg. HEATING or COOLING).The mode symbol of the remote control will go off and the fan
speed can not be set AUTO. At this time, you may feel HEATING is performed with units in other
rooms. Indoor fan will decrease its rotating speed and will ture ON and OFF depending on the
room temperature.
(eg. HEATING or COOLING).The mode symbol of the remote control will go off and the fan
speed can not be set AUTO. At this time, you may feel HEATING is performed with units in other
rooms. Indoor fan will decrease its rotating speed and will ture ON and OFF depending on the
room temperature.
SWING
CLEAN
FAN
MODE
SET/C
1h
AM
AUTO
PLASMACLUSTER OPERATION
SELF CLEAN OPERATION
1
1
(only for models AY-XPM7CR/AY-XPM9CR/AY-XPM12CR)
(only for models AY-XPM7CR/AY-XPM9CR/AY-XPM12CR)
37
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
AY-XPM7/9/12CR
AE-XM18/24CR
The ionizer inside the air conditioner will release cluster ions, which are
collective mass of positive and negative ions, into the room.
The cluster ions reduce airborne mold fungus and deodorize/decompose odor-
causing molecules.
collective mass of positive and negative ions, into the room.
The cluster ions reduce airborne mold fungus and deodorize/decompose odor-
causing molecules.
AIR CLEAN OPERATION
Cluster ions released into the air will reduce airborne mold fungus and deodorize/decompose
odor-causing molecules.
odor-causing molecules.
REFRESHING OPERATION
It is said that plenty of negative ions exist in places such as waterfalls or forests in natural
environment. In this operation mode, negative inos will be released in an increased rate, in order
to bring the room air close to this condition.
environment. In this operation mode, negative inos will be released in an increased rate, in order
to bring the room air close to this condition.
PLASMACLUSTER AUTO OPERATION
Dust sensor and odor sensor will detect foul air in the room.
Air Clean Operation will be performed for one minute after the air conditioner is operated to
detect foul air.
Air Clean Operation and Refreshing Operation will be selected and be performed automatically
depending on the air foul degree.
Air Clean Operation will be performed when the air is detected to be foul, Refreshing Operation
will be performed when the air is clean.
Air Clean Operation will be performed for one minute after the air conditioner is operated to
detect foul air.
Air Clean Operation and Refreshing Operation will be selected and be performed automatically
depending on the air foul degree.
Air Clean Operation will be performed when the air is detected to be foul, Refreshing Operation
will be performed when the air is clean.
SELF CLEAN OPERATION
Plasmacluster Operation will be performed with FAN or HEAT mode, in order to reduce the
growth of mold fungus, and dry inside of the air conditioner unit.
Utilize the operation at seasonal change over terms.
Mold fungus already grown can not be eliminated by this operation.
growth of mold fungus, and dry inside of the air conditioner unit.
Utilize the operation at seasonal change over terms.
Mold fungus already grown can not be eliminated by this operation.
Ionizer
Cluster ions
Mold fungus
Odor
Odor
TIPS ABOUT PLASMACLUSTER OPERATION
(only for models AY-XPM7CR/AY-XPM9CR/AY-XPM12CR)
38
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
AY-XPM7/9/12CR
AE-XM18/24CR
2.OUTDOOR UNIT
2-1 FREQUENCY CONTROL
(1) AC current peak control
(1) AC current peak control
Cooling MODE
Heating MODE
14.0A
14.0A
(2) Prevention control of outdoor heat exchanger
overheating
If the temperature of the outdoor heat exchanger
exceeds the overheating prevention line 1or 2
during cooling, the operating frequency is
lowered by approximately 5 to 15Hz.
After that, the frequency is lowered
approximately 5Hz once every 60 seconds or
approximately 15Hz once every 120 seconds.
When the temperature of the outdoor heat
exchanger goes below the overheating
prevention clear line, the frequency is raised by
approximately 5Hz once every 60 seconds, and
normal operation is restored.
If the frequency is lowered to minimum
frequency without the temperature of the outdoor
heat exchanger decreasing and this condition
lasts for 1 minute, the compressor will be
stopped.
If the temperature of the outdoor heat exchanger
exceeds the overheating prevention line 1or 2
during cooling, the operating frequency is
lowered by approximately 5 to 15Hz.
After that, the frequency is lowered
approximately 5Hz once every 60 seconds or
approximately 15Hz once every 120 seconds.
When the temperature of the outdoor heat
exchanger goes below the overheating
prevention clear line, the frequency is raised by
approximately 5Hz once every 60 seconds, and
normal operation is restored.
If the frequency is lowered to minimum
frequency without the temperature of the outdoor
heat exchanger decreasing and this condition
lasts for 1 minute, the compressor will be
stopped.
Overheating Prevention line 1
Overheating Prevention line 2
Lower 5Hz once every 60 seconds
Lower 15Hz once every 120 seconds
Overheating Prevention clear line
55˚C
57˚C
54˚C
(3) Prevention control of compressor overheating
If the temperature of the compressor exceeds
approximately 108ÅãC, the operating frequency
is lowered approximately 5Hz.
After that, the frequency is lowered
approximately 5Hz once every 60 seconds.
When the compressor temperature drops below
approximately 108ÅãC, the frequency is raised
approximately 5Hz once every 60 seconds, and
normal operation is restored.
