Sharp AE-XM18CR (serv.man10) Service Manual ▷ View online
41
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
AY-XPM7/9/12CR
AE-XM18/24CR
FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
NO.
1
2
3
4
5
6
7
Function
Operation
Description
Operation is stopped if rotation
pulse signal is not input from the
indoor fan motor for 1 minute.
pulse signal is not input from the
indoor fan motor for 1 minute.
Operation is stopped if rotation
pulse signal from the indoor fan
indicates low rpm (approximately
300 rpm or less).
pulse signal from the indoor fan
indicates low rpm (approximately
300 rpm or less).
Expansion valve is closed if the
temperature stays below 2˚C for
4 minutes.
temperature stays below 2˚C for
4 minutes.
Compressor is stopped if a current
approximately 55A or more flows in
the power transistor module.
Compressor is also stopped if the
temperature of the power transistor
module exceeds 100˚C
approximately 55A or more flows in
the power transistor module.
Compressor is also stopped if the
temperature of the power transistor
module exceeds 100˚C
Lowers the operating frequency if
the compressor AC current exceeds
set value( ). Stops the compressor
if the current exceeds at minimum
frequency.
the compressor AC current exceeds
set value( ). Stops the compressor
if the current exceeds at minimum
frequency.
Lowers the operating frequency if
the temperature of the compressor
thermistor (TH1) rises above 108˚C.
Compressor is stopped if the
thermistor stays above 108˚C for
1 minute at minimum frequency.
the temperature of the compressor
thermistor (TH1) rises above 108˚C.
Compressor is stopped if the
thermistor stays above 108˚C for
1 minute at minimum frequency.
Compressor is stopped if the
compressor thermistor is above
113˚C. (Or when TH1 shorts)
compressor thermistor is above
113˚C. (Or when TH1 shorts)
Lowers the operating frequency if
the temperature of the outdoor heat
exchanger rises above 56˚C during
cooling. Stops the compressor if the
temperature stays above 56˚C for
1 minute at minimum frequency
the temperature of the outdoor heat
exchanger rises above 56˚C during
cooling. Stops the compressor if the
temperature stays above 56˚C for
1 minute at minimum frequency
Indoor fan
lock
lock
Indoor fan
rpm error
rpm error
Indoor
freezing
prevention
freezing
prevention
DC over
current
current
AC over
current
current
Compressor
overheat
prevention
control
overheat
prevention
control
Compressor
high
temperature
error
high
temperature
error
Outdoor
heat
exchanger
overheat
prevention
control
heat
exchanger
overheat
prevention
control
Detection time
When indoor
fan is rotating
fan is rotating
When indoor
fan is rotating
and stops
fan is rotating
and stops
During cooling
operation
operation
During
compressor
operation
compressor
operation
During
compressor
operation
compressor
operation
During
compressor
operation
compressor
operation
During
compressor
operation
compressor
operation
During
compressor
operation
compressor
operation
Restart condition Restart
time
No limit
Opearation OFF
Automatically
restarts when the
heat exchanger
temperature rises
above the freezing
prevention
temperature
(above 2˚C)
restarts when the
heat exchanger
temperature rises
above the freezing
prevention
temperature
(above 2˚C)
Automatically
restarts after safety
time(90 seconds)
restarts after safety
time(90 seconds)
Automatically
restarts after safety
time (90 seconds)
restarts after safety
time (90 seconds)
Automatically
restarts after safety
time (90 seconds)
restarts after safety
time (90 seconds)
Automatically
restarts when
thermistor (TH1)
temperature falls
below 99˚C
(approximately
30 minutes)
restarts when
thermistor (TH1)
temperature falls
below 99˚C
(approximately
30 minutes)
Automatically
restarts after safety
time (90 seconds)
restarts after safety
time (90 seconds)
In
door
door
Out
door
door
Yes
No
No limit
No
No
8 times Yes
Yes
8 times
Yes
Yes
No limit
No
No
8 times Yes
Yes
No limit
No
No
Cooling MODE
Heating MODE
14.0A
14.0A
42
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
AY-XPM7/9/12CR
AE-XM18/24CR
8
9
10
11
12
Compressor ia stopped, if heat
exchanger or outdoor thermistor
shorts.
