DOWNLOAD Sharp AE-X08 (serv.man19) Service Manual ↓ Size: 1.16 MB | Pages: 2 in PDF or view online for FREE

Model
AE-X08 (serv.man19)
Pages
2 Few pages! See other manuals at the bottom of the first or last page.
Size
1.16 MB
Type
PDF
Document
Service Manual / Technical Bulletin
Brand
Device
Air Conditioner / Air conditioner stops and shows error code 14 on display unit.
File
ae-x08-sm19.pdf
Date

Sharp AE-X08 (serv.man19) Service Manual / Technical Bulletin ▷ View online

AIR2002 10 01
Month of Issue:  
October 2002
        
Classification: 
White
AIR CONDITIONER TECHNICAL BULLETIN
Page 1 of 2
Sharp Electronics (UK) Limited
Reference EHH-157
Revision 1
White – Carry out as required
Yellow – Carry out as required and whenever the unit comes in for service
Red
Carry out on all units
MODELS
AEX08BE
AEX10BE
SYMPTOM
The air conditioner stops and shows error code “14” on the indoor unit display.
CAUSE
Due to the dispersion characteristic of the active filter and resultant distortion of the
power supply waveform, the active filter’s over-voltage protection circuit could be
activated intermittently.
ACTION
Change C8 from 1000μF 420V to 1500μF 420V.
REF NO
DESCRIPTION
NEW PART NUMBER
PRICE CODE
1-10
Capacitor (C8), 1500
µ
F 420V
RC-AZA046JBE0
BE
1-54
Capacitor clamp
LBNDKA099JBWZ
AS
PROCEDURE FOR CAPACITOR REPLACEMENT
1.  Remove the plug or cut off the breaker.
 CAUTION :
To avoid any electric
shock, leave the unit
disconnected for at least
10 minutes so that the
capacitor can discharge.
2. To ensure the complete discharge of
the original capacitor, short circuit the
red and blue lead wire terminals on the
power factor module.
Original capacitor
& capacitor clamp
1500!F capacitor
& capacitor clamp
Make short
Power factor module
AIR2002 10 01
Month of Issue:  
October 2002
        
Classification: 
White
AIR CONDITIONER TECHNICAL BULLETIN
Page 2 of 2
Sharp Electronics (UK) Limited
Reference EHH-157
Revision 1
White – Carry out as required
Yellow – Carry out as required and whenever the unit comes in for service
Red
Carry out on all units
3. Remove two screws holding the PWB
and unlock two spacers.
4.
Remove the screw holding the
capacitor band and remove the band.
5. Disconnect the lead wires.
6. Connect lead wires to 1500μF
capacitor as original and install with
new capacitor clamp using another
screw hole.
* The blue lead wire should be
connected to the white line side
terminal.
(Refer to the above picture.)
7. Re-assemble the unit.
Use this hole for new band fixing with the screw.
A screw
White line on the capacitor
Blue lead wire
Red lead wire
Two screws
Two spacers
Display

Sharp AE-X08 (serv.man19) Service Manual / Technical Bulletin ▷ Download

  • DOWNLOAD Sharp AE-X08 (serv.man19) Service Manual ↓ Size: 1.16 MB | Pages: 2 in PDF or view online for FREE
  • Here you can View online or download the Service Manual / Technical Bulletin for the Sharp AE-X08 (serv.man19) in PDF for free, which will help you to disassemble, recover, fix and repair Sharp AE-X08 (serv.man19) Air Conditioner. Information contained in Sharp AE-X08 (serv.man19) Service Manual / Technical Bulletin (repair manual) includes:
  • Disassembly, troubleshooting, maintenance, adjustment, installation and setup instructions.
  • Schematics, Circuit, Wiring and Block diagrams.
  • Printed wiring boards (PWB) and printed circuit boards (PCB).
  • Exploded View and Parts List.