If the frequency is lowered to minimum
frequency without the temperature of the
compressor decreasing,and this condition lasts
for 1 minute, the compressor will be stopped.
approximately 108ÅãC, the operating frequency
is lowered approximately 5Hz.
After that, the frequency is lowered
approximately 5Hz once every 60 seconds.
When the compressor temperature drops below
approximately 108ÅãC, the frequency is raised
approximately 5Hz once every 60 seconds, and
normal operation is restored.
If the frequency is lowered to minimum
frequency without the temperature of the
compressor decreasing,and this condition lasts
for 1 minute, the compressor will be stopped.
(4) Prevention control of indoor heat exchanger
overheating
< for 2 minutes since 2room ON 1room ON >
If the temperature of any of indoor heat exchangers
exceeds the overheating prevention line 1 or 2
during heating, the operating frequency is lowered to
minimum frequency.
When the temperature of all of indoor heat
exchangers go below the overheating prevention
line 1, the frequency is raised by approximately 5Hz
once every 60 seconds, and normal operation is
restored.
If the condition that the frequency is minimum lasts
for 1 min, the compressor will be stopped.
If the temperature of any of indoor heat exchangers
exceeds the overheating prevention line 1 or 2
during heating, the operating frequency is lowered to
minimum frequency.
When the temperature of all of indoor heat
exchangers go below the overheating prevention
line 1, the frequency is raised by approximately 5Hz
once every 60 seconds, and normal operation is
restored.
If the condition that the frequency is minimum lasts
for 1 min, the compressor will be stopped.
< when normal >
If the temperature of any of indoor heat exchangers
exceeds the overheating prevention line 1 or 2
during heating, the operating frequency is lowered
by approximately 5 to 15Hz.
After that, the frequency is lowered approximately
5Hz once every 60 seconds or approximately 15Hz
once every 90 seconds.
When the temperature of all of indoor heat
exchangers go below the overheating prevention
line 1, the frequency is raised by approximately 5Hz
once every 60 seconds, and normal operation is
restored.
If the condition that the frequency is minimum lasts
for 1 min, the compressor will be stopped.
If the temperature of any of indoor heat exchangers
exceeds the overheating prevention line 1 or 2
during heating, the operating frequency is lowered
by approximately 5 to 15Hz.
After that, the frequency is lowered approximately
5Hz once every 60 seconds or approximately 15Hz
once every 90 seconds.
When the temperature of all of indoor heat
exchangers go below the overheating prevention
line 1, the frequency is raised by approximately 5Hz
once every 60 seconds, and normal operation is
restored.
If the condition that the frequency is minimum lasts
for 1 min, the compressor will be stopped.
2-2 OVER CURRENT PROTECTION
DC over current detection, AC over current
detection
To protect against over current due to sudden
change in load, the compressor is stopped if 55A
DC is exceeded in the DC section. If the set
value of AC current is exceeded in the AC
section, the compressor is stopped. 90 seconds
after the compressor has been stopped, another
starting try will be made.
Three retries are allowed. On the fourth retry, a
complete stop request signal is sent to the
indoor unit, and the outdoor unit will remain
stopped until the indoor operation is stopped.
DC over current is detected by the power
module. AC over current is detected by CT1, on
the outdoor PWB.
detection
To protect against over current due to sudden
change in load, the compressor is stopped if 55A
DC is exceeded in the DC section. If the set
value of AC current is exceeded in the AC
section, the compressor is stopped. 90 seconds
after the compressor has been stopped, another
starting try will be made.
Three retries are allowed. On the fourth retry, a
complete stop request signal is sent to the
indoor unit, and the outdoor unit will remain
stopped until the indoor operation is stopped.
DC over current is detected by the power
module. AC over current is detected by CT1, on
the outdoor PWB.
The set value of AC current
16.0A
Cooling mode
Heating mode
16.0A
When
ON
ON
When
OFF
OFF
Overheat
prevention line 2
prevention line 2
Overheat
prevention line 1
prevention line 1
Overheat
prevention line 2
prevention line 2
Overheat
prevention line 1
prevention line 1
~ 25Hz
25 ~
35Hz
35Hz
35 ~
95Hz
95Hz
95Hz ~
47.0˚C
45.0˚C
60.0˚C
57.0˚C
54.0˚C
52.0˚C
63.0˚C
59.0˚C
56.0˚C
54.0˚C
64.0˚C
60.0˚C
55.0˚C
53.0˚C
62.0˚C
58.0˚C
2-3 COMPRESSOR PROTECTION CONTROL
If the temperature of the compressor exceeds
113 ˚C, the compressor is stopped.
In this case, the outdoor fan is not stopped until the
temperature of compressor drops below 99ÅãC.
In 90 seconds after the compressor is stopped, if the
temperature is below 90ÅãC, another starting try will
be made. Three retries are allowed. On the fourth
retry, a complete stop request signal is sent to the
indoor unit, and the outdoor unit will remain stopped
until the indoor operation is stopped.
113 ˚C, the compressor is stopped.
In this case, the outdoor fan is not stopped until the
temperature of compressor drops below 99ÅãC.
In 90 seconds after the compressor is stopped, if the
temperature is below 90ÅãC, another starting try will
be made. Three retries are allowed. On the fourth
retry, a complete stop request signal is sent to the
indoor unit, and the outdoor unit will remain stopped
until the indoor operation is stopped.