Close the expansion valve of the
corresponding room, if some
suction thermistor shorts.
exchanger or outdoor thermistor
shorts.
Close the expansion valve of the
corresponding room, if some
suction thermistor shorts.
Compressor is stopped, if
compressor or heat exchanger or
outdoor thermistor opens.
Close the expansion valve of the
corresponding room, if some
suction thermistor shorts. opens.
compressor or heat exchanger or
outdoor thermistor opens.
Close the expansion valve of the
corresponding room, if some
suction thermistor shorts. opens.
Compressor is stopped, if the
operating frequency is above 70Hz
and the compressor current is
below 0.8A.
operating frequency is above 70Hz
and the compressor current is
below 0.8A.
INDOOR
If open, while timer LED blinks,
operation is continued.
If short, operation is continued.
OUTDOOR
Closes the expansion valve of the
corresponding room if the
outdoor unit does not receive a
serial signal from one or more
indoor unit for 30 seconds.
Compressor is stopped, if the
outdoor unit does not receive a
serial signal from all indoor units.
If open, while timer LED blinks,
operation is continued.
If short, operation is continued.
OUTDOOR
Closes the expansion valve of the
corresponding room if the
outdoor unit does not receive a
serial signal from one or more
indoor unit for 30 seconds.
Compressor is stopped, if the
outdoor unit does not receive a
serial signal from all indoor units.
Compressor is stopped, and
miswiring check operation ends.
miswiring check operation ends.
Thermistor
short
short
Thermistor
open
open
AC
abnormal
current
abnormal
current
Serial signal
error
error
Miswiring
check error
check error
When the room
is activated
turns ON and
the compressor
starts.
is activated
turns ON and
the compressor
starts.
When the room
turns ON
and the
compressor
starts.
turns ON
and the
compressor
starts.
During
compressor
operation
compressor
operation
During
operation
operation
During
miswiring
operation
miswiring
operation
Operation OFF
Operation OFF
Automatically
restarts after safety
time(90 seconds)
restarts after safety
time(90 seconds)
Automatically
restarts as soon as
the serial
communication
becomes possible.
restarts as soon as
the serial
communication
becomes possible.
Miswiring check
operation will not
restart automatically.
operation will not
restart automatically.
1 time
Yes
Yes
1 time
Yes
Yes
8 times
Yes
Yes
No limit
Yes
Yes
8 times
Yes
Yes
13
Lowers the operating frequency if
the temperature of any of indoor
heat exchanger rises high
temperature during heating.
Stops the compressor if the
temperature srays high for 1 minute
at minumum frequency.
the temperature of any of indoor
heat exchanger rises high
temperature during heating.
Stops the compressor if the
temperature srays high for 1 minute
at minumum frequency.
Indoor heat
exchanger
overheat
prevention
control
exchanger
overheat
prevention
control
During
compressor
operation
compressor
operation
Automatically
restarts after
safety time.(90 sec.)
restarts after
safety time.(90 sec.)
Automatically
restarts after
safety time.(90 sec.)
restarts after
safety time.(90 sec.)
Automatically
restarts after
safety time.(90 sec.)
restarts after
safety time.(90 sec.)
No limit
No
No
14
When a power factor module error
input is detected.
input is detected.
Power factor
module
(Active filter)
error
module
(Active filter)
error
During
compressor
operation
compressor
operation
During
compressor
operation
compressor
operation
8 times
Yes
Yes
15
In the case that the feed back signal
from the compressor is not input or
abnormal.
from the compressor is not input or
abnormal.
DC
Compressor
rotation
error
Compressor
rotation
error
8 times
Yes
Yes
NO. Function
Operation
Description
Detection time Restarts condition Restarts
time
In
door
door
Out
door
door
